444 questions

Definitions, Theory, and Plans

A retail store has 35 ft of lighting track. Using the standard method, what load must be included for the track in the feeder calculation?

  • a.2,550 VA
  • b.2,625 VA
  • c.2,700 VA✓
  • d.5,250 VA

In other than dwelling units, lighting track is counted at 150 VA for every 2 feet or fraction of 2 feet. Working: 35 / 2 = 17.5, which counts as 18 units, and 18 x 150 = 2,700 VA. The 2,625 VA answer does not round the fraction up, 2,550 VA rounds it down, and 5,250 VA applies 150 VA to every foot. See 120.46(B).2026 NEC §120.46(B)

Definitions, Theory, and Plans

A one-family dwelling has four appliances fastened in place on the same service: a 1,200 VA dishwasher, a 900 VA disposal, a 4,500 VA water heater and an 800 VA trash compactor. Using the standard method, what is the demand load for these appliances?

  • a.5,550 VA✓
  • b.5,920 VA
  • c.6,660 VA
  • d.7,400 VA

Where four or more fastened-in-place appliances rated 500 watts or more are on the same feeder or service of a dwelling, a 75 percent demand factor may be applied to their total nameplate load. Working: 1,200 + 900 + 4,500 + 800 = 7,400 VA, and 7,400 x 0.75 = 5,550 VA. The other answers use 80 or 90 percent, or take the full nameplate total. See 120.53.2026 NEC §120.53

Electrical Services, Service Equipment, and Separately Derived Systems

Using the dwelling service and feeder conductor table, what is the minimum copper conductor size for a 200-ampere single-phase dwelling service?

  • a.1/0 AWG
  • b.3/0 AWG
  • c.4/0 AWG
  • d.2/0 AWG✓

For single-phase dwelling services and the main power feeder, conductors are permitted to be sized at 83 percent of the service rating, and the dwelling table lists 2/0 copper for a 200-ampere service. The 3/0 answer is what Table 310.16 alone would require without the dwelling allowance, and 1/0 is below what the dwelling table permits.2026 NEC §310.12

Electrical Services, Service Equipment, and Separately Derived Systems

A service uses 3/0 AWG copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor?

  • a.4 AWG✓
  • b.6 AWG
  • c.2 AWG
  • d.1/0 AWG

Table 250.66 groups 2/0 and 3/0 copper service conductors together and calls for a 4 AWG copper grounding electrode conductor. The 6 AWG row applies to service conductors of 1 or 1/0 AWG, 2 AWG copper is required only above 3/0 through 350 kcmil, and 1/0 applies to service conductors above 350 through 600 kcmil.2026 NEC Table 250.66

Electrical Services, Service Equipment, and Separately Derived Systems

A service is supplied by two parallel sets of 250 kcmil copper conductors per phase. What is the minimum size copper grounding electrode conductor?

  • a.4 AWG
  • b.2 AWG
  • c.1/0 AWG✓
  • d.3/0 AWG

With parallel conductors the equivalent area is the sum of the areas in one phase: 2 x 250 kcmil = 500 kcmil, which falls in the over 350 through 600 kcmil row and requires 1/0 copper. Using 2 AWG treats a single 250 kcmil conductor as the whole service, and 3/0 corresponds to services above 1,100 kcmil.2026 NEC Table 250.66

Electrical Services, Service Equipment, and Separately Derived Systems

Where the grounding electrode conductor connects only to a driven ground rod, what is the largest size it is required to be?

  • a.2 AWG copper
  • b.4 AWG copper
  • c.6 AWG copper✓
  • d.1/0 AWG copper

A rod, pipe or plate electrode has a limited earth contact area, so the conductor to it is never required to be larger than 6 AWG copper regardless of what Table 250.66 would otherwise demand. The 4 AWG limit applies to a concrete-encased electrode, and larger sizes are not required for any rod connection.2026 NEC §250.66(A)

Electrical Services, Service Equipment, and Separately Derived Systems

Where the grounding electrode conductor connects only to a concrete-encased electrode, what is the largest size it is required to be?

