Chapter 10 of 10

Renewable Energy Technologies: Photovoltaics and EV Chargers

This area covers two articles you will use more every year: electric vehicle charging equipment and photovoltaic systems. The EV questions are mostly single look-ups. The PV questions lean on a small set of multipliers, and the main skill is knowing how many times to apply 125 percent.

The EV charging circuit

An EV charger draws its full current for hours, so the Code classifies electric vehicle supply equipment (EVSE) as a continuous load. That one classification drives the circuit sizing: you size with the continuous load rules and not at 100 percent of the charger current. If a question asks how the Code treats EVSE loads, the answer is continuous, and any answer that sizes the circuit at the bare charger current is the trap. Larger chargers do not share circuits. An outlet supplying EVSE rated more than 16 amperes or more than 120 volts must be on an individual branch circuit. Remember both triggers, because the question may give you only one of them. Cord-and-plug-connected equipment has its own plug rule. The attachment plug must be rated at least 125 percent of the equipment's maximum rating, so 24-ampere equipment needs a plug rated 24 x 1.25 = 30 amperes. Article 625 also closes a door the general receptacle table leaves open: a 50-ampere receptacle for EVSE may not be installed on a 40-ampere branch circuit. Finally, every receptacle installed for connecting EV charging needs GFCI protection for personnel. There is no voltage, ampere or location limit on that rule, so pick the answer that says all of them.

Continuous load
EVSE is treated as a continuous load when sizing its supply circuit.
2026 NEC §625.41
Individual branch circuit
EVSE rated above 16 amperes or above 120 volts needs its own branch circuit.
2026 NEC §625.40
Plug and receptacle rating
The plug is rated at least 125 percent of the equipment rating, and a 50-ampere EVSE receptacle may not go on a 40-ampere circuit.
2026 NEC §625.44
GFCI
All receptacles installed for EV charging need GFCI protection for personnel.
2026 NEC §625.54

EVSE installation details: cable, coupler height, ventilation

Three installation details show up as look-ups. The output cable to the vehicle is limited to an overall usable length of 25 ft unless the listed equipment includes a cable management system. Outdoors, fixed equipment that is not specifically listed and marked for its location must store the coupling means at least 24 in. above grade. The wrong answer most people choose is 18 in., which is the indoor figure measured above the floor. Ventilation questions are simple multiplication. Where the EVSE is listed for vehicles that need ventilation during indoor charging, the table gives an airflow per vehicle for the circuit voltage and ampere rating, and you multiply by the number of vehicles that can charge at once. With three vehicles on 208-volt single-phase, 40-ampere circuits at 171 cfm each, the minimum is 3 x 171 = 513 cfm. Make sure you are in the correct column: the single-phase and three-phase values at the same voltage are different.

Output cable length
Usable output cable length is limited to 25 ft without a listed cable management system.
2026 NEC §625.17(C)
Coupler storage height
Outdoors the coupling means is stored at least 24 in. above grade unless the equipment is listed and marked otherwise.
2026 NEC §625.50
Ventilation
Multiply the per-vehicle table airflow by the number of vehicles that can charge at one time.
2026 NEC Table 625.52(B)(1)(2)

PV system voltage and general rules

A PV module produces its highest voltage when it is cold, so the Code makes you design for the coldest expected day and not for the nameplate. For crystalline silicon modules, add the rated open-circuit voltages of the modules in series, then multiply by the correction factor from the table for the lowest expected ambient temperature. Twelve modules at 40 volts give 12 x 40 = 480 volts. At -8°C the factor is 1.14, so the maximum circuit voltage is 480 x 1.14 = 547.2 volts. The wrong answers skip the correction or take the factor from the temperature band above or below, so find the band carefully. That result then has to fit under a limit. On or in a one- or two-family dwelling, PV dc circuits may not exceed 600 volts. The 547.2-volt string above would pass on a house. A few general rules round this out. PV equipment and its disconnecting means may not be installed in bathrooms. Calculations under the PV article may be rounded to the nearest whole number, dropping a fraction below 0.5, so 12.4 becomes 12. An ac module has its inverter built in, so its output is treated as an inverter output circuit and the dc source circuit rules do not apply to it.

