Branch Circuits and Conductors
Branch circuits are where most of your daily work happens, and the exam covers them from both sides: the rules questions on required circuits, receptacle placement and protection, and the calculation questions on continuous loads, ampacity and voltage drop. This chapter groups the rules by where they sit in the 2026 Code so you can find them fast with the book open.
Continuous loads and what a circuit may supply
A continuous load makes both the overcurrent device and the conductor larger by a factor of 125 percent. For the device, multiply and go to the next standard rating: 24 amperes x 1.25 = 30 amperes, 16 x 1.25 = 20, 20 x 1.25 = 25 (a standard size), and 44 x 1.25 = 55, which is not standard, so 60 amperes. If the load is given in watts, get the current first: a 5,000-watt, 240-volt heater draws 20.8 amperes, times 1.25 is 26, and the device is 30 amperes. Run the rule backward and you get the limit on an existing circuit: a 15-ampere circuit can carry 15 x 0.80 = 12 amperes of continuous load. For the conductor, compare the 125 percent figure to the 75 degree C column when the question gives 75 degree terminations. A 32-ampere continuous load needs 40 amperes: 10 AWG copper at 35 amperes fails and 8 AWG at 50 amperes passes. A 24-ampere continuous load needs 30 amperes, so 10 AWG. Watch the small conductors: for a 16-ampere continuous load, 14 AWG shows 20 amperes in the table, but the small-conductor rule holds 14 AWG to a 15-ampere device, so the answer is 12 AWG. The Code also limits what you plug into a shared circuit. On a 15- or 20-ampere circuit, one cord-and-plug appliance that is not fastened in place may use up to 80 percent of the rating, 16 amperes on a 20-ampere circuit. Fastened-in-place equipment other than luminaires on a circuit that also supplies lighting is limited to 50 percent, 7.5 amperes on a 15-ampere circuit. On a 30-ampere circuit one cord-and-plug appliance is limited to 24 amperes. A multiple-outlet circuit larger than 50 amperes may serve only nonlighting outlet loads, and two or more receptacles on a 40-ampere circuit must be rated 40 or 50 amperes.
Ampacity: table value, correction and adjustment
A conductor's ampacity starts in the ampacity table and is then reduced for conditions. Two things reduce it: ambient temperature above 30 degrees C (correction) and more than three current-carrying conductors in one raceway (adjustment). Heat is the reason for both. Wires in hot surroundings or bundled together cannot shed heat as well. The key habit is where you start. With 90 degree C insulation such as THHN or THWN-2, you apply the factors to the 90 degree C value, then check the result against the termination limit afterward. The adjustment factors are 80 percent for 4 to 6 conductors, 70 percent for 7 to 9, and 50 percent for 10 to 20. So six 12 AWG THHN (30 amperes at 90 degrees C) carry 30 x 0.80 = 24 amperes each, and nine 10 AWG (40 amperes) carry 40 x 0.70 = 28. Small conductors still obey their device limit: four 10 AWG adjust to 32 amperes, but the device stays at 30. Worked example. Four current-carrying 8 AWG THWN-2 copper conductors run in a raceway through a 48 degree C ambient. Find the ampacity of each. Step 1: take the 90 degree C table value for 8 AWG copper: 55 amperes. Step 2: find the correction factor for the 46 to 50 degree C range: 0.82. Step 3: find the adjustment factor for four conductors: 0.80. Step 4: multiply all three: 55 x 0.82 x 0.80 = 36 amperes. The wrong answers are built from partial work: 44 amperes uses only the 80 percent, and 40 or 33 amperes start from the 75 degree C value of 50. The same method gives 30 x 0.91 x 0.50 = 13.65 amperes for twelve 12 AWG at 38 degrees C, where 0.91 covers 36 to 40 degrees C. On counting conductors: the equipment grounding conductor is never counted. The neutral of a 4-wire, three-phase wye circuit is counted when the major portion of the load is nonlinear, which makes four. For straight look-ups, 4/0 AWG copper is 230 amperes in the 75 degree C column, and the general minimum conductor size is 16 AWG copper.