  • a.2 AWG copper
  • b.6 AWG copper
  • c.4 AWG copper✓
  • d.1/0 AWG copper

The conductor to a concrete-encased electrode is never required to be larger than 4 AWG copper. The 6 AWG cap belongs to rod, pipe and plate electrodes, and 2 AWG or 1/0 would only come from Table 250.66 before this limiting rule is applied.2026 NEC §250.66(B)

Electrical Services, Service Equipment, and Separately Derived Systems

A service is supplied by a single set of 500 kcmil copper ungrounded conductors. What is the minimum size copper main bonding jumper?

  • a.3/0 AWG
  • b.2 AWG
  • c.4 AWG
  • d.1/0 AWG✓

The main bonding jumper is sized from Table 250.102(C)(1), the same table used for the grounded conductor and supply-side bonding jumpers, and the over 350 through 600 kcmil row calls for 1/0 copper. The 2 AWG and 4 AWG answers come from smaller service conductor rows, and 3/0 is larger than this row requires.2026 NEC §250.28(D)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A service uses two parallel sets of 750 kcmil copper per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?

  • a.250 kcmil
  • b.3/0 AWG
  • c.4/0 AWG✓
  • d.2/0 AWG

Where the ungrounded service conductors exceed 1,100 kcmil of copper, the main bonding jumper must be at least 12.5 percent of that area: 2 x 750 = 1,500 kcmil, and 1,500 x 0.125 = 187.5 kcmil. The smallest standard conductor with at least that area is 4/0 AWG at 211.6 kcmil; 3/0 at 167.8 kcmil falls short and 250 kcmil is larger than the calculated minimum.2026 NEC Table 250.102(C)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?

  • a.205 amperes✓
  • b.188 amperes
  • c.235 amperes
  • d.225 amperes

Service-entrance conductors must have an ampacity of at least the noncontinuous load plus 125 percent of the continuous load: 120 + (68 x 1.25) = 120 + 85 = 205 A. The 188-ampere answer simply adds the loads, 235 amperes applies 125 percent to the whole load, and 225 amperes is a standard device rating, not the required conductor ampacity.2026 NEC §230.42(A)(1)

Want these explained in order? Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Electrical Services, Service Equipment, and Separately Derived Systems

Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?

  • a.600 kcmil
  • b.500 kcmil
  • c.350 kcmil
  • d.400 kcmil✓

Table 310.12(A) lists 400 kcmil copper for a 400-ampere single-phase dwelling service, reflecting the 83 percent allowance in 310.12(A). The 350 kcmil value is the table entry for a 350-ampere service, and 500 and 600 kcmil are larger than the table requires.2026 NEC Table 310.12(A)

Electrical Services, Service Equipment, and Separately Derived Systems

What is the minimum length of a rod-type grounding electrode?

  • a.10 feet
  • b.6 feet
  • c.8 feet✓
  • d.5 feet

Rod and pipe electrodes must be at least 8 feet long. The 10-foot value is the minimum earth contact required of a metal underground water pipe electrode, and 5 or 6 feet fall short of the rod requirement.2026 NEC §250.52(A)(5)

Electrical Services, Service Equipment, and Separately Derived Systems

Where two rod electrodes are installed to make up the grounding electrode system, what is the minimum spacing between them?

  • a.3 feet
  • b.6 feet✓
  • c.8 feet
  • d.10 feet

Rods that supplement one another must be separated by at least 6 feet so their earth shells do not overlap and defeat the purpose of the second rod. The 8-foot figure is the minimum rod length rather than spacing, and 3 or 10 feet are not the code minimum.2026 NEC §250.53(A)(3)

Electrical Services, Service Equipment, and Separately Derived Systems

A single ground rod does not have to be supplemented by a second electrode if its resistance to earth does not exceed what value?

  • a.5 ohms
  • b.25 ohms✓
  • c.100 ohms
  • d.1 ohm

A single rod, pipe or plate electrode must be supplemented unless it is shown to have a resistance to earth of 25 ohms or less. The 5-, 1- and 100-ohm values do not appear in this rule.2026 NEC §250.53(A)(2)

Electrical Services, Service Equipment, and Separately Derived Systems

A metal underground water pipe qualifies as a grounding electrode only if it is in direct contact with the earth for at least what length?

