444 questions
A 30-ampere branch circuit supplies several outlets for utilization equipment. What is the maximum rating of any one cord-and-plug-connected utilization equipment on this circuit?
- a.12 A
- b.16 A
- c.24 A✓
- d.30 A
On a 30-ampere multiple-outlet circuit, any one cord-and-plug-connected utilization equipment may not exceed 80 percent of the circuit rating: 30 x 0.8 = 24 amperes. The 12 and 16 ampere values are the limits for 15- and 20-ampere receptacles, and 30 amperes would load one appliance to the full circuit rating. Table 210.21(B)(2) shows the same 24 ampere limit for a 30-ampere receptacle. See 210.23(C).2026 NEC §210.23(C)
What is the smallest conductor size generally permitted to be installed in parallel?
- a.250 kcmil
- b.2 AWG
- c.4/0 AWG
- d.1/0 AWG✓
Conductors of 1/0 AWG and larger may be run in parallel when the paralleled sets are the same length, material, size and insulation type and terminate in the same manner. Sizes smaller than 1/0, such as 2 AWG, are not permitted to be paralleled except in a few narrow special applications, and 4/0 or 250 kcmil are simply larger than the stated minimum.2026 NEC §310.10(G)
An outlet box used as the sole support of a ceiling-suspended paddle fan must meet what requirement?
- a.Any 4-inch box rated for 50 pounds is acceptable
- b.It must be listed and marked as suitable for supporting a fan, and it may support a fan of no more than 70 pounds✓
- c.It must be a nonmetallic box only
- d.No special outlet box is required as long as two long wood screws are driven through the box and directly into the structural framing member above
An outlet box may be the sole support of a ceiling-suspended paddle fan only if it is listed and marked by its manufacturer as suitable for that purpose, and it may not support more than 70 pounds. A box supporting more than 35 pounds must also be marked with the maximum weight (314.27(B)). A standard lighting outlet box is not rated for the dynamic load of a rotating fan.2026 NEC §314.27(B)
What is the maximum weight of a ceiling-suspended paddle fan that may be supported solely by a listed fan-rated outlet box without additional independent support?
- a.70 pounds✓
- b.50 pounds
- c.90 pounds
- d.35 pounds
A listed fan-rated outlet box may be the sole support of a fan weighing up to 70 pounds; a heavier fan must be supported independently of the box. See NEC 314.27(B)(1).2026 NEC §314.27(B)
A box contains six 12 AWG conductors, one internal cable clamp and one duplex receptacle, all 12 AWG. What minimum box volume is required?
- a.20.25 cubic inches✓
- b.13.5 cubic inches
- c.18.0 cubic inches
- d.22.5 cubic inches
Count six conductors, one allowance for all internal clamps and two allowances for the device yoke, giving 9 volume allowances. Each 12 AWG allowance is 2.25 cubic inches, so 9 x 2.25 = 20.25 cubic inches. Counting only the conductors gives 13.5 cubic inches, and forgetting that a yoke counts as two conductors gives 18.0 cubic inches.2026 NEC §314.16(B)
A device box has three 14-2 NM cables with equipment grounding conductors entering through internal clamps, and one single-pole switch is installed. What minimum box volume is required?
- a.20.0 cubic inches✓
- b.18.0 cubic inches
- c.16.0 cubic inches
- d.22.5 cubic inches
Six insulated conductors count individually, all equipment grounding conductors together count as one, all internal clamps together count as one, and the switch yoke counts as two, for 10 allowances. At 2.00 cubic inches for 14 AWG, 10 x 2.00 = 20.0 cubic inches. The 18.0 answer misses one allowance, 16.0 omits both the clamp and grounding allowances, and 22.5 uses the 12 AWG allowance by mistake.2026 NEC §314.16(B)
What is the minimum trade size of EMT required for nine 12 AWG THHN conductors?