Cold-temperature voltage
Multiply the summed open-circuit voltage by the table factor for the lowest expected temperature.
2026 NEC Table 690.7(A)
Dwelling voltage limit
PV dc circuits on or in one- and two-family dwellings are limited to 600 volts.
2026 NEC §690.7
Prohibited location
PV equipment and disconnects may not be installed in bathrooms.
2026 NEC §690.4(D)
Rounding
Results may be rounded to the nearest whole number, dropping fractions under 0.5.
2026 NEC §690.4(G)
AC modules
The output of an ac module is an inverter output circuit.
2026 NEC §690.6(B)

PV circuit current and overcurrent protection

PV current questions are where points are lost, because 125 percent is applied twice for two different reasons. The first 125 percent accounts for sunlight stronger than the rating conditions: the maximum circuit current is 125 percent of the module short-circuit current. The second 125 percent is the sizing step for the conductor or the overcurrent device, applied to that maximum current. Worked example: a PV source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustment? Step 1, maximum circuit current: 10 x 1.25 = 12.5 amperes. Step 2, conductor sizing: 12.5 x 1.25 = 15.6 amperes. An answer of 12.5 amperes stopped after one step. With 8-ampere modules the same two steps give 10 amperes and then 12.5 amperes. Read the question for which step it wants. If it asks only for the maximum current of a source circuit with three 12-ampere modules in parallel, add the modules first and apply 125 percent once: 3 x 12 = 36, and 36 x 1.25 = 45 amperes. If it gives you a maximum current that has already been calculated, such as 16 amperes, and asks for the overcurrent device, apply 125 percent once more: 16 x 1.25 = 20 amperes. That second step is for a device that is not part of an assembly listed for continuous operation at 100 percent of its rating. One rule has no multiplier at all. A common-return conductor shared by several PV circuits needs an ampacity at least equal to the sum of the overcurrent device ratings of those circuits. For devices of 15, 15 and 20 amperes the answer is 50 amperes. As elsewhere on the exam, ignore exceptions and optional methods unless the question brings them up, and assume copper conductors unless told otherwise.

Conductor ampacity
Take 125 percent of short-circuit current for maximum current, then 125 percent again for the conductor.
2026 NEC §690.8
Parallel modules
Sum the parallel short-circuit currents, then multiply by 125 percent.
2026 NEC §690.8(A)(1)(a)(1)
Overcurrent device
A device not in a 100 percent rated assembly is rated at least 125 percent of the maximum current.
2026 NEC §690.9(B)(1)
Common-return conductor
Its ampacity is at least the sum of the individual circuit overcurrent device ratings.
2026 NEC §690.8(C)

Rapid shutdown, arc-fault protection, labels and interconnection

Rapid shutdown exists for firefighters. A rooftop array keeps producing voltage whenever the sun is up, so the Code requires a way to bring the conductors on a building down to a safe level. The array boundary is drawn 1 ft from the array in all directions. Controlled conductors outside that boundary must drop to 30 volts or less within 30 seconds of initiation. Do not confuse the 1 ft boundary with the 3 ft figure, which is measured from where conductors enter the building. The initiation device must be readily accessible, and on a one- or two-family dwelling it must be outdoors so responders can reach it without going inside. The building label that shows where the initiation devices are has a capitalized title with letters at least 3/8 in. high. Separately, each PV system disconnecting means is permanently marked as the PV system disconnect or with equivalent wording. PV dc circuits on a building need dc arc-fault protection when they operate at 80 volts dc or more between any two conductors. Keep 80 volts for arc-fault and 30 volts for rapid shutdown outside the boundary in separate boxes in your memory. Last, equipment that connects a power production source to run in parallel with the utility must be listed for the interactive function or be field labeled for it. Utility approval does not replace the listing.

Array boundary
The boundary extends 1 ft from the array in all directions.
2026 NEC §690.12(B)
Outside the boundary
Controlled conductors must fall to 30 volts or less within 30 seconds.
2026 NEC §690.12(B)(1)
Initiation device location
On one- and two-family dwellings it must be readily accessible and outdoors.
2026 NEC §690.12(C)(1)
DC arc-fault protection
Required on building PV dc circuits at 80 volts dc or more between conductors.
2026 NEC §690.11
Interactive equipment
Interconnection equipment must be listed or field labeled for the interactive function.
2026 NEC §705.2