  • a.20 feet
  • b.10 feet✓
  • c.8 feet
  • d.5 feet

The metal underground water pipe electrode must have 10 feet or more in direct contact with the earth. The 20-foot value belongs to the concrete-encased electrode, and 5 or 8 feet do not meet the requirement.2026 NEC §250.52(A)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A concrete-encased electrode may be formed by at least 20 feet of which of the following?

  • a.Bare 4 AWG copper conductor encased in the concrete footing✓
  • b.Bare 6 AWG copper conductor encased in the concrete footing
  • c.Insulated 4 AWG copper conductor run through the footing
  • d.Bare 8 AWG copper conductor encased in the concrete footing

A concrete-encased electrode consists of at least 20 feet of bare copper not smaller than 4 AWG, or at least 20 feet of one-half inch or larger reinforcing bar, encased in at least 2 inches of concrete. Smaller conductors do not qualify, and the copper conductor must be bare.2026 NEC §250.52(A)(3)

Electrical Services, Service Equipment, and Separately Derived Systems

When a metal underground water pipe is used as a grounding electrode, what else is required?

  • a.It must be bonded to the interior metal gas piping system, which then serves as the required supplemental grounding electrode
  • b.No supplement is required if the pipe is longer than 20 feet
  • c.It must be supplemented by an additional electrode of a type identified in 250.52✓
  • d.It may be used as the sole electrode only if its measured resistance to earth is 25 ohms or less at installation

A metal underground water pipe electrode is not allowed to stand alone. It must be supplemented by another electrode of a type listed in 250.52(A)(2) through (A)(8), such as a rod or a concrete-encased electrode. Pipe length does not remove the requirement, bonding to interior gas piping does not satisfy it, and the 25-ohm provision applies to rod, pipe and plate electrodes.2026 NEC §250.53(D)(2)

Electrical Services, Service Equipment, and Separately Derived Systems

What is the maximum number of service disconnecting means permitted for a single set of service-entrance conductors?

  • a.Eight
  • b.Two
  • c.Four
  • d.Six✓

A service normally has one disconnecting means, but 230.71(B) permits two to six service disconnects where they are arranged as that section describes. Two and four are below the ceiling but are not the maximum, and eight exceeds the limit.2026 NEC §230.71(B)

Electrical Services, Service Equipment, and Separately Derived Systems

What is the minimum service disconnecting means rating for a one-family dwelling?

  • a.60 amperes
  • b.100 amperes✓
  • c.125 amperes
  • d.200 amperes

A one-family dwelling service disconnect must be rated at least 100 amperes. The 60-ampere minimum in 230.79(D) applies to installations not covered by the more specific rules, while 125 and 200 amperes are common design choices but exceed the minimum.2026 NEC §230.79(C)

Electrical Services, Service Equipment, and Separately Derived Systems

What is the minimum clearance above a residential driveway for overhead service conductors not over 300 volts to ground?

  • a.18 feet
  • b.10 feet
  • c.12 feet✓
  • d.15 feet

Residential driveways and commercial areas not subject to truck traffic require 12 feet of clearance. The 10-foot clearance applies only above finished grade, sidewalks and platforms accessible to pedestrians, and 18 feet is required over public streets, alleys and roads.2026 NEC §230.24(B)(2)

Electrical Services, Service Equipment, and Separately Derived Systems

Overhead service conductors must maintain what minimum clearance from a window that is designed to be opened?

  • a.6 feet
  • b.5 feet
  • c.10 feet
  • d.3 feet✓

Service conductors must keep 3 feet of clearance from windows designed to open, doors, porches, balconies, stairs and similar locations. Conductors run above the top level of a window are considered out of reach and are exempt, and the other distances do not appear in this rule.2026 NEC §230.9(A)

Electrical Services, Service Equipment, and Separately Derived Systems

Ground-fault protection of equipment is required for a solidly grounded wye service with more than 150 volts to ground when the disconnect is rated at least what value?