- a.One-half inch✓
- b.Three-quarter inch
- c.One inch
- d.One and one-quarter inch
Chapter 9, Table 5 gives 0.0133 square inch for a 12 AWG THHN conductor, so nine take 9 x 0.0133 = 0.1197 square inch. With more than two conductors, Chapter 9, Table 1 limits fill to 40 percent. In Chapter 9, Table 4, one-half inch EMT allows 0.122 square inch at 40 percent, which is just enough. Three-quarter inch (0.213) and one inch (0.346) also work but are larger than the minimum.2026 NEC Chapter 9, Table 4
When more than two conductors are installed in a raceway, what is the maximum permitted percentage of the raceway cross-sectional area they may occupy?
- a.53 percent
- b.31 percent
- c.40 percent✓
- d.60 percent
Chapter 9, Table 1 allows 53 percent fill for one conductor, 31 percent for exactly two conductors and 40 percent for three or more. The 60 percent value applies only to a nipple not exceeding 24 inches in length between boxes or enclosures.2026 NEC Chapter 9, Table 1
A short raceway nipple no longer than 24 inches connects two enclosures. What fill percentage is permitted?
- a.31 percent
- b.40 percent
- c.53 percent
- d.60 percent✓
Notes to Chapter 9, Table 1 permit a nipple not exceeding 24 inches in length to be filled to 60 percent of its total cross-sectional area, because heat buildup and pulling friction are both minimal over such a short run. The 40, 53 and 31 percent values are the normal fills for three or more, one, and two conductors respectively.2026 NEC Chapter 9, Table 1, Note 4
Four 3/0 AWG THWN conductors, each 0.2679 square inch in area, are pulled into rigid metal conduit. What is the minimum trade size?
- a.2 inch✓
- b.1 and 1/2 inch
- c.2 and 1/2 inch
- d.1 and 1/4 inch
Total conductor area is 4 x 0.2679 = 1.0716 square inches, and with more than two conductors only 40 percent of the raceway may be filled. In Chapter 9, Table 4, one and one-half inch RMC allows 0.829 square inch at 40 percent, which is too little, while 2 inch RMC allows 1.363 square inches and is adequate. Two and one-half inch is larger than the calculated minimum.2026 NEC Chapter 9, Table 4
Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
What is the minimum cover for a direct-buried UF cable installed in a residential yard on a 120-volt, 20-ampere circuit that is NOT GFCI protected?
- a.18 inches
- b.24 inches✓
- c.12 inches
- d.6 inches
Direct-buried cables and conductors under all locations not otherwise covered require 24 inches of cover. The 12-inch reduction applies only to residential branch circuits rated 120 volts or less, 20 amperes or less, and provided with GFCI protection, so removing the GFCI removes the reduction. The 6-inch value belongs to rigid and intermediate metal conduit, and the 18-inch value to nonmetallic raceways listed for direct burial.2026 NEC Table 300.7(A)
What is the minimum burial cover for rigid metal conduit installed underground in a location not otherwise specified?
- a.18 inches
- b.12 inches
- c.6 inches✓
- d.24 inches
Rigid metal conduit and intermediate metal conduit are permitted at 6 inches of cover because the metal wall provides its own physical protection. Nonmetallic raceways listed for direct burial require 18 inches, direct-buried cable requires 24 inches, and 12 inches applies to GFCI-protected residential branch circuits.2026 NEC Table 300.7(A)
What is the minimum burial cover for a nonmetallic raceway listed for direct burial without concrete encasement, installed under a lawn?
- a.18 inches✓
- b.6 inches
- c.24 inches
- d.12 inches
Listed nonmetallic raceways buried without concrete encasement require 18 inches of cover in locations not otherwise specified. Rigid and intermediate metal conduit need only 6 inches, direct-buried cable needs 24 inches, and 12 inches applies to GFCI-protected 120-volt residential branch circuits.2026 NEC Table 300.7(A)
A GFCI-protected 120-volt, 20-ampere residential branch circuit is direct buried in a yard. What is the minimum cover?
