A service supplies an installation consisting of not more than two 2-wire branch circuits. What is the minimum rating of the service disconnecting means?
- a.15 amperes
- b.30 amperes✓
- c.60 amperes
- d.100 amperes
Section 230.79(B) sets a 30 ampere minimum for installations of not more than two 2-wire branch circuits. The 15 ampere value is for a single branch circuit with limited load, 100 amperes is for a one-family dwelling, and 60 amperes is for all other installations.2026 NEC §230.79(B)
A ground ring used as a grounding electrode must be installed at least how far below the surface of the earth?
- a.12 in.
- b.18 in.
- c.24 in.
- d.30 in.✓
Section 250.53(F) requires the ground ring to be not less than 30 in. below the surface of the earth. The same 30 in. depth applies to plate electrodes in 250.53(A)(5). The 18 in. and 24 in. answers are common burial depths for wiring methods, not for this electrode.2026 NEC §250.53(F)
Which of the following is not permitted to be used as a grounding electrode?
- a.A metal in-ground support structure in contact with the earth vertically for 10 ft
- b.A ground ring of bare 2 AWG copper
- c.A plate electrode exposing 2 sq ft of surface to the soil
- d.A metal underground gas piping system✓
Section 250.52(B) lists metal underground gas piping systems among the items that may not be used as grounding electrodes. The other three choices are recognised electrodes in 250.52(A)(2), (A)(4) and (A)(7). Gas piping is still bonded under a separate rule, which is why it gets confused with an electrode.2026 NEC §250.52(B)
Where the main bonding jumper in a service panelboard is a screw only, how must the screw be identified?
- a.By a white or gray marking on the screw head
- b.By a tag reading BONDING attached next to the screw
- c.By a green finish that is visible with the screw installed✓
- d.By a listing mark stamped on the screw threads
Section 250.28(B) requires a main or system bonding jumper that is a screw only to have a green finish that can be seen with the screw installed. White or gray would suggest a grounded conductor, and a tag or a stamped mark is not what this section calls for.2026 NEC §250.28(B)
Service-entrance conductors supply 96 amperes of continuous lighting load, 24 amperes of continuous sign load, and 70 amperes of noncontinuous load. The service equipment is not listed for operation at 100 percent of its rating. Before any adjustment or correction factors, what minimum ampacity is required?
- a.190 A
- b.207.5 A
- c.220 A✓
- d.237.5 A
Section 230.42(A)(1) requires an ampacity of at least the noncontinuous load plus 125 percent of the continuous load. The continuous load is 96 + 24 = 120 amperes, so 70 + (1.25 x 120) = 70 + 150 = 220 amperes. The 190 ampere answer adds the loads with no factor, and 237.5 amperes applies 125 percent to everything.2026 NEC §230.42(A)(1)
A service has three disconnecting means as permitted by 230.71. The rating required for the service by 230.79 is 400 amperes. Two of the disconnects are rated 200 amperes and 100 amperes. What is the smallest rating the third disconnect may have for the combined rating to comply?
- a.100 A✓
- b.133 A
- c.200 A
- d.400 A
Section 230.80 requires the combined ratings of all the switches or circuit breakers to be not less than the rating required by 230.79. The first two total 200 + 100 = 300 amperes, so the third must supply at least 400 - 300 = 100 amperes. The 400 ampere answer treats each disconnect as if it had to carry the full rating alone.2026 NEC §230.80
Three pieces of bare 1/2 in. rebar, 8 ft, 6 ft and 5 ft long, are tied end to end with steel tie wires inside a concrete footing that is in direct contact with the earth. How much more connected rebar length is needed before this can qualify as a concrete-encased electrode?