Required dwelling circuits and their loads
A dwelling needs certain circuits no matter how it is laid out: at least two 20-ampere small-appliance circuits for the kitchen, pantry, breakfast room and dining room receptacles, at least one 20-ampere circuit for the laundry receptacles, and a 20-ampere circuit for bathroom receptacles. These circuits are dedicated to those uses. In the load calculation, general lighting for a dwelling is 2 volt-amperes per square foot, so 2,000 square feet is 4,000 volt-amperes and 2,500 square feet is 5,000. The wrong choice uses 3 volt-amperes per square foot, which is not the current value. General-use 15- and 20-ampere receptacles are already included in that figure and are not added separately. Each small-appliance and laundry circuit adds 1,500 volt-amperes: two plus one is 4,500. These figures are in Article 120. For a single household range over 12 kilowatts, start with the 8 kilowatts from Column C and add 5 percent for each kilowatt above 12. A 16-kilowatt range is 8 x 1.20 = 9.6 kilowatts. A multiwire branch circuit shares one neutral between ungrounded conductors, so all of its ungrounded conductors must open together at the point where the circuit originates.
Receptacle and lighting outlet placement
Placement questions are pure look-up, and every wrong choice is a real number from a neighboring rule. Keep the measurements paired with their locations. General wall space: no point along the floor line may be more than 6 feet from a receptacle, which works out to 12 feet between outlets. Kitchen countertops: no point along the wall line more than 24 inches from a receptacle, a countertop or work surface 12 inches or wider needs one, and the receptacle may be no more than 20 inches above the countertop. Bathrooms: a receptacle within 3 feet of the outside edge of each basin. Hallways: at least one receptacle when the hallway is 10 feet or longer. Garages: at least one receptacle in each vehicle bay, not more than 5 1/2 feet above the floor. For lighting, an interior stairway with six or more risers between floor levels needs switch control at each floor level and at each landing that has a stairway entry.
GFCI and AFCI protection
The two devices guard against different hazards, and the exam likes to swap their lists. GFCI protects people from shock, so it follows water and grounded surfaces: bathrooms, kitchens, laundry areas, garages, basements whether finished or not, crawl spaces and outdoors. Receptacles within 6 feet of the top inside edge of a sink bowl are included. AFCI protects against fires from arcing in the wiring, so it follows the living space: bedrooms, living rooms, kitchens, laundry areas and most other habitable rooms. Kitchens and laundry areas are on both lists. A bedroom, hallway or closet is an AFCI answer, not a GFCI answer. PSI's rules for this exam say to ignore exceptions unless the question raises them, and to treat conductors as copper unless stated.
Voltage drop and equipment grounding conductors
For a single-phase circuit, voltage drop is (2 x K x I x L) / CM, where L is the one-way length and the 2 accounts for the trip out and back. A 20-ampere load 100 feet away on 12 AWG copper (6,530 circular mils) with K = 12.9 drops (2 x 12.9 x 20 x 100) / 6,530 = about 7.9 volts. Leaving out the 2 gives 3.9 volts, which will be one of the choices. To size a wire for a target, turn the formula around. For 12 amperes at 120 feet with a 3 percent target on 120 volts, the allowed drop is 3.6 volts and CM = (2 x 12.9 x 12 x 120) / 3.6 = 10,320. A 12 AWG has 6,530 circular mils and fails; 10 AWG has 10,380 and passes. The equipment grounding conductor is sized from the overcurrent device rating. For copper: 15 amperes is 14 AWG, 20 is 12 AWG, 60 is 10 AWG, 100 is 8 AWG. If the circuit conductors are upsized, the grounding conductor is increased in the same circular-mil proportion, but it never has to be larger than the circuit conductors themselves.
Keep going: the full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) guide covers every section of the exam. Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
Want the dense 50-page printable for exam week? Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) cheat sheet PDF — $9.99 →

Practice stays free. The full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.