- a.18 inches
- b.6 inches
- c.12 inches✓
- d.24 inches
Residential branch circuits rated 120 volts or less and 20 amperes or less that have GFCI protection may be buried with only 12 inches of cover, because a ground fault from a dig-in will clear immediately. Without GFCI protection the general 24-inch requirement applies. The 6-inch value belongs to rigid and intermediate metal conduit, and the 18-inch value to nonmetallic raceways listed for direct burial.2026 NEC Table 300.7(A)
What is the maximum total amount of bend permitted in one run of EMT between pull points?
- a.270 degrees
- b.180 degrees
- c.360 degrees✓
- d.540 degrees
No more than the equivalent of four quarter bends, or 360 degrees total, is permitted between pull points such as conduit bodies and boxes, because friction rises sharply with each bend. Section 300.24 states this limit once for every conduit and tubing wiring method, so it applies to EMT.2026 NEC §300.24
A cable passes through a bored hole in a wood stud. If the edge of the hole is less than 1 and 1/4 inches from the nearest edge of the stud, what is required?
- a.The cable must be removed and rerouted through a notch cut into the edge of the wood stud rather than the bored hole
- b.A steel plate or bushing at least 1/16 inch thick installed to protect the cable✓
- c.A listed nonmetallic sleeve of any thickness
- d.Nothing additional is required, provided that the cable installed in the bored hole is Type MC or Type AC armored cable
When the required 1 and 1/4-inch setback cannot be maintained, a steel plate or bushing at least 1/16 inch thick must cover the area of the wiring so a drywall screw or nail cannot reach it. Notching is more damaging to the stud and creates the same exposure, and nonmetallic sleeves do not satisfy this rule.2026 NEC §300.6(A)(1)
A pull box is used for a straight pull, and the largest raceway entering it is 3 inch trade size. What is the minimum required length of the box in the direction of the pull?
- a.18 inches
- b.24 inches✓
- c.12 inches
- d.36 inches
For straight pulls, the box length must be at least eight times the trade size of the largest raceway: 8 x 3 = 24 inches. The 18-inch answer uses a factor of six, which applies to angle and U pulls, and 12 inches uses a factor of four that appears nowhere in the rule.2026 NEC §314.28(A)(1)
An angle pull box has one 2-inch raceway and one 1-inch raceway entering the same wall, with conductors turning 90 degrees. What is the minimum distance from that wall to the opposite wall?
- a.24 inches
- b.12 inches
- c.16 inches
- d.13 inches✓
For angle pulls the distance is six times the trade size of the largest raceway plus the sum of the diameters of the other raceways on the same wall: (6 x 2) + 1 = 13 inches. The 12-inch answer forgets to add the additional raceway, and 24 inches applies the straight-pull factor of eight.2026 NEC §314.28(A)(2)
How many 12 AWG conductors may be installed in a 4-11/16 inch by 2-1/8 inch square box with a volume of 42.0 cubic inches, assuming no clamps, devices or fittings?
- a.21
- b.20
- c.16
- d.18✓
Each 12 AWG conductor requires 2.25 cubic inches, so 42.0 / 2.25 = 18.67, and the count must be rounded down to 18 whole conductors. The 21-conductor answer uses the 14 AWG allowance of 2.00 cubic inches, and 20 and 16 do not follow from dividing the box volume by 2.25.2026 NEC §314.16(A)
Direct-buried conductors emerging from grade must be protected by an approved enclosure or raceway from below grade to what height?
- a.8 feet above finished grade✓
- b.6 feet above finished grade
- c.10 feet above finished grade
- d.4 feet above finished grade
Protection must extend from the required burial depth below grade to at least 8 feet above finished grade. The protection below grade never has to go deeper than 18 inches. Six feet leaves the conductors within easy reach of damage, and neither 4 nor 10 feet is the code value.2026 NEC §300.7(D)(1)
What is the maximum fill percentage when exactly two conductors are installed in a raceway?
