Renewable Energy Technologies: Photovoltaics and EV Chargers
This area covers two articles you will use more every year: electric vehicle charging equipment and photovoltaic systems. The EV questions are mostly single look-ups. The PV questions lean on a small set of multipliers, and the main skill is knowing how many times to apply 125 percent.
The EV charging circuit
An EV charger draws its full current for hours, so the Code classifies electric vehicle supply equipment (EVSE) as a continuous load. That one classification drives the circuit sizing: you size with the continuous load rules and not at 100 percent of the charger current. If a question asks how the Code treats EVSE loads, the answer is continuous, and any answer that sizes the circuit at the bare charger current is the trap. Larger chargers do not share circuits. An outlet supplying EVSE rated more than 16 amperes or more than 120 volts must be on an individual branch circuit. Remember both triggers, because the question may give you only one of them. Cord-and-plug-connected equipment has its own plug rule. The attachment plug must be rated at least 125 percent of the equipment's maximum rating, so 24-ampere equipment needs a plug rated 24 x 1.25 = 30 amperes. Article 625 also closes a door the general receptacle table leaves open: a 50-ampere receptacle for EVSE may not be installed on a 40-ampere branch circuit. Finally, every receptacle installed for connecting EV charging needs GFCI protection for personnel. There is no voltage, ampere or location limit on that rule, so pick the answer that says all of them.
EVSE installation details: cable, coupler height, ventilation
Three installation details show up as look-ups. The output cable to the vehicle is limited to an overall usable length of 25 ft unless the listed equipment includes a cable management system. Outdoors, fixed equipment that is not specifically listed and marked for its location must store the coupling means at least 24 in. above grade. The wrong answer most people choose is 18 in., which is the indoor figure measured above the floor. Ventilation questions are simple multiplication. Where the EVSE is listed for vehicles that need ventilation during indoor charging, the table gives an airflow per vehicle for the circuit voltage and ampere rating, and you multiply by the number of vehicles that can charge at once. With three vehicles on 208-volt single-phase, 40-ampere circuits at 171 cfm each, the minimum is 3 x 171 = 513 cfm. Make sure you are in the correct column: the single-phase and three-phase values at the same voltage are different.
PV system voltage and general rules
A PV module produces its highest voltage when it is cold, so the Code makes you design for the coldest expected day and not for the nameplate. For crystalline silicon modules, add the rated open-circuit voltages of the modules in series, then multiply by the correction factor from the table for the lowest expected ambient temperature. Twelve modules at 40 volts give 12 x 40 = 480 volts. At -8°C the factor is 1.14, so the maximum circuit voltage is 480 x 1.14 = 547.2 volts. The wrong answers skip the correction or take the factor from the temperature band above or below, so find the band carefully. That result then has to fit under a limit. On or in a one- or two-family dwelling, PV dc circuits may not exceed 600 volts. The 547.2-volt string above would pass on a house. A few general rules round this out. PV equipment and its disconnecting means may not be installed in bathrooms. Calculations under the PV article may be rounded to the nearest whole number, dropping a fraction below 0.5, so 12.4 becomes 12. An ac module has its inverter built in, so its output is treated as an inverter output circuit and the dc source circuit rules do not apply to it.
PV circuit current and overcurrent protection
PV current questions are where points are lost, because 125 percent is applied twice for two different reasons. The first 125 percent accounts for sunlight stronger than the rating conditions: the maximum circuit current is 125 percent of the module short-circuit current. The second 125 percent is the sizing step for the conductor or the overcurrent device, applied to that maximum current. Worked example: a PV source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustment? Step 1, maximum circuit current: 10 x 1.25 = 12.5 amperes. Step 2, conductor sizing: 12.5 x 1.25 = 15.6 amperes. An answer of 12.5 amperes stopped after one step. With 8-ampere modules the same two steps give 10 amperes and then 12.5 amperes. Read the question for which step it wants. If it asks only for the maximum current of a source circuit with three 12-ampere modules in parallel, add the modules first and apply 125 percent once: 3 x 12 = 36, and 36 x 1.25 = 45 amperes. If it gives you a maximum current that has already been calculated, such as 16 amperes, and asks for the overcurrent device, apply 125 percent once more: 16 x 1.25 = 20 amperes. That second step is for a device that is not part of an assembly listed for continuous operation at 100 percent of its rating. One rule has no multiplier at all. A common-return conductor shared by several PV circuits needs an ampacity at least equal to the sum of the overcurrent device ratings of those circuits. For devices of 15, 15 and 20 amperes the answer is 50 amperes. As elsewhere on the exam, ignore exceptions and optional methods unless the question brings them up, and assume copper conductors unless told otherwise.
Rapid shutdown, arc-fault protection, labels and interconnection
Rapid shutdown exists for firefighters. A rooftop array keeps producing voltage whenever the sun is up, so the Code requires a way to bring the conductors on a building down to a safe level. The array boundary is drawn 1 ft from the array in all directions. Controlled conductors outside that boundary must drop to 30 volts or less within 30 seconds of initiation. Do not confuse the 1 ft boundary with the 3 ft figure, which is measured from where conductors enter the building. The initiation device must be readily accessible, and on a one- or two-family dwelling it must be outdoors so responders can reach it without going inside. The building label that shows where the initiation devices are has a capitalized title with letters at least 3/8 in. high. Separately, each PV system disconnecting means is permanently marked as the PV system disconnect or with equivalent wording. PV dc circuits on a building need dc arc-fault protection when they operate at 80 volts dc or more between any two conductors. Keep 80 volts for arc-fault and 30 volts for rapid shutdown outside the boundary in separate boxes in your memory. Last, equipment that connects a power production source to run in parallel with the utility must be listed for the interactive function or be field labeled for it. Utility approval does not replace the listing.