Chapter 3 of 10

Electrical Feeders: Sizing, Protection and Load Calculations

A feeder is the set of conductors between the service equipment and the last branch-circuit overcurrent device, so every feeder question comes down to three things: how much load it carries, what protects it, and what size wire that requires. This chapter walks through the feeder rules in the order you would use them on a job, with the 2026 Code sections to tab in your book. Most of the calculation items are short: one factor, one table, one answer.

Continuous loads: the 125 percent habit

The most common feeder calculation asks for the minimum overcurrent device or conductor when part of the load is continuous. The rule is the same for both: take the noncontinuous load at 100 percent, add 125 percent of the continuous load, and size to the result. The extra 25 percent exists because devices and terminations heat up when they carry current for hours, and the margin keeps them inside their temperature limits. For the device, the answer is the next standard rating at or above the calculated number. A feeder with 30 amperes continuous and 50 amperes noncontinuous needs 50 + (30 x 1.25) = 87.5 amperes, so the answer is 90 amperes. If the result lands exactly on a standard size, use it: 60 + (40 x 1.25) = 110 amperes, and 110 is the answer. When the question gives watts, find the current first. An 8-kilowatt continuous load at 240 volts single-phase draws 8,000 / 240 = 33.3 amperes, times 1.25 is 41.7 amperes, and the next standard size is 45 amperes. For the conductor, compare the same calculated ampacity to the column that matches the terminations. With 75 degree C terminations, a 100-ampere continuous load needs 125 amperes: 2 AWG copper at 115 amperes falls short and 1 AWG at 130 amperes passes. A 90 degree C insulation such as THHN does not let you read the 90 degree column for the final size when the terminations are rated 75 degrees C. A 200-ampere feeder with 75 degree terminations needs 3/0 AWG copper (200 amperes), because 2/0 is only 175 amperes in that column. The wrong choices are predictable: the plain sum without the 125 percent factor, or a device two sizes up. PSI's rules for this exam say conductors are copper unless the question states otherwise, and that exceptions and optional methods are ignored unless the question calls for them.

Feeder overcurrent device
Rate the device for the noncontinuous load plus 125 percent of the continuous load, then go to the next standard size.
2026 NEC §215.5
Feeder conductor ampacity
The conductor must carry the noncontinuous load plus 125 percent of the continuous load.
2026 NEC §215.4(A)(1)
Termination temperature
With 75 degree C terminations the final ampacity comes from the 75 degree C column, even for 90 degree C wire.
2026 NEC §110.14(C)(1)(b)
Next size up limit
Rounding up to the next standard device above the conductor ampacity is allowed only up to 800 amperes.
2026 NEC §240.4(B)

Dwelling feeder loads in Article 120

Load calculations now live in Article 120, so that is where your tabs belong. The standard dwelling calculation is built from a few pieces, and the exam usually tests one piece at a time. General lighting, small-appliance and laundry loads are added together and then reduced: the first 3,000 volt-amperes counts at 100 percent and the rest, up to 120,000, at 35 percent. For a 12,000 volt-ampere total that is 3,000 + (9,000 x 0.35) = 6,150 volt-amperes. The trap is taking 35 percent of the whole amount. Each small-appliance circuit goes in at 1,500 volt-amperes, so the two required circuits add 3,000 before any demand factor. A household dryer is entered at 5,000 volt-amperes or its nameplate, whichever is larger. A 4.5-kilowatt dryer is counted at 5,000; a 5.5-kilowatt dryer at 5,500. Fastened-in-place appliances get a 75 percent factor only when there are four or more on the feeder, each at least 1/4 horsepower or 500 watts. With three, use 100 percent. Ranges, dryers, heating, air-conditioning and vehicle charging equipment do not count toward the four. For household ranges not over 12 kilowatts each, read Column C of the range table: one range is 8 kilowatts, two are 11, three are 14. Do not multiply nameplates. Two more items appear. Show windows are figured at 200 volt-amperes per linear foot, so 15 feet is 3,000 volt-amperes. Where a feeder supplies several motors with other loads, the largest motor is taken at 125 percent of its full-load current. If the question names the optional dwelling method, the general loads take the first 8 kVA at 100 percent and the remainder at 40 percent: 40 kVA becomes 8 + (32 x 0.40) = 20.8 kVA.

Lighting demand
First 3,000 VA at 100 percent, remainder to 120,000 VA at 35 percent.
2026 NEC Table 120.45
Dryer load
Use 5,000 VA or the nameplate rating, whichever is larger.
2026 NEC §120.54
Fastened-in-place appliances
Four or more qualifying appliances on one dwelling feeder may be taken at 75 percent of their nameplate total.
2026 NEC §120.53
Household ranges
Column C gives 8, 11 and 14 kW for one, two and three ranges of 12 kW or less.
2026 NEC Table 120.55
Optional method general loads
First 8 kVA at 100 percent and the rest at 40 percent.
2026 NEC §120.82(B)

The feeder neutral

The neutral carries only the unbalanced current, and at higher currents the line-to-neutral loads are unlikely to all be on at once. The Code allows a reduction for that reason: the first 200 amperes of maximum unbalanced load counts at 100 percent and the part above 200 amperes at 70 percent. A 250-ampere unbalanced load becomes 200 + (50 x 0.70) = 235 amperes. The reduction does not apply to nonlinear loads on a wye system, because harmonic currents can load that neutral as heavily as the phases. If a question asks where the demand factor starts, the answer is 200 amperes.