- a.40 percent
- b.31 percent✓
- c.53 percent
- d.60 percent
Two conductors are limited to 31 percent fill, a lower figure than the 40 percent allowed for three or more, because two round conductors of similar size can jam in a bend and damage insulation during the pull. One conductor may fill 53 percent, and 60 percent applies only to a nipple 24 inches or shorter.2026 NEC Chapter 9, Table 1
What is the minimum trade size of EMT required for twenty-four 12 AWG THHN conductors?
- a.One inch✓
- b.Three-quarter inch
- c.One and one-quarter inch
- d.One and one-half inch
Chapter 9, Table 5 gives 0.0133 square inch for a 12 AWG THHN conductor, so twenty-four take 24 x 0.0133 = 0.3192 square inch. In Chapter 9, Table 4, three-quarter inch EMT allows only 0.213 square inch at 40 percent fill and is too small, while one inch EMT allows 0.346 square inch and is adequate. Remember that twenty-four current-carrying conductors would also be adjusted to 45 percent of their ampacity under Table 310.15(C)(1).2026 NEC Chapter 9, Table 4
Conductors installed in an underground raceway in a wet location must have which characteristic?
- a.A nylon jacket, which by itself qualifies the conductor for wet locations
- b.Any thermoplastic insulation, since the raceway keeps water out
- c.Insulation rated 90 degrees C, regardless of wet-location listing
- d.Insulation listed for use in wet locations, such as THWN or THWN-2✓
Raceways in underground and other wet locations are considered wet inside, so the conductors must carry a wet-location listing such as THWN, THWN-2 or XHHW. The W in the type designation is what matters; plain THHN without the dual THWN-2 marking is a dry- and damp-location conductor, and a temperature rating or nylon jacket alone does not confer a wet-location listing.2026 NEC §310.10(C)
A junction box contains four 14 AWG conductors and two 12 AWG conductors, with no devices, clamps or fittings. What minimum box volume is required?
- a.12.5 cubic inches✓
- b.13.5 cubic inches
- c.11.0 cubic inches
- d.15.0 cubic inches
Each conductor is counted at the volume allowance for its own size: four 14 AWG at 2.00 cubic inches is 8.0, and two 12 AWG at 2.25 cubic inches is 4.5, for a total of 12.5 cubic inches. Using 2.25 for every conductor gives the incorrect 13.5 figure.2026 NEC §314.16(B)(1)
Type NM (nonmetallic-sheathed) cable is NOT permitted in which of the following?
- a.Wet or damp locations✓
- b.The framed walls of a one-family dwelling
- c.An exposed dry run in the basement of a dwelling
- d.A concealed dry run in an attic
Type NM cable is permitted for exposed and concealed work only in normally dry locations, so it may not be used in wet or damp locations. It remains a standard method for the dry, concealed and exposed interior wiring of dwellings, which is what the other three choices describe. See NEC 334.10(A)(1).2026 NEC §334.10(A)(1)
Flexible metal conduit (FMC) may serve as an equipment grounding conductor only where the total length in the ground-return path does not exceed 6 feet and which additional condition is met?
- a.The conduit is at least 1 inch trade size
- b.The circuit voltage does not exceed 50 volts
- c.The circuit conductors are protected at 20 amperes or less and the conduit terminates in listed fittings✓
- d.A separate equipment bonding jumper is installed on the outside of the conduit for its full length and terminated at both ends
Listed FMC qualifies as an equipment grounding conductor only when the ground-return length is 6 feet or less, the overcurrent protection is 20 amperes or less, the conduit is no larger than trade size 1 and 1/4, and it terminates in listed fittings. Where any of these limits is exceeded, a separate equipment grounding conductor must be installed. See NEC 250.118(A)(5).2026 NEC §250.118(A)(5)
A box or conduit body installed in a wet location must meet which requirement?