- a.0 ft
- b.1 ft✓
- c.6 ft
- d.12 ft
Section 250.52(A)(3) requires at least 20 ft of rebar, and it allows multiple pieces connected by steel tie wires or similar effective means to make up that length. The pieces total 8 + 6 + 5 = 19 ft, so 1 ft more is needed. The 12 ft answer assumes the 20 ft must be a single bar added to the longest piece, which the section does not require.2026 NEC §250.52(A)(3)
A 480-volt, three-phase feeder carries 40 amperes 250 feet using 6 AWG copper (26,240 circular mils). Using K = 12.9, what is the approximate voltage drop?
- a.14.8 volts
- b.4.9 volts
- c.8.5 volts✓
- d.17.0 volts
For three-phase, VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 40 x 250) / 26,240, or about 8.5 volts, roughly 1.8 percent of 480 volts. The 4.9-volt answer leaves out the 1.732 multiplier, 14.8 volts applies it twice, and 17.0 volts doubles the correct result as if the run length were counted out and back.2026 NEC Chapter 9, Table 8
A feeder supplies 30 amperes of continuous load plus 50 amperes of noncontinuous load. What is the minimum standard overcurrent device rating?
- a.100 amperes
- b.80 amperes
- c.90 amperes✓
- d.110 amperes
The device must be sized for the noncontinuous load plus 125 percent of the continuous load: 50 + (30 x 1.25) = 87.5 A, and the next standard size in 240.6(A) is 90 A. The 80 A answer simply adds the loads without the 125 percent factor, and 100 A or 110 A skip past the next standard rating.2026 NEC §215.5
A feeder supplies a 100-ampere continuous load. Using 75 degrees C terminations and copper THWN, what is the minimum feeder conductor size?
- a.1 AWG✓
- b.2 AWG
- c.1/0 AWG
- d.3 AWG
The feeder conductor must have an ampacity of at least 100 x 1.25 = 125 A. In the 75 degrees C column, 2 AWG copper is 115 A and falls short, while 1 AWG copper is 130 A and satisfies the requirement. 1/0 AWG at 150 A is larger than necessary, and 3 AWG at 100 A does not cover the continuous-load multiplier.2026 NEC §215.4(A)(1)
Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
A 277-volt feeder supplies three continuous lighting loads of 12, 15 and 18 amperes. What is the minimum standard feeder overcurrent device rating?
- a.50 amperes
- b.45 amperes
- c.60 amperes✓
- d.70 amperes
Total the loads first: 12 + 15 + 18 = 45 A, all continuous, so the device must be at least 45 x 1.25 = 56.25 A and the next standard rating is 60 A. The 45 A answer omits the continuous-load factor, 50 A is below the calculated minimum, and 70 A overshoots the next standard size.2026 NEC §215.5
A feeder supplies a 45-ampere continuous lighting load. What is the minimum copper feeder conductor size at 75 degrees C terminations?
- a.6 AWG✓
- b.8 AWG
- c.4 AWG
- d.10 AWG
The conductor must carry 45 x 1.25 = 56.25 A. In the 75 degrees C column, 8 AWG copper is 50 A and is insufficient, while 6 AWG copper at 65 A meets the requirement. 4 AWG is oversized for the stated minimum, and 10 AWG at 35 A is far below the calculated ampacity.2026 NEC §215.4(A)(1)
The rule permitting the next higher standard overcurrent device rating above the conductor ampacity may be applied only where that device rating does not exceed what value?
- a.400 amperes
- b.600 amperes
- c.1,000 amperes
- d.800 amperes✓
The round-up allowance stops at 800 amperes; above that rating the overcurrent device must not exceed the ampacity of the conductors it protects. The other values are not thresholds in 240.4(B), and choosing 600 A would needlessly restrict legitimate designs in the 601 to 800 A range.2026 NEC §240.4(B)
A 200-ampere feeder uses THHN copper conductors, but the equipment terminations are rated 75 degrees C. What is the minimum conductor size?