  • a.800 amperes
  • b.1,000 amperes✓
  • c.600 amperes
  • d.1,200 amperes

The threshold is a service disconnect rated 1,000 amperes or more on a solidly grounded wye system of more than 150 volts to ground but not exceeding 1,000 volts phase-to-phase, which describes a typical 480Y/277-volt service. The 1,200-ampere figure is the maximum permitted setting of the ground-fault protection, not the threshold at which it is required.2026 NEC §230.95(A)

Electrical Services, Service Equipment, and Separately Derived Systems

On the load side of the service disconnecting means, what is the general rule for using the grounded neutral conductor to ground equipment enclosures?

  • a.It is permitted only in dwelling units
  • b.It is permitted where the grounded neutral conductor is at least 6 AWG copper and runs directly to the equipment
  • c.It is permitted in any panelboard or subpanel that is supplied directly from the service equipment enclosure
  • d.It is not permitted; a separate equipment grounding conductor must be used✓

Downstream of the service disconnect the neutral and the equipment grounding conductor must be kept separate so that normal load current does not travel on enclosures and raceways. Bonding them together at a subpanel creates parallel neutral paths and objectionable current, and neither conductor size nor occupancy type changes this general prohibition.2026 NEC §250.24(B)

Electrical Services, Service Equipment, and Separately Derived Systems

The interior metal water piping system of a building must be bonded to the service equipment. How is the required bonding jumper sized?

  • a.From Table 250.102(C)(1), based on the size of the ungrounded service-entrance conductors✓
  • b.From Table 250.122, based on the rating of the overcurrent device protecting the largest service conductor
  • c.Always 6 AWG copper regardless of service size
  • d.From Table 310.16, based on the service ampacity and the temperature rating of the terminations used

The bonding jumper for the interior metal water piping system is sized from Table 250.102(C)(1) using the ungrounded service-entrance conductors, and it is not required to be larger than 3/0 copper. Table 250.122 sizes equipment grounding conductors by overcurrent device rating and does not apply to this bond, and Table 310.16 is an ampacity table.2026 NEC §250.104(A)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

For a separately derived system such as a transformer secondary, where is the system bonding jumper permitted to be installed?

  • a.At every downstream panelboard
  • b.Only at the main service disconnecting means of the building and never at the transformer, panelboard, or any other point of the separately derived system
  • c.At the source of the separately derived system or at the first disconnecting means, but at only one of those points✓
  • d.It is not required for separately derived systems

A separately derived system requires a single system bonding jumper connecting the grounded conductor to the equipment grounding system, installed either at the source or at the first disconnecting means but at only one location. Installing it at more than one point creates parallel neutral paths, and omitting it leaves no effective fault-clearing path for the derived system.2026 NEC §250.30(A)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A single-family dwelling has a calculated demand load of 21,600 volt-amperes on a 240-volt, single-phase service. What is the minimum service disconnecting means rating permitted?

  • a.90 amperes
  • b.100 amperes✓
  • c.125 amperes
  • d.60 amperes

The calculated current is 21,600 / 240 = 90 amperes, but the service disconnecting means for a one-family dwelling must be rated at least 100 amperes, so the code floor governs. Selecting 90 amperes satisfies the calculation but violates the 100-ampere minimum, and 125 amperes exceeds the required minimum.2026 NEC §230.79(C)

Electrical Services, Service Equipment, and Separately Derived Systems

The grounded (neutral) service conductor also serves as the effective ground-fault current path back to the utility. It must be sized not smaller than what?

  • a.The equipment grounding conductor from Table 250.122
  • b.6 AWG copper in all cases
  • c.One-half the ungrounded conductor size
  • d.The grounded conductor size from Table 250.102(C)(1)✓

The grounded service conductor is the path for ground-fault current back to the source, so 250.24(D)(1) does not allow it to be smaller than the size given in Table 250.102(C)(1), which is entered with the size of the ungrounded service conductors. Sizing it from the equipment grounding conductor table, using a fixed 6 AWG, or using half the ungrounded size is not the rule.2026 NEC §250.24(D)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A grounding electrode conductor is run from the service to a driven ground rod. What is the rule regarding splices in that conductor?