- a.It may be any standard indoor box, provided that a weatherproof gasket is added between the box and the cover plate
- b.It must be completely filled with an approved duct seal compound to keep out all moisture and condensation
- c.It must be nonmetallic only
- d.It must be listed for wet locations and be installed so water cannot enter or accumulate within it✓
Boxes and fittings in damp or wet locations must be placed or equipped so water cannot enter or accumulate inside, and in wet locations they must be listed for that use. Both metallic and nonmetallic boxes are permitted if properly listed and installed, so material alone does not satisfy the rule.2026 NEC §314.15
A box contains six 14 AWG conductors, one internal cable clamp and one duplex receptacle wired with 14 AWG. What minimum box volume is required?
- a.16.0 cubic inches
- b.12.0 cubic inches
- c.20.25 cubic inches
- d.18.0 cubic inches✓
Count six conductors, one allowance for all internal clamps, and two allowances for the device yoke = 9 allowances. Each 14 AWG allowance is 2.00 cubic inches: 9 x 2.00 = 18.0. See 2026 NEC 314.16(B) and Table 314.16(B)(4).2026 NEC §314.16(B)
A device box has two 12-2 nonmetallic-sheathed cables with equipment grounding conductors entering through internal clamps, and one single-pole switch (12 AWG). What minimum box volume is required?
- a.18.0 cubic inches✓
- b.16.0 cubic inches
- c.20.25 cubic inches
- d.15.75 cubic inches
Four insulated 12 AWG conductors, the two grounding conductors as one, all clamps as one, and the switch yoke as two = 8 allowances. At 2.25 cubic inches each: 8 x 2.25 = 18.0. See 2026 NEC 314.16(B) and Table 314.16(B)(4).2026 NEC §314.16(B)
How many 12 AWG conductors may be installed in a 22.5-cubic-inch box with no clamps, devices or fittings?
- a.9
- b.10✓
- c.12
- d.11
Each 12 AWG conductor requires 2.25 cubic inches: 22.5 / 2.25 = 10 conductors exactly. See 2026 NEC 314.16(B)(1) and Table 314.16(B)(4).2026 NEC Table 314.16(B)(4)
How many 14 AWG conductors may be installed in an 18.0-cubic-inch box with no clamps, devices or fittings?
- a.12
- b.10
- c.8
- d.9✓
Each 14 AWG conductor requires 2.00 cubic inches: 18.0 / 2.00 = 9 conductors. See 2026 NEC 314.16(B)(1) and Table 314.16(B)(4).2026 NEC Table 314.16(B)(4)
What is the minimum trade size of EMT required for sixteen 12 AWG THHN conductors?
- a.One-half inch
- b.One inch
- c.Three-quarter inch✓
- d.One and one-quarter inch
Each 12 AWG THHN conductor is 0.0133 square inch, so sixteen take 16 x 0.0133 = 0.2128 square inch. More than two conductors are limited to 40 percent fill. One-half-inch EMT allows 0.122 square inch at 40 percent and is too small; three-quarter-inch EMT allows 0.213 square inch and just fits. See 2026 NEC Chapter 9, Tables 1, 4 and 5.2026 NEC Chapter 9, Tables 1, 4 and 5
When exactly one conductor is installed in a conduit or tubing, what is the maximum permitted fill percentage?
- a.40 percent
- b.31 percent
- c.53 percent✓
- d.60 percent
Chapter 9, Table 1 permits 53 percent fill for a single conductor, 31 percent for two, and 40 percent for more than two. See 2026 NEC Chapter 9, Table 1.2026 NEC Chapter 9, Table 1
Four 250 kcmil THWN conductors, each 0.3970 square inch, are pulled into EMT. What is the minimum trade size?
- a.3 inch
- b.1 and 1/2 inch
- c.2 inch
- d.2 and 1/2 inch✓
Total area = 4 x 0.3970 = 1.588 square inches, limited to 40 percent fill. Two-inch EMT allows 1.342 square inches and fails; 2 and 1/2-inch EMT allows 2.343 square inches and works. See 2026 NEC Chapter 9, Tables 1, 4 and 5.2026 NEC Chapter 9, Tables 1, 4 and 5
What is the maximum support spacing for a horizontal run of 1/2-inch trade size rigid metal conduit?