- a.4/0 AWG
- b.2/0 AWG
- c.3/0 AWG✓
- d.250 kcmil
Because the terminations are rated 75 degrees C, the final ampacity must be taken from the 75 degrees C column even though THHN is a 90 degrees C insulation (110.14(C)(1)(b)). In that column 2/0 copper is 175 A and fails, while 3/0 copper is 200 A and matches the device. Even in the 90 degrees C column 2/0 is only 195 A, and 4/0 or 250 kcmil exceed the minimum.2026 NEC §110.14(C)(1)(b)
A dwelling has a combined general lighting, small-appliance and laundry load of 12,000 volt-amperes. Applying the standard demand factors, what is the demand load?
- a.12,000 volt-amperes
- b.4,200 volt-amperes
- c.7,650 volt-amperes
- d.6,150 volt-amperes✓
The dwelling lighting demand table takes the first 3,000 volt-amperes at 100 percent and the remainder from 3,001 to 120,000 volt-amperes at 35 percent: 3,000 + (9,000 x 0.35) = 3,000 + 3,150 = 6,150 volt-amperes. Applying 35 percent to the whole 12,000 gives the incorrect 4,200 figure.2026 NEC Table 120.45
Using the standard demand table for household cooking appliances, what is the demand load for a single 12-kilowatt household electric range?
- a.8 kilowatts✓
- b.12 kilowatts
- c.6 kilowatts
- d.9.6 kilowatts
Column C of Table 120.55 gives a demand of 8 kilowatts for one household range rated not over 12 kilowatts, reflecting the fact that all burners and the oven are rarely at full power at once. The 9.6-kilowatt answer applies the 80 percent factor from the columns for smaller appliances, which does not apply to a 12-kilowatt range, and 12 kilowatts ignores the demand allowance entirely.2026 NEC Table 120.55
A dwelling has a single household electric clothes dryer with a nameplate rating of 4.5 kilowatts. What value must be used for the dryer load in the service calculation?
- a.4,500 volt-amperes
- b.4,000 volt-amperes
- c.5,000 volt-amperes✓
- d.3,600 volt-amperes
The load for a household electric clothes dryer is 5,000 volt-amperes or the nameplate rating, whichever is larger, so a 4,500-volt-ampere nameplate is calculated at the 5,000-volt-ampere floor. Using the nameplate 4,500 value violates the minimum, and the other figures apply factors that do not belong here.2026 NEC §120.54
A dwelling feeder supplies four fastened-in-place appliances (a disposal, a dishwasher, a water heater and a trash compactor), each rated at least 1/4 horsepower or 500 watts, in addition to other loads. What demand factor may be applied to the nameplate total of these appliances?
- a.100 percent
- b.75 percent✓
- c.50 percent
- d.80 percent
Where four or more fastened-in-place appliances, each rated at least 1/4 horsepower or 500 watts, are on the same feeder or service in a dwelling, a 75 percent demand factor may be applied to their nameplate total (120.53). Cooking equipment, clothes dryers, space-heating and air-conditioning equipment and electric vehicle supply equipment do not count toward this group. With three or fewer such appliances no reduction is permitted, which is where the 100 percent answer applies.2026 NEC §120.53
Using the optional calculation method for a dwelling, the general loads total 40 kVA. What is the demand load for these general loads?
- a.40 kVA
- b.16 kVA
- c.20.8 kVA✓
- d.22 kVA
The optional dwelling method takes the first 8 kVA of general load at 100 percent and the remainder at 40 percent (120.82(B)): 8 + (32 x 0.40) = 8 + 12.8 = 20.8 kVA. The 22-kVA answer takes the first 10 kVA at 100 percent, which is not the current rule, and applying 40 percent to the entire 40 kVA gives the incorrect 16-kVA figure.2026 NEC §120.82(B)
When calculating a feeder or service that supplies several motors plus other loads, how is the largest motor accounted for?
- a.At 100 percent of its full-load current
- b.At 80 percent of its full-load current
- c.At 115 percent of its full-load current
- d.At 125 percent of its full-load current✓
Section 430.24 requires the conductors to carry 125 percent of the full-load current of the largest motor plus the full-load currents of the remaining motors and the other loads. In a combined load calculation this is the same as adding an extra 25 percent of the largest motor to the total. The 115 percent figure is the minimum rating of a motor disconnecting means, not the conductor calculation.2026 NEC §430.24
Using the standard demand table for household cooking appliances, what is the demand load for three 12-kilowatt household electric ranges supplied by one feeder?