  • a.Any split-bolt connector may be used at any point along the run, including concealed or buried locations
  • b.It must be installed in one continuous length unless it is spliced by a permitted method, such as irreversible compression connectors or exothermic welding✓
  • c.Up to three twist-on wire connector splices are permitted along the run, provided that each connection is made accessible and the conductor is not reduced in size at any of the splice points
  • d.Splices are never permitted in this conductor, so a damaged or short conductor must always be replaced from end to end

A grounding electrode conductor must be installed in one continuous length, but 250.64(C) lists permitted splicing methods. These include irreversible compression connectors listed as grounding and bonding equipment, exothermic welding, and, where the splice is at an accessible location, listed grounding and bonding equipment. Unlisted connectors, concealed mechanical splices and twist-on wire connectors do not meet the rule, and splices are not banned outright.2026 NEC §250.64(C)

Electrical Services, Service Equipment, and Separately Derived Systems

A service uses 4/0 AWG copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor?

  • a.4 AWG
  • b.2 AWG✓
  • c.1/0 AWG
  • d.6 AWG

Table 250.66 places service conductors over 3/0 through 350 kcmil copper in the row requiring a 2 AWG copper grounding electrode conductor. The 4 AWG row is for 2/0 and 3/0, so reading one row low understates it. See NEC Table 250.66.2026 NEC Table 250.66

Electrical Services, Service Equipment, and Separately Derived Systems

A service is supplied by a single set of 400 kcmil copper ungrounded conductors. What is the minimum size copper grounding electrode conductor?

  • a.2 AWG
  • b.4 AWG
  • c.1/0 AWG✓
  • d.3/0 AWG

Service conductors over 350 through 600 kcmil copper require a 1/0 AWG copper grounding electrode conductor. The 2 AWG row applies to over 3/0 through 350 kcmil. See NEC Table 250.66.2026 NEC Table 250.66

Electrical Services, Service Equipment, and Separately Derived Systems

A service uses 1 AWG copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor?

  • a.2 AWG
  • b.6 AWG✓
  • c.4 AWG
  • d.8 AWG

Table 250.66 groups 1 and 1/0 AWG copper service conductors together and requires a 6 AWG copper grounding electrode conductor. The 8 AWG row is for 2 AWG and smaller. See NEC Table 250.66.2026 NEC Table 250.66

Electrical Services, Service Equipment, and Separately Derived Systems

A ground ring encircling a building must be formed from at least 20 feet of bare copper conductor not smaller than what size?

  • a.4 AWG
  • b.6 AWG
  • c.2 AWG✓
  • d.1/0 AWG

A ground ring must encircle the building and consist of at least 20 feet of bare copper conductor not smaller than 2 AWG. See NEC 250.52(A)(4).2026 NEC §250.52(A)(4)

Electrical Services, Service Equipment, and Separately Derived Systems

A plate electrode must present at least how much surface area to exterior soil?

  • a.8 square feet
  • b.4 square feet
  • c.2 square feet✓
  • d.1 square foot

A plate electrode of iron, steel or nonferrous metal must expose at least 2 square feet of surface to the surrounding earth. See NEC 250.52(A)(7).2026 NEC §250.52(A)(7)

Electrical Services, Service Equipment, and Separately Derived Systems

A service is supplied by a single set of 350 kcmil copper ungrounded conductors. What is the minimum size copper main bonding jumper?

  • a.3 AWG
  • b.1/0 AWG
  • c.2 AWG✓
  • d.4 AWG

The main bonding jumper is sized from Table 250.102(C)(1), and 350 kcmil copper falls in the over 3/0 through 350 kcmil row requiring 2 AWG copper. See NEC 250.28(D)(1).2026 NEC Table 250.102(C)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A service uses two parallel sets of 600 kcmil copper conductors per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?

