Control Devices and Disconnecting Means: Where It Goes and How Big It Is
Disconnect questions come in two kinds. Location questions ask where the switch must be and what it must be in sight of. Rating questions ask for a minimum ampere value, usually one multiplication. This chapter covers both for motors, air-conditioning equipment, services and detached buildings, with the section to open for each.
Three terms the questions depend on
Most location rules in this area use the same few terms, so learn them first. In sight from has a precise meaning in 110.29: the equipment is visible and not more than 50 feet away. Both parts must be true. A disconnect 30 feet away behind a wall fails, and so does one in plain view at 60 feet. Readily accessible is the second term. For overcurrent devices, 240.24(A) adds a measurable limit: the center of the grip of the operating handle, at its highest position, may be no more than 6 ft 7 in. above the floor or working platform. The measurement is to the handle, not to the top of the enclosure. Expect a wrong choice that measures to the cabinet. The third idea is the prohibited location. Section 240.24(D) keeps overcurrent devices away from easily ignitible material and names clothes closets as the example. Bathrooms are also off limits, but under a separate subsection, 240.24(E), and for a different reason. If the question asks which location the Code names as an example of ignitible material, the answer is the clothes closet.
Motor disconnects: location and what they must open
A motor circuit has two things that need a disconnect, the controller and the motor, and the Code gives each its own sentence. Under 430.102(A), each motor controller needs a disconnecting means in sight from the controller location. Under 430.102(B), there must be a disconnecting means in sight from the motor location and the driven machinery location. The purpose is that a person working on the machine can see that the switch is open. One switch can do both jobs. Section 430.102(B)(2) lets the controller disconnect serve as the motor disconnect when it is in sight from the motor and the driven machinery. A larger rating or a label does not replace that condition. There is an exception that lets the motor disconnect be omitted in limited cases, and a lockable controller disconnect alone is not enough to use it. Remember that the exam ignores exceptions and optional methods unless the question says to apply one, so answer with the in-sight rule. The usual trap is swapping the two rules. The controller disconnect is tied to the controller. The driven machinery matters only for the motor disconnect. Three short rules complete the picture. Where a circuit has two disconnects, 430.107 requires at least one of them to be readily accessible, and it does not say which. Section 430.103 requires the disconnect to open all ungrounded supply conductors together, with no pole able to operate independently. A controller is different: under 430.84 it need not open all conductors to the motor, which is one reason a separate disconnect is required.
Rating a motor disconnect, with a worked example
The general rule in 430.110(A) is that the disconnecting means must have an ampere rating of at least 115 percent of the motor full-load current. Worked example. A 30-horsepower, 460-volt, three-phase motor has a table full-load current of 40 amperes. What is the minimum ampere rating of the disconnecting means? Step 1. Identify the current: 40 amperes. Step 2. Multiply by 115 percent: 40 x 1.15 = 46 amperes. Step 3. Read what is asked. The question asks for the minimum rating, so the answer is 46 amperes. In the field you would install a 60-ampere switch, and 50 and 60 will both be among the choices, but they are equipment sizes and not the calculated minimum. The exam also runs the rule backward. A 100-ampere disconnect can serve a motor up to 100 / 1.15 = 86.96 amperes. If the choices include 83 and 88, check each: 83 x 1.15 = 95.45, which fits, and 88 x 1.15 = 101.2, which does not. Keep 115 percent apart from 125 percent. The 125 percent figure sizes conductors. For a torque motor, 430.110(B) uses 115 percent of the nameplate current, so 12 amperes gives 13.8 amperes, and the 15-ampere choice is the 125 percent mistake. Small stationary motors have their own switch rules. For motors of 2 horsepower or less and 300 volts or less, 430.109(C)(1) permits a general-use switch rated at least twice the motor full-load current: a 9.8-ampere motor needs 19.6 amperes. Under 430.109(C)(2), an ac-only general-use snap switch may be used when the motor current is no more than 80 percent of the switch rating, so a 20-ampere snap switch can serve up to 16 amperes. When a disconnect serves a combination load, the calculation needs locked-rotor current. For small motors not in the Code current tables, 430.110(C)(3) assumes six times the full-load current: 2.4 amperes becomes 14.4 amperes.
Air-conditioning and refrigeration disconnects
Article 440 follows the same pattern as motors, with compressor currents in place of table currents. Under 440.12(A)(1), the disconnect for a hermetic refrigerant motor-compressor is rated at least 115 percent of the rated-load current or the branch-circuit selection current, whichever is greater. With a rated-load current of 22 amperes and a branch-circuit selection current of 27 amperes, use 27: 27 x 1.15 = 31.05 amperes. Using 22 gives 25.3, which is the planted wrong answer. For location, 440.14 allows the disconnect on or within the equipment, but not on a panel designed to allow access to the equipment and not where it hides the nameplate. A wall within sight of and readily accessible from the unit is the ordinary choice. Where the disconnect is readily accessible to unqualified persons, 440.11 requires any enclosure door or hinged cover that exposes energized parts to be locked or to need a tool to open. A single-phase room air conditioner rated 250 volts or less may use its attachment plug and receptacle as the disconnect under 440.63 when the manual controls on the unit are readily accessible and within 6 ft of the floor. Do not confuse that 6 ft figure with the 6 ft 7 in. handle limit.
Service and building disconnects
For a one-family dwelling, 230.70(A)(1) puts the service disconnect in a readily accessible outdoor location, on the dwelling or within sight of it. The indoor location nearest the point of entrance belongs to other occupancies under 230.70(A)(2), and it is the trap in dwelling questions. Each service starts with one disconnect, and 230.71(B) permits two to six, so six is the maximum. Where there are two to six, 230.72(A) requires them to be grouped and each marked to show the load it serves, so that the whole building can be shut off from one place. A power-operated breaker may be the service disconnect under 230.76 only if it can still be opened by hand when its power supply fails. The minimum rating for a one-family dwelling service disconnect is 100 amperes under 230.79(C). The 60-ampere figure belongs to all other installations. A detached building supplied by a feeder follows Article 225. An outside building disconnect must be readily accessible, on the building or within sight of it, under 225.31(B). The breaker back at the supply panel does not count by itself. For rating, 225.39 requires at least the calculated load and at least a floor value. A workshop that is not a dwelling, with five branch circuits and a 48-ampere calculated load, falls under 225.39(D) at 60 amperes. Since 48 is below the floor, the answer is 60 amperes. The emergency disconnect for a one-family dwelling is marked on the outside front of its enclosure with a red background, white text and letters at least 1/2 in. high under 225.41(C). The exam reverses the colors in the wrong choices. Conductors in exam problems are copper unless the question states otherwise.