- a.24 kilowatts
- b.8 kilowatts
- c.14 kilowatts✓
- d.22 kilowatts
Column C of Table 120.55 gives a demand of 14 kilowatts for three ranges rated not over 12 kilowatts each, applying diversity across the appliances. The 24-kilowatt answer would result from a naive sum with a partial factor, and 8 kilowatts is the single-range value.2026 NEC Table 120.55
A feeder supplies 40 amperes of continuous load plus 60 amperes of noncontinuous load. What is the minimum standard overcurrent device rating?
- a.90 amperes
- b.125 amperes
- c.110 amperes✓
- d.100 amperes
The device is sized for the noncontinuous load plus 125 percent of the continuous load: 60 + (40 x 1.25) = 110 A, which is a standard rating. See NEC 215.5 and Table 240.6(A).2026 NEC §215.5
A 240-volt single-phase feeder supplies an 8-kilowatt continuous load. What is the minimum standard overcurrent device rating?
- a.45 amperes✓
- b.35 amperes
- c.50 amperes
- d.40 amperes
Load current = 8,000 / 240 = 33.3 A. Because the load is continuous, the feeder device must be at least 33.3 x 1.25 = 41.7 A, so the next standard rating is 45 A. See NEC 215.5 and Table 240.6(A).2026 NEC §215.5
An apartment has the two required small-appliance branch circuits and no laundry circuit. What load must be included for the small-appliance circuits before demand factors?
- a.3,000 volt-amperes✓
- b.6,000 volt-amperes
- c.4,500 volt-amperes
- d.1,500 volt-amperes
Each small-appliance branch circuit is calculated at 1,500 VA: 2 x 1,500 = 3,000 VA. See NEC 120.52(A).2026 NEC §120.52(A)
Using Column C of the household cooking-appliance demand table, what is the demand load for two 12-kilowatt household ranges on one feeder?
- a.11 kilowatts✓
- b.10 kilowatts
- c.8 kilowatts
- d.16 kilowatts
Column C of Table 120.55 gives 11 kilowatts for two household ranges rated not over 12 kilowatts each. See NEC 120.55.2026 NEC Table 120.55
A dwelling has a single household electric clothes dryer with a nameplate rating of 5.5 kilowatts. What value must be used for the dryer load?
- a.4,000 volt-amperes
- b.5,000 volt-amperes
- c.5,250 volt-amperes
- d.5,500 volt-amperes✓
The dryer load is 5,000 VA or the nameplate rating, whichever is larger: 5,500 exceeds 5,000, so 5,500 VA is used. See NEC 120.54.2026 NEC §120.54
A dwelling feeder supplies three fastened-in-place appliances other than ranges, dryers and heating or air-conditioning equipment. What demand factor may be applied to their nameplate total?
- a.65 percent
- b.75 percent
- c.100 percent✓
- d.50 percent
The 75 percent demand factor requires four or more such fastened-in-place appliances; with only three, no reduction is permitted. See NEC 120.53.2026 NEC §120.53
Using the optional dwelling calculation, the general loads total 30 kVA. What is the demand load for these general loads?
- a.30.0 kVA
- b.18.0 kVA
- c.12.0 kVA
- d.16.8 kVA✓
The optional method takes the first 8 kVA of the general loads at 100 percent and the remainder at 40 percent: 8 + (22 x 0.40) = 16.8 kVA. See NEC 120.82(B).2026 NEC §120.82(B)
A retail store has 15 linear feet of show window. What show-window load must be included?