- a.10 feet✓
- b.6 feet
- c.5 feet
- d.12 feet
Rigid metal conduit is supported at intervals not exceeding 10 feet, and the support table gives the same 10 feet for the 1/2 and 3/4 inch sizes. It must also be fastened within 3 feet of each termination. See 2026 NEC 344.30(A) and (B) and Table 344.30(B).2026 NEC §344.30(B)
A cable is run through a notch cut in the edge of a wood stud. What is required to protect it?
- a.A plastic bushing of any thickness
- b.A steel plate at least 1/8 inch thick
- c.A steel plate at least 1/16 inch thick installed across the notch✓
- d.No protection if the cable is stapled at the notch
Where a cable is laid in a notch in a wood member, it must be covered by a steel plate at least 1/16 inch thick, put on before the wall finish, to guard it from nails and screws. See 2026 NEC 300.6(A)(2).2026 NEC §300.6(A)(2)
A pull box is used for a straight pull, and the largest raceway entering it is 4-inch trade size. What is the minimum length of the box in the direction of the pull?
- a.16 inches
- b.24 inches
- c.32 inches✓
- d.48 inches
For straight pulls the box length must be at least eight times the trade size of the largest raceway: 8 x 4 = 32 inches. See 2026 NEC 314.28(A)(1).2026 NEC §314.28(A)(1)
An angle pull box has a 3-inch raceway and a 2-inch raceway entering the same wall with conductors turning 90 degrees. What is the minimum distance from that wall to the opposite wall?
- a.13 inches
- b.20 inches✓
- c.24 inches
- d.18 inches
For angle pulls the distance is six times the largest raceway plus the sum of the other raceway sizes in the same row on the same wall: (6 x 3) + 2 = 20 inches. See 2026 NEC 314.28(A)(2).2026 NEC §314.28(A)(2)
What is the minimum burial cover for any wiring method installed directly beneath a public street, road or alley?
- a.12 inches
- b.6 inches
- c.18 inches
- d.24 inches✓
Under streets, highways, roads, alleys, driveways and parking lots, every column of the cover table calls for 24 inches. A separate row with smaller values applies only to driveways of one- and two-family dwellings. See 2026 NEC Table 300.7(A).2026 NEC Table 300.7(A)
Which of the following is a recognized equipment grounding conductor?
- a.Electrical nonmetallic tubing
- b.Rigid metal conduit installed under its article✓
- c.A nonmetallic pull string
- d.Rigid PVC conduit
Metal raceways such as rigid metal conduit, intermediate metal conduit and EMT are recognized equipment grounding conductors; nonmetallic raceways are not. See 2026 NEC 250.118(A).2026 NEC §250.118(A)
How many 12 AWG conductors may be installed in a 21.0-cubic-inch box with no clamps, devices or fittings?
- a.8
- b.10
- c.9✓
- d.11
Each 12 AWG conductor requires 2.25 cubic inches: 21.0 / 2.25 = 9.33, rounded down to 9 conductors. See 2026 NEC 314.16(B)(1) and Table 314.16(B)(4).2026 NEC Table 314.16(B)(4)
An underground raceway enters a building, and moisture passing through it could contact live parts. What is required?
- a.It must be sealed or plugged so that moisture cannot reach the live parts✓
- b.It must be left open for ventilation
- c.It must be filled completely with concrete
- d.It must be bonded but is never sealed
A conduit or raceway through which moisture could contact live parts must be sealed or plugged at one or both ends, and the sealant must be identified for use with the conductor insulation. See 2026 NEC 300.7(G).2026 NEC §300.7(G)
Under the exception that lets Type NM cable enter a single-gang nonmetallic box without being secured to the box, the cable must be fastened within what distance of the box?
- a.24 inches
- b.8 inches✓
- c.3 feet
- d.4 and 1/2 feet
Where a single-gang nonmetallic box not larger than nominal 2-1/4 in. x 4 in. is mounted in a wall or ceiling, the NM cable need not be secured to the box if it is fastened within 8 inches of the box, measured along the sheath, and the sheath extends through a cable knockout at least 1/4 inch. See 2026 NEC 314.17(B)(2) Exception.2026 NEC §314.17(B)(2) Exception
A junction box contains four 12 AWG and three 10 AWG conductors with no devices, clamps or fittings. What minimum box volume is required?