  • a.2/0 AWG
  • b.4/0 AWG
  • c.3/0 AWG✓
  • d.250 kcmil

Where copper service conductors exceed 1,100 kcmil, the main bonding jumper must be at least 12.5 percent of that area: 2 x 600 = 1,200 kcmil, and 1,200 x 0.125 = 150 kcmil. 2/0 (133.1 kcmil) is too small; 3/0 (167.8 kcmil) qualifies. See NEC Table 250.102(C)(1), Note 1, and Chapter 9, Table 8.2026 NEC Table 250.102(C)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A reinforcing bar used to form a concrete-encased electrode must be at least what diameter?

  • a.1/4 inch
  • b.5/8 inch
  • c.3/8 inch
  • d.1/2 inch✓

A concrete-encased electrode may be formed with at least 20 feet of reinforcing bar not smaller than 1/2 inch in diameter. See NEC 250.52(A)(3).2026 NEC §250.52(A)(3)

Electrical Services, Service Equipment, and Separately Derived Systems

A concrete-encased electrode using bare copper must be formed with at least 20 feet of what minimum conductor size?

  • a.2 AWG
  • b.4 AWG✓
  • c.8 AWG
  • d.6 AWG

A concrete-encased electrode may be formed with at least 20 feet of bare copper conductor not smaller than 4 AWG, or with at least 20 feet of reinforcing bar not smaller than 1/2 inch in diameter. See NEC 250.52(A)(3).2026 NEC §250.52(A)(3)

Electrical Services, Service Equipment, and Separately Derived Systems

Where rock bottom is encountered and an 8-foot rod cannot be driven vertically, at what maximum angle from vertical may the rod be driven?

  • a.90 degrees
  • b.45 degrees✓
  • c.60 degrees
  • d.30 degrees

If rock bottom prevents vertical driving, a rod electrode may be driven at an angle not exceeding 45 degrees from vertical, or buried in a trench at least 30 inches deep. See NEC 250.53(A)(4), Exceptions No. 1 and No. 2.2026 NEC §250.53(A)(4)

Electrical Services, Service Equipment, and Separately Derived Systems

A grounding electrode conductor connection to a ground rod buried in the earth must use what kind of fitting?

  • a.A connector or clamp listed for direct burial in soil✓
  • b.A tape-wrapped mechanical lug
  • c.A solder joint
  • d.Any indoor split-bolt connector

A clamp or fitting used to connect to a rod, pipe or other electrode that is buried must be listed for direct soil burial. See NEC 250.70(A)(2).2026 NEC §250.70(A)(2)

Electrical Services, Service Equipment, and Separately Derived Systems

Under the current code, how must two to six service disconnects for a single service be arranged?

  • a.Behind a single main breaker feeding sub-disconnects
  • b.All mounted on a single removable panel
  • c.Each in a separate enclosure, or in a separate section or compartment of the equipment, all grouped✓
  • d.In any convenient locations throughout the building

Where two to six service disconnects serve one service, each must be in its own enclosure or in its own section or compartment of equipment such as a switchboard, switchgear or metering center, and the disconnects must be grouped. See NEC 230.71(B) and 230.72(A).2026 NEC §230.71(B)

Electrical Services, Service Equipment, and Separately Derived Systems

The point of attachment of overhead service-drop conductors to a building must be at least how far above finished grade?

  • a.10 feet✓
  • b.12 feet
  • c.8 feet
  • d.15 feet

The point of attachment of the service-drop or overhead service conductors must be at least 10 feet above finished grade and positioned to maintain the required conductor clearances. See NEC 230.26.2026 NEC §230.26

Electrical Services, Service Equipment, and Separately Derived Systems

What is the minimum vertical clearance of overhead service conductors above a roof that is not readily accessible?

  • a.8 feet 6 inches✓
  • b.10 feet 6 inches
  • c.12 feet 6 inches
  • d.3 feet

Overhead service conductors must keep at least 8 feet 6 inches of vertical clearance above the roof surface, maintained for 3 feet in all directions from the roof edge. The smaller clearances, such as 3 feet, come from the exceptions to 230.24(A), which the exam does not apply unless the question directs it. See NEC 230.24(A).2026 NEC §230.24(A)

Electrical Services, Service Equipment, and Separately Derived Systems

What is the minimum clearance for overhead service conductors passing over a public street or road?