- a.1,800 volt-amperes
- b.1,500 volt-amperes
- c.2,700 volt-amperes
- d.3,000 volt-amperes✓
Show-window lighting is calculated at 200 VA per linear foot of show window: 15 x 200 = 3,000 VA. See NEC 120.46(A).2026 NEC §120.46(A)
A feeder supplies 50 amperes of continuous load plus 40 amperes of noncontinuous load. Using 75 degrees C copper terminations, what is the minimum conductor size?
- a.1 AWG
- b.2 AWG✓
- c.3 AWG
- d.4 AWG
Required ampacity = noncontinuous + 125 percent continuous = 40 + (50 x 1.25) = 102.5 A. In the 75 degrees C column 3 AWG (100 A) fails and 2 AWG (115 A) qualifies. See NEC 215.4(A)(1) and Table 310.16.2026 NEC §215.4(A)(1)
A feeder neutral has a maximum unbalanced load of 250 amperes of linear (not nonlinear) line-to-neutral load. Applying the permitted demand factor, what is the calculated neutral load?
- a.175 amperes
- b.250 amperes
- c.225 amperes
- d.235 amperes✓
For a feeder or service, the first 200 A of unbalanced neutral load is taken at 100 percent and the portion over 200 A at 70 percent: 200 + (50 x 0.70) = 235 A. See NEC 120.61(B)(2).2026 NEC §120.61(B)(2)
A dwelling has a combined general lighting, small-appliance and laundry load of 8,000 volt-amperes. Applying the standard demand factors, what is the demand load?
- a.4,750 volt-amperes✓
- b.8,000 volt-amperes
- c.2,800 volt-amperes
- d.5,000 volt-amperes
The dwelling lighting demand table takes the first 3,000 VA at 100 percent and the remainder at 35 percent: 3,000 + (5,000 x 0.35) = 4,750 VA. See NEC Table 120.45.2026 NEC Table 120.45
A feeder supplies a 60-ampere continuous load. What is the minimum standard overcurrent device rating?
- a.70 amperes
- b.75 amperes
- c.80 amperes✓
- d.90 amperes
60 x 1.25 = 75 A, which is not a standard rating, so the next standard size of 80 A must be used. See NEC 215.5 and 240.6(A).2026 NEC §215.5
A dwelling has a combined general lighting, small-appliance and laundry load of 3,600 volt-amperes. Applying the standard demand factors, what is the demand load?
- a.3,600 volt-amperes
- b.3,150 volt-amperes
- c.3,210 volt-amperes✓
- d.1,260 volt-amperes
The first 3,000 VA is taken at 100 percent and the remainder at 35 percent: 3,000 + (600 x 0.35) = 3,210 VA. See NEC Table 120.45.2026 NEC Table 120.45
A 200-ampere feeder requires what minimum size copper equipment grounding conductor?
- a.3 AWG
- b.8 AWG
- c.4 AWG
- d.6 AWG✓
The 200-ampere row of Table 250.122 specifies 6 AWG copper. 8 AWG belongs to 100 amperes, 4 AWG to 300 amperes and 3 AWG to 400 amperes, so those choices come from reading adjacent rows.2026 NEC Table 250.122
What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?
- a.4 AWG
- b.3 AWG✓
- c.2 AWG
- d.1 AWG
Table 250.122 lists 3 AWG copper at 400 amperes. 4 AWG is the 300-ampere value, 2 AWG the 500-ampere value and 1 AWG the 600-ampere value, so all three are one row away from the correct entry.2026 NEC Table 250.122
A 100-ampere feeder originally sized with 3 AWG copper (52,620 circular mils) is upsized to 1/0 AWG copper (105,600 circular mils) for voltage drop. What is the minimum equipment grounding conductor?
- a.4 AWG copper✓
- b.8 AWG copper
- c.6 AWG copper
- d.2 AWG copper
When ungrounded conductors are increased in size, the equipment grounding conductor must be increased in the same proportion by circular-mil area. The ratio is 105,600 / 52,620 = 2.0, and the base 100-ampere equipment grounding conductor of 8 AWG (16,510 circular mils) doubles to about 33,100 circular mils; 6 AWG has only 26,240 circular mils, so 4 AWG at 41,740 circular mils is the smallest that qualifies. Leaving it at 8 AWG ignores the proportional rule.2026 NEC §250.122(D)
A demand factor may be applied to the portion of a feeder neutral load that exceeds what value?
