Special Occupancies, Equipment and Conditions
This area covers the places where the general wiring rules are not enough: hazardous locations, garages, health care, mobile homes, marinas, pools and emergency systems. Most questions are look-ups of one number in one article, so your job is to know which article owns the topic and which neighbouring number the wrong answers are borrowed from. A few short calculations come from the mobile home and pool rules.
Reading a hazardous location: class, division, group, temperature
A hazardous location label has three parts and each answers a different question. The class tells you what the fuel is. Class I is flammable gas or vapor, Class II is combustible dust, and Class III is fibers and flyings. The division tells you how often the fuel is there. Division 1 means an ignitible concentration can exist in normal operation. Division 2 means it shows up only when something goes wrong. A solvent room that stays safe only because its exhaust fans are running is the standard Division 2 example: the hazard appears if the ventilation fails. The trap is metal dust. Aluminum and other combustible metal dusts are Group E, and a Group E location is Class II, Division 1 even when the dust is present only under abnormal conditions. Dust groups are worth memorizing: Group E is metal, Group F is carbonaceous dust such as coal with more than 8 percent total entrapped volatiles, and Group G is everything else, including flour, grain, wood and plastic. Equipment carries a temperature class so its surface cannot ignite the atmosphere. From the table, T3 is 200°C and T4 is 135°C, and the wrong answers are the rows on either side. Two more equipment rules are asked often. Explosionproof equipment may not be used below -25°C ambient unless identified for low temperature. Dusttight equipment is accepted in Class II, Division 2 and in Class III, but not in Class II, Division 1. If a question offers Zone-marked equipment for a Class I, Division 1 location, only Zone 0 equipment qualifies.
Class I wiring: threads, seals and bonding
In Division 1 the wiring itself has to contain an explosion, which is why the rules keep coming back to threaded joints. Rigid and intermediate metal conduit must use threaded connections. Field-cut NPT threads entering explosionproof equipment are made up wrenchtight with at least five threads fully engaged. PVC conduit is accepted underground only when it is encased in at least 2 in. of concrete. Seals stop gas and flame from travelling through the conduit. The numbers to know: a splice-only explosionproof enclosure needs a seal at entries of trade size 2 or larger. One seal can serve two enclosures if the nipple between them is 36 in. or less and the seal is within 18 in. of each. Sealing compound must have a melting point of at least 200°F, and conductors in a seal may fill no more than 25 percent of the area of rigid metal conduit of the same trade size. Exam writers swap the 18 in. and 36 in. figures, so read whether the question asks for the seal distance or the nipple length. Bonding is stricter too. Locknut-bushing and double-locknut connections are not accepted as the bonding means in a hazardous location. In Division 2, a short length of listed liquidtight flexible metal conduit can go without a bonding jumper only on a meter, instrument or relay circuit protected at 10 amperes or less.
Garages, fuel dispensers and patient care
Not every garage is classified. A garage used only for parking or storage may be unclassified. In a repair garage, the space within 3 ft in every direction of a point where a Class I liquid other than fuel is dispensed is Class I, Division 2. An adjacent stock room can be unclassified if it is mechanically ventilated at four or more air changes per hour. At a motor fuel dispenser, the Code figure shows the Class I, Division 2 area reaching 20 ft horizontally from the dispenser. Health care questions at this level are about grounding around the patient. Where a normal panelboard and an essential panelboard serve the same patient care vicinity, their grounding buses are tied together with an insulated continuous copper conductor of at least 10 AWG. An isolated ground receptacle is not allowed inside a patient care vicinity.
Mobile homes, RVs and marinas
Mobile home questions mix look-ups with small calculations. The look-ups: a mobile home may be supplied by one listed feeder assembly rated 50 amperes, the cord is between 21 ft and 36 1/2 ft overall, the bottom of the distribution equipment is at least 24 in. above the floor, the heat tape outlet is within 2 ft of the cold water inlet, and the service equipment is rated at least 100 amperes at 120/240 volts. Worked example: a mobile home measures 80 ft by 15 ft outside, coupler excluded. How many 15-ampere lighting circuits does it need at 3 VA per square foot and 120 volts? Step 1, area: 80 x 15 = 1200 sq ft. Step 2, load: 1200 x 3 VA = 3600 VA. Step 3, current: 3600 / 120 = 30 amperes. Step 4, circuits: 30 / 15 = 2 circuits. The appliance limits are percentages of the circuit rating. A single cord-and-plug appliance on a circuit with no other outlets may be rated up to 80 percent of the circuit, so 16 amperes on a 20-ampere circuit. If lighting outlets share the circuit, fixed appliances may total only 50 percent, so 7.5 amperes on a 15-ampere circuit. Going the other way, a single appliance of 13.3 amperes or more on an individual circuit may have an overcurrent device up to 150 percent of its rating: 16 x 1.5 = 24 amperes. Unless a question says otherwise, the exam ignores exceptions and optional methods and assumes copper conductors, so work these with the basic rule. For an RV, generator supply conductors must terminate within 18 in. of where they enter the vehicle. At a marina, floating dock service equipment sits on land at least 5 ft from the structure, shore power comes from single receptacles rated at least 30 amperes, and each shore power receptacle has ground-fault protection of equipment rated 30 mA or less.
Pools: distances, depths and bonding
Pool rules exist because wet skin and a grounded body of water make small voltages dangerous. Receptacles stay at least 6 ft from the inside wall of a permanently installed pool, and at least one required receptacle must fall between 6 ft and 20 ft. Indoors, a totally enclosed luminaire on a GFCI-protected circuit may be as low as 7 ft 6 in. above the maximum water level. A wall-mounted underwater luminaire not listed for a lesser depth has the top of its lens at least 18 in. below normal water level. A wet-niche luminaire cord carries an equipment grounding conductor no smaller than 16 AWG, and a pool junction box needs one more grounding terminal than it has conduit entries, so three entries need four terminals. Equipotential bonding uses solid copper no smaller than 8 AWG, and perimeter surface bonding connects to the pool steel or grid at four or more evenly spaced points. For circuits above 150 volts to ground, the special purpose GFCI may trip at up to 20 mA. Electric pool water heaters give you one calculation. Resistance elements are subdivided into loads of 48 amperes or less, each protected at 60 amperes or less, and the branch-circuit conductors are sized at 125 percent of the nameplate load: 40 x 1.25 = 50 amperes. The same 125 percent continuous-load step applies to a 40-ampere electric vehicle charging load, which also comes out to 50 amperes.
Emergency and standby systems
Emergency system questions test two time figures that are easy to swap. An on-site fuel supply for a generator must run the system for at least 2 hours. Batteries feeding emergency illumination must carry the load for at least 1 1/2 hours. Exposed emergency cable or raceway with no boxes along it is marked at intervals of 25 ft or less. Meter-mounted transfer switches are not permitted on emergency systems. When one source feeds several kinds of load through load management, emergency circuits come first, then legally required standby, then optional standby. An optional standby system with a manual transfer switch only has to carry the equipment intended to run at one time, not the whole building.
Keep going: the full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) guide covers every section of the exam. Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
Want the dense 50-page printable for exam week? Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) cheat sheet PDF — $9.99 →

Practice stays free. The full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.