  • a.15 feet
  • b.12 feet
  • c.10 feet
  • d.18 feet✓

Overhead service conductors over public streets and other areas subject to truck traffic require 18 feet of clearance from final grade. See NEC 230.24(B).2026 NEC §230.24(B)

Electrical Services, Service Equipment, and Separately Derived Systems

Neutral current that flows onto metal enclosures and grounding conductors because of an improper neutral-to-ground connection is known as what?

  • a.Inductive reactance
  • b.Fault current
  • c.Displacement current
  • d.Objectionable current✓

A neutral-to-ground bond made on the load side of the service creates parallel neutral paths, and the resulting current on grounding paths is objectionable current, which must be eliminated by correcting the connection. See NEC 250.6 and 250.24(B).2026 NEC §250.6

Electrical Services, Service Equipment, and Separately Derived Systems

On the load side of the service disconnecting means, may the grounded neutral conductor be used to ground equipment enclosures?

  • a.Yes, where the neutral is 6 AWG copper or larger
  • b.Yes, in any subpanel fed from the service equipment
  • c.No; a separate equipment grounding conductor must be used✓
  • d.Yes, but only in dwelling units

Downstream of the service disconnect the neutral and equipment grounding conductor must be kept separate so load current does not travel on enclosures and raceways. See NEC 250.24(B).2026 NEC §250.24(B)

Electrical Services, Service Equipment, and Separately Derived Systems

For a separately derived system, the grounding electrode conductor connects to the grounded conductor at the same point where what is installed?

  • a.The largest branch-circuit overcurrent device
  • b.The main bonding jumper at the service
  • c.The system bonding jumper✓
  • d.Every downstream equipment grounding bus

The grounding electrode conductor for a separately derived system connects the grounded conductor to the electrode at the same single point where the system bonding jumper is installed. See NEC 250.30(A)(5).2026 NEC §250.30(A)(5)

Electrical Services, Service Equipment, and Separately Derived Systems

A supply-side bonding jumper on the line side of the service is sized from which table?

  • a.Table 120.55
  • b.Table 250.102(C)(1)✓
  • c.Table 310.16
  • d.Table 250.122

Supply-side bonding jumpers are sized from Table 250.102(C)(1), based on the ungrounded supply conductors, not from the equipment grounding conductor table. See NEC 250.102(C)(1).2026 NEC §250.102(C)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

What is the rule for a bare aluminum grounding electrode conductor near the earth?

  • a.It must be installed within 18 inches of the earth
  • b.It may not be terminated within 18 inches of the earth where run outside a building✓
  • c.It may be terminated at any height above the earth, the same as copper
  • d.Aluminum grounding electrode conductors are prohibited entirely

An aluminum grounding electrode conductor run outside a building or equipment enclosure may not be terminated within 18 inches of the earth. Bare aluminum also may not be installed in direct contact with concrete or where subject to corrosive conditions. See NEC 250.64(A).2026 NEC §250.64(A)

Electrical Services, Service Equipment, and Separately Derived Systems

How must the multiple grounding electrodes present at a building be arranged?

  • a.Electrodes must be at least 100 feet apart
  • b.A ground rod may never be combined with a water pipe electrode
  • c.All electrodes present must be bonded together to form the grounding electrode system✓
  • d.Only one electrode is permitted per building

All grounding electrodes that are present, such as a water pipe, concrete-encased electrode and ground rods, must be bonded together to form the grounding electrode system. See NEC 250.50.2026 NEC §250.50

Electrical Services, Service Equipment, and Separately Derived Systems

What is the maximum setting permitted for the ground-fault protection of equipment on a service disconnecting means?

  • a.600 amperes
  • b.800 amperes
  • c.1000 amperes
  • d.1200 amperes✓

Section 230.95(C) caps the ground-fault protection setting at 1200 amperes. The 1000 ampere figure is the disconnect rating at which the protection becomes required under 230.95(A), not the pickup setting, and that swap is the usual mistake.2026 NEC §230.95(C)