- a.100 amperes
- b.150 amperes
- c.200 amperes✓
- d.400 amperes
For a feeder or service, the portion of the maximum unbalanced neutral load that exceeds 200 amperes may be taken at 70 percent, recognizing the diversity of line-to-neutral loads at higher currents. This reduction does not apply to nonlinear loads on a wye system, where the neutral can be as heavily loaded as the phases. See NEC 120.61(B) and 120.61(C).2026 NEC §120.61(B)
What is the minimum size copper equipment grounding conductor for a 300-ampere feeder?
- a.2 AWG
- b.6 AWG
- c.3 AWG
- d.4 AWG✓
The 300-ampere row of Table 250.122 specifies 4 AWG copper. 6 AWG is 200 amperes and 3 AWG is 400 amperes, so those are adjacent rows. See NEC Table 250.122.2026 NEC Table 250.122
What is the minimum size copper equipment grounding conductor for a 500-ampere feeder?
- a.1 AWG
- b.4 AWG
- c.3 AWG
- d.2 AWG✓
The 500-ampere row of Table 250.122 requires 2 AWG copper. 3 AWG is 400 amperes and 1 AWG is 600 amperes. See NEC Table 250.122.2026 NEC Table 250.122
No exception applies. Which feeder disconnecting means requires ground-fault protection of equipment?
- a.A 1200 A disconnect on a 208Y/120-volt solidly grounded wye system
- b.An 800 A disconnect on a 480Y/277-volt solidly grounded wye system
- c.A 1200 A disconnect on a 480Y/277-volt solidly grounded wye system✓
- d.A 1200 A disconnect on a 480-volt ungrounded delta system
Section 215.10(A) applies to feeder disconnects rated 1000 amperes or more on solidly grounded wye systems with more than 150 volts to ground and not over 1000 volts phase to phase. Only the 1200 ampere, 480Y/277-volt disconnect meets every part of that test. The 208Y/120-volt system is only 120 volts to ground, the 800 ampere device is below the rating threshold, and an ungrounded delta is not a solidly grounded wye.2026 NEC §215.10(A)
A feeder carries the total load supplied by a set of service conductors. The feeder ampacity must be not less than that of the service conductors when the service conductors have an ampacity of what value or less?
- a.55 amperes✓
- b.60 amperes
- c.100 amperes
- d.125 amperes
Section 215.4(C) applies where the feeder carries the whole load of service conductors that have an ampacity of 55 amperes or less; the feeder may not then be smaller in ampacity than those service conductors. The 60 and 100 ampere values are service disconnect ratings from Article 230, not the threshold in this rule.2026 NEC §215.4(C)
A building has both 480Y/277-volt and 208Y/120-volt systems. Where must each ungrounded feeder conductor be identified by phase or line and by nominal voltage system?
- a.Only at the feeder overcurrent device where it originates
- b.At intervals not exceeding 24 in. along its entire length
- c.Only where the conductor is 4 AWG or larger
- d.At all termination, connection, and splice points✓
Where premises wiring has more than one nominal voltage system, 215.12(C)(2) requires each ungrounded feeder conductor to be identified by phase or line and by system at every termination, connection, and splice point. The 24 in. interval and the 4 AWG break point belong to the dc feeder rules in 215.12(C)(3). Marking only at the source would leave downstream splices unidentified.2026 NEC §215.12(C)(2)
The method used to identify ungrounded feeder conductors of different voltage systems must be documented in a readily available manner or permanently posted at what location?
