Motors and Generators: Four Numbers for Every Motor Circuit
Almost every motor question on the journeyman exam asks for one of four things: the conductor, the short-circuit and ground-fault device, the overload device, or the feeder. Each one has its own percentage and its own starting current. This chapter shows which current and which percentage belong to each, then finishes with the two generator rules in the bank.
Start with the right current: table or nameplate
A motor has two full-load currents and the Code uses both. One is printed on the motor nameplate. The other comes from the Code tables: Table 430.248 for single-phase motors and Table 430.250 for three-phase motors. Section 430.6(A)(1) tells you to use the table value for the conductors, for the branch-circuit short-circuit and ground-fault protection, and for the disconnect rating. The reason is practical. The wiring stays in the building for decades, while the motor may be replaced by another maker's motor of the same horsepower with a slightly different nameplate. The table value is conservative and does not depend on any one manufacturer. The nameplate current is used for one job only: the overload device, because that device protects the particular motor that is actually installed. The exam tests this by giving you both numbers. A typical item describes a 25-horsepower motor with a table current of 34 amperes and a nameplate current of 32 amperes. Use 34 for the wire and the breaker, and 32 for the overloads. Mixing them is the most common way to lose the point.
Branch-circuit conductors: 125 percent
The conductors to a single continuous-duty motor need an ampacity of at least 125 percent of the table full-load current. Multiply, then go to the 75 degree C column of Table 310.16 and pick the first size that is equal to or greater than your number. Conductors are copper unless the question says otherwise. Equal counts. A 5-horsepower, 230-volt single-phase motor at 28 amperes needs 28 x 1.25 = 35 amperes, and 10 AWG copper is exactly 35 amperes in the 75 degree C column, so 10 AWG is the answer. Do not step up a size out of habit. The question asks for the minimum. There is also a floor. A small motor at 7.6 amperes needs only 9.5 amperes, but 430.22(G) makes 14 AWG the smallest motor conductor unless special conditions for 18 or 16 AWG are given, so the answer is 14 AWG. Motors that do not run continuously get a different treatment. Table 430.22(E) sizes the conductor as a percentage of the nameplate current that depends on the type of duty and the time rating of the motor. For intermittent duty with a 15-minute rated motor the figure is 85 percent, so a 40-ampere nameplate needs 40 x 0.85 = 34 amperes.
Short-circuit and ground-fault protection: the big percentages
A motor draws several times its running current while it starts. If the branch breaker were sized like an ordinary circuit, it would trip on every start. So the Code lets the fuse or breaker be much larger than the wire rating and gives it only one job: clearing short circuits and ground faults. Overloads are handled by a separate device. Table 430.52(C)(1) gives the maximum as a percentage of the table full-load current. For squirrel-cage motors the three figures to know are 175 percent for a dual-element time-delay fuse, 250 percent for an inverse-time circuit breaker, and 300 percent for a non-time-delay fuse. A wound-rotor motor has its own row, and an inverse-time breaker there is limited to 150 percent. When the result is not a standard rating, 430.52(C)(1)(a) lets you go up to the next standard size in Table 240.6(A). One size up only. For a 22-ampere motor on an inverse-time breaker, 22 x 2.5 = 55 amperes, and the answer is 60 amperes. The wrong choices are usually the size below (rounding down) or two sizes up. Be aware that a 10 AWG conductor can end up behind a breaker far larger than 30 amperes on a motor circuit. That is correct, because motor branch-circuit protection is sized under Article 430.
Overload protection: nameplate current
The overload device protects the motor windings from running hot, so it is sized from the nameplate. For a continuous-duty motor over 1 horsepower with a separate overload device, 430.32(A)(1) allows 125 percent of nameplate current if the motor is marked with a service factor of 1.15 or greater, or with a temperature rise of 40 degrees C or less. Every other motor is limited to 115 percent, because it has less thermal margin. A motor marked service factor 1.0 and 50 degrees C rise with an 18-ampere nameplate gets 18 x 1.15 = 20.7 amperes. If the device chosen at the basic percentage will not let the motor start or carry its load, 430.32(C) allows an increase: up to 140 percent for the better-rated motors and up to 130 percent for all others. A thermal protector built into the motor follows 430.32(A)(2) and is based on the table current: 170 percent where the full-load current does not exceed 9 amperes, 156 percent from 9.1 through 20 amperes, and 140 percent above 20 amperes. Table 430.37 sets how many overload units are needed. A three-phase motor needs three, one in each phase, so that the loss of one phase is detected. A single-phase, two-wire motor needs one.
Worked example: one motor, then the feeder
A 25-horsepower, 460-volt, three-phase squirrel-cage motor has a table full-load current of 34 amperes, a nameplate current of 32 amperes and a marked service factor of 1.15. Step 1, conductor. 34 x 1.25 = 42.5 amperes. In the 75 degree C column, 10 AWG copper is 35 amperes and fails, and 8 AWG is 50 amperes. Answer: 8 AWG. Step 2, inverse-time breaker. 34 x 2.50 = 85 amperes. Not a standard rating, so go up one size. Answer: 90 amperes. With a dual-element fuse it would be 34 x 1.75 = 59.5, so 60 amperes. With a non-time-delay fuse, 34 x 3.00 = 102, so 110 amperes. Step 3, overload. Use the nameplate: 32 x 1.25 = 40 amperes. Step 4, feeder conductor. Add a 10-horsepower motor at 14 amperes to the same feeder. Section 430.24 takes 125 percent of the largest motor plus the full-load currents of the rest: (34 x 1.25) + 14 = 56.5 amperes. The largest motor means the one with the highest full-load current. Adding the two currents with no increase gives 48, and applying 125 percent to both gives 67.5. Both appear as wrong choices. Step 5, feeder overcurrent device. Section 430.62(A) caps it at the largest branch-circuit device plus the full-load currents of the other motors: 90 + 14 = 104 amperes. This is a ceiling, so you round down. Answer: 100 amperes. Rounding up is allowed for the branch device in Step 2 and not here. The exam uses that difference on purpose.
Generators
Generator questions in this area are short. Under 445.13(A), the conductors from the generator terminals to the first overcurrent device need an ampacity of at least 115 percent of the generator nameplate current rating. A 200-ampere generator needs 200 x 1.15 = 230 amperes. A 150-ampere generator needs 172.5 amperes. In the 75 degree C copper column 1/0 AWG is 150 amperes and fails, and 2/0 AWG at 175 amperes is the answer. The trap is using 125 percent out of motor habit. Under 445.19(B), a generator rated greater than 15 kW must have a remote emergency shutdown device, except at one- and two-family dwelling units. One last reminder for this whole area: the exam follows the general rule. Ignore exceptions and optional methods unless the question itself tells you to apply one.