Neutral reduction threshold
Only the portion of the unbalanced neutral load above 200 amperes may be reduced.
2026 NEC §120.61(B)
Neutral reduction amount
The portion over 200 amperes is taken at 70 percent.
2026 NEC §120.61(B)(2)

Equipment grounding conductors for feeders

The equipment grounding conductor table is entered with the rating of the overcurrent device, not the wire size or the load. For copper the feeder rows to know are 200 amperes: 6 AWG, 300 amperes: 4 AWG, 400 amperes: 3 AWG, 500 amperes: 2 AWG. The wrong choices are almost always the row above or below, so put a straightedge on the table. If the ungrounded conductors are made larger, for example to control voltage drop, the wire-type grounding conductor must grow in the same proportion by circular-mil area. Take a 100-ampere feeder whose 3 AWG conductors (52,620 circular mils) are upsized to 1/0 AWG (105,600 circular mils). The ratio is about 2.0. The table grounding conductor for 100 amperes is 8 AWG at 16,510 circular mils; doubled, that is about 33,100. A 6 AWG has only 26,240 circular mils, so the answer is 4 AWG at 41,740.

Size by device rating
Read the copper column at the row for the overcurrent device ahead of the feeder.
2026 NEC Table 250.122
Upsized conductors
Increase the equipment grounding conductor in proportion to the circular-mil increase of the ungrounded conductors.
2026 NEC §250.122(D)

Feeder taps

A tap is a smaller conductor connected to a feeder without its own overcurrent device at the point of connection. Because the tap is under-protected for some distance, the Code limits length and controls how it ends. First, the next-size-up allowance does not apply to taps. The device at the end of the tap may not be larger than the tap conductor ampacity. A tap made under the 25-foot rule must end in a single circuit breaker or a single set of fuses that limits the load to the tap ampacity; that one device can then feed any number of others. The rule for longer taps in high bay manufacturing buildings sets a floor of 6 AWG copper or 4 AWG aluminum, and the tap must still have at least one-third of the feeder device rating. Where a tap supplies a transformer, the primary conductor plus the secondary conductor together are limited to 25 feet, not counting any part of the primary that is protected at its ampacity. With 9 feet of unprotected primary, the secondary can be no longer than 25 - 9 = 16 feet.

No rounding up on taps
The next higher standard device rating is not permitted for tap conductors.
2026 NEC §240.21(B)
25-foot tap termination
The tap ends in one breaker or one set of fuses sized to the tap ampacity.
2026 NEC §240.21(B)(2)
Transformer tap length
Primary plus secondary conductor length may not exceed 25 feet in total.
2026 NEC §240.21(B)(3)
High bay tap minimum
Tap conductors are at least 6 AWG copper or 4 AWG aluminum.
2026 NEC §240.21(B)(4)

Ground-fault protection, identification and voltage drop

Ground-fault protection of equipment is required for a feeder disconnect only when every part of a three-part test is met: rated 1000 amperes or more, on a solidly grounded wye system, with more than 150 volts to ground and not over 1000 volts phase to phase. A 1200-ampere disconnect on a 480Y/277-volt system qualifies. A 208Y/120-volt system does not, because it is only 120 volts to ground. Where a building has more than one nominal voltage system, each ungrounded feeder conductor must be identified by phase or line and by system at every termination, connection and splice point, and the method must be documented or posted at each feeder panelboard or similar distribution equipment. One more look-up item: where a feeder carries the whole load of service conductors rated 55 amperes or less, the feeder ampacity may not be smaller than that of the service conductors. Worked example, three-phase voltage drop. A 480-volt, three-phase feeder carries 40 amperes for 250 feet on 6 AWG copper (26,240 circular mils), with K = 12.9. Step 1: pick the three-phase formula, VD = (1.732 x K x I x L) / CM. Step 2: multiply the top line: 1.732 x 12.9 x 40 x 250 = 223,428. Step 3: divide by the circular mils: 223,428 / 26,240 = about 8.5 volts. Step 4: check the percentage: 8.5 / 480 is roughly 1.8 percent. L is the one-way length. The wrong answers come from dropping the 1.732 (4.9 volts), using it twice (14.8 volts), or doubling the length as if this were a single-phase run (17.0 volts).

Feeder ground-fault protection
Required at 1000 amperes or more on solidly grounded wye systems over 150 volts to ground and not over 1000 volts phase to phase.
2026 NEC §215.10(A)
Identification by system
With more than one voltage system, identify each ungrounded feeder conductor at all termination, connection and splice points and post the method at feeder distribution equipment.
2026 NEC §215.12(C)(2)
Feeder versus small service
A feeder carrying the full load of service conductors of 55 amperes or less may not have less ampacity than they do.
2026 NEC §215.4(C)
Circular-mil areas
Conductor areas for voltage-drop formulas come from the conductor properties table.
2026 NEC Chapter 9, Table 8