- a.Each feeder panelboard or similar feeder distribution equipment✓
- b.The service equipment only
- c.Each junction box and pull box along the feeder route
- d.The utility meter enclosure
Section 215.12(C)(2)(b) requires the identification method to be documented in a readily available manner or permanently posted at each feeder panelboard or similar feeder distribution equipment. Posting only at the service would not help someone working at a downstream panel, and boxes and meter enclosures are not named.2026 NEC §215.12(C)(2)
Feeder tap conductors end at a circuit breaker. May the rule that allows the next higher standard overcurrent device rating above the conductor ampacity be used for these tap conductors?
- a.Yes, if the breaker is rated 800 amperes or less
- b.Yes, if the tap conductors are 10 ft long or less
- c.No, it is not permitted for tap conductors✓
- d.Yes, if the taps are in metal raceway
Section 240.21(B) states that the next higher rating allowance of 240.4(B) is not permitted for tap conductors, so the device at the end of the tap may not exceed the tap ampacity. The 800 ampere limit is a condition of that allowance for ordinary circuits, which is the trap. Tap length and wiring method do not change the answer.2026 NEC §240.21(B)
Under the rule for feeder taps not over 25 ft long, the tap conductors must terminate in which of the following?
- a.A main lug only panelboard with no more than six breakers
- b.A single circuit breaker or a single set of fuses✓
- c.Any number of breakers whose ratings total the tap ampacity
- d.A fused or unfused switch of any rating
Section 240.21(B)(2) requires the tap to end in one circuit breaker or one set of fuses that limits the load to the ampacity of the tap conductors. That single device may then supply any number of additional overcurrent devices on its load side. Ending the tap on main lugs or on several breakers leaves the tap conductors without a single limiting device.2026 NEC §240.21(B)(2)
Under the rule for feeder taps over 25 ft long in high bay manufacturing buildings, what is the smallest copper tap conductor permitted?
- a.8 AWG
- b.6 AWG✓
- c.4 AWG
- d.2 AWG
One of the conditions in 240.21(B)(4) is that the tap conductors are 6 AWG copper or 4 AWG aluminum or larger. Choosing 4 AWG confuses the aluminum value with the copper value. The tap must still have an ampacity of at least one-third of the feeder overcurrent device rating, so 6 AWG is a floor, not a sizing method.2026 NEC §240.21(B)(4)
Under the rule for feeder taps supplying a transformer, the primary tap conductor is 9 ft long and no part of it is protected at its ampacity. What is the longest secondary conductor permitted?
- a.10 ft
- b.16 ft✓
- c.25 ft
- d.91 ft
Section 240.21(B)(3) limits the total length of one primary conductor plus one secondary conductor to 25 ft, not counting any part of the primary that is protected at its ampacity. With 9 ft of unprotected primary, 25 - 9 = 16 ft remains for the secondary. Answering 25 ft ignores the primary length, and 10 ft belongs to a different tap rule.2026 NEC §240.21(B)(3)
A 208-volt, single-phase branch circuit supplies a continuous load of 24 amperes. What is the minimum standard overcurrent device rating permitted?
- a.30 amperes✓
- b.25 amperes
- c.24 amperes
- d.40 amperes
An overcurrent device supplying a continuous load must be rated at not less than 125 percent of that load: 24 A x 1.25 = 30 A, which is a standard rating in 240.6(A). The 24 A and 25 A choices ignore or under-apply the 125 percent factor, and 40 A jumps past the next standard size above the calculated value.2026 NEC §210.20(A)
A branch circuit supplies a continuous load of 24 amperes. What is the minimum size copper branch-circuit conductor, assuming 75 degrees C terminations and THWN insulation?
- a.12 AWG
- b.10 AWG✓
- c.8 AWG
- d.14 AWG
The conductor must carry at least 125 percent of the continuous load, or 30 A (210.19(A)). In the 75 degrees C column of Table 310.16, 12 AWG copper is only 25 A, so it fails; 10 AWG copper is 35 A and is adequate, and 240.4(D) allows a 30 A device on 10 AWG. Choosing 8 AWG is oversized for the minimum asked, and 14 AWG is 20 A in that column and limited to a 15 A device.2026 NEC §210.19(A)