- a.16.5 cubic inches✓
- b.17.5 cubic inches
- c.14.0 cubic inches
- d.15.75 cubic inches
Each conductor is counted at the allowance for its own size: four 12 AWG at 2.25 = 9.0, and three 10 AWG at 2.50 = 7.5, for 16.5 cubic inches. See 2026 NEC 314.16(B)(1) and Table 314.16(B)(4).2026 NEC §314.16(B)(1)
What is the minimum trade size of EMT required for six 10 AWG THHN conductors?
- a.One inch
- b.Three-quarter inch✓
- c.One-half inch
- d.One and one-quarter inch
Each 10 AWG THHN conductor is 0.0211 square inch, so six take 6 x 0.0211 = 0.1266 square inch. More than two conductors are limited to 40 percent fill. One-half-inch EMT allows only 0.122 square inch at 40 percent and is too small; three-quarter-inch EMT allows 0.213 square inch and works. See 2026 NEC Chapter 9, Tables 1, 4 and 5.2026 NEC Chapter 9, Tables 1, 4 and 5
A metal outlet box is supplied by a wiring method that includes an equipment grounding conductor. How must the box be treated?
- a.It must be left isolated from ground
- b.It must be connected to the grounded neutral bar
- c.It must be connected to the equipment grounding conductor✓
- d.It need be bonded only in a wet location
A metal box must be grounded and bonded under the Article 250 rules, which here means connecting it to the equipment grounding conductor so a fault will clear. See 2026 NEC 314.6.2026 NEC §314.6
An insulated bushing or fitting to protect conductors from abrasion is required where conductors of what size or larger enter a raceway or enclosure?
- a.1 AWG
- b.4 AWG✓
- c.8 AWG
- d.6 AWG
Where a raceway contains insulated circuit conductors of 4 AWG or larger and they enter a cabinet, box, enclosure or raceway, they must be protected, for example by a fitting with a smoothly rounded insulating surface such as an insulating bushing. See 2026 NEC 300.6(G).2026 NEC §300.6(G)
In box-fill calculations, how is a device yoke or strap counted?
- a.As two conductor volume allowances, based on the largest conductor connected to the device✓
- b.It is not counted at all, because a device adds no conductors to the box
- c.As one conductor volume allowance, based on the largest conductor connected
- d.As two allowances, based on the smallest conductor connected to the device
Each yoke or strap holding a device or utilization equipment is counted as two conductor volume allowances, based on the largest conductor connected to it. See 2026 NEC 314.16(B)(4).2026 NEC §314.16(B)(4)
A 240-volt feeder is installed as direct-buried cable under the driveway of a single-family house. The driveway is used only for dwelling-related purposes. What is the minimum cover required?
- a.12 in.
- b.18 in.✓
- c.24 in.
- d.30 in.
Table 300.7(A) has a separate row for one- and two-family dwelling driveways used only for dwelling-related purposes, and the direct-burial column there shows 18 in. The 24 in. figure is for streets, highways, and other driveways and parking lots. The 12 in. figure in that row applies only to a residential branch circuit of 120 volts or less with GFCI protection and overcurrent protection of 20 amperes or less.2026 NEC Table 300.7(A)
Underground service conductors that are not encased in concrete are buried 24 in. below grade. A warning ribbon must be placed in the trench at least how far above the underground installation?
- a.12 in.✓
- b.18 in.
- c.24 in.
- d.30 in.
Section 300.7(D)(3) requires a warning ribbon in the trench at least 12 in. above underground service conductors that are not concrete-encased and are buried 18 in. or more below grade. The 18 in. figure is the burial depth that triggers the rule, not the ribbon spacing. The ribbon gives a digger notice before reaching the conductors.2026 NEC §300.7(D)(3)