Electrical Equipment and Devices
Equipment and devices questions ask how the gear at the end of the circuit is protected, where it may be placed and how much room it needs. Most are one-line look-ups in Articles 110, 406, 440 and 450, with a few short calculations for compressors and transformers. Learn where each rule lives and what the standard wrong answers are.
Working space around equipment
Anyone servicing energized equipment needs room to stand, work and get away. Section 110.26 defines that room in three dimensions. Depth comes from Table 110.26(A)(1) and depends on what faces the equipment. In the 151 to 600 volts to ground row, which is the one the 480-volt panelboard questions use, Condition 1 (no live or grounded parts opposite) needs 3 feet, Condition 2 (a grounded surface opposite, such as a concrete wall) needs 3-1/2 feet, and Condition 3 (exposed live parts on both sides) needs 4 feet. Width is 30 inches or the width of the equipment, whichever is greater, with room for doors and hinged panels to open 90 degrees. Headroom is 6-1/2 feet, or the equipment height if taller. Do not confuse headroom with dedicated equipment space. The dedicated space is the footprint of the equipment from the floor to 6 feet above it or to the structural ceiling, whichever is lower, and it must stay clear of foreign piping and ducts. A suspended ceiling with removable panels is not a structural ceiling. Two more facts: equipment rated 1,200 amperes or more and over 6 feet wide needs an entrance at each end of the working space, and indoor working spaces around service equipment, switchboards, panelboards and motor control centers must be illuminated.
Device ratings, panelboards and single receptacles
Fuses and inverse-time breakers come in the standard ampere ratings listed in Section 240.6(A). The list includes 45, 50, 60, 70, 80, 90, 100 and 110, and it does not include 55 or 65. This matters in every sizing calculation, because a computed value has to be matched to a real size, and one of the answer choices is often a rating that does not exist. A panelboard must be protected by an overcurrent device rated no higher than the panelboard itself, either as a main in the panel or ahead of it in the feeder. The sum of the branch breakers is irrelevant; it normally exceeds the panel rating. A single receptacle on an individual branch circuit must be rated at least as high as the circuit, so a 20-ampere individual circuit needs a 20-ampere receptacle.
Air-conditioning and refrigeration equipment
Article 440 has its own numbers because a hermetic compressor draws a heavy starting current. For a single motor-compressor, the branch-circuit conductors need an ampacity of at least 125 percent of the rated-load current or the branch-circuit selection current, whichever is greater. The short-circuit and ground-fault device may be up to 175 percent of rated-load current. For a 20-ampere compressor that is 25 amperes of conductor ampacity and a 35-ampere device. Mixing up the two multipliers is the usual error. If the question tells you to apply the exception allowing the next higher standard rating, a 22-ampere compressor at 175 percent is 38.5 amperes and the device becomes 40. When the unit has a nameplate, read it instead of calculating. The marked minimum circuit ampacity sizes the conductors: 28.4 amperes needs 10 AWG copper at 75°C, since 12 AWG is good for only 25. The marked maximum overcurrent protective device is a ceiling, so a unit marked 40 gets a device of 40 amperes or less, and no extra multiplier is applied to it. A cord-and-plug room air conditioner may be rated up to 80 percent of the branch circuit when it is the only load, and only 50 percent when the circuit also serves lighting or other appliances.
Transformer primary protection
Table 450.5(B) sets the overcurrent protection for transformers. The case the journeyman questions use is primary-only protection with a primary current of 9 amperes or more: the device may be 125 percent of primary current, and where that does not land on a standard rating, Note 1 to the table permits the next higher standard rating. The primary current comes from general theory. Single-phase: volt-amperes divided by volts. Three-phase: volt-amperes divided by (1.732 x volts). Worked example: a 30 kVA, three-phase transformer with a 480-volt primary and primary-only protection. Step 1: 30,000 / (1.732 x 480) = 36.1 amperes. Step 2: 36.1 x 1.25 = 45.1 amperes. Step 3: 45.1 is above the standard 45-ampere rating, so go to the next higher standard rating. The answer is 50 amperes. The trap is choosing 45 because it looks close enough. The single-phase version drops the 1.732: a 25 kVA, 480-volt unit draws 25,000 / 480 = 52.1 amperes, 125 percent is 65.1, and the next standard size is 70. Forgetting the 1.732 on a three-phase unit, or adding it to a single-phase one, is the other way to miss these.
Receptacles
Article 406 rules are mostly about location. In a damp location, such as under a roofed open porch, the cover must be weatherproof when nothing is plugged in. In a wet location it must be weatherproof whether or not a plug is inserted, which is the in-use cover. In both, the receptacle itself must be a listed weather-resistant type. Receptacles are kept out of the tub or shower space and out of a zone 3 feet horizontally from its outside edge and 8 feet vertically above the rim or threshold. Dwelling-unit 15- and 20-ampere receptacles must be listed tamper-resistant. Replacement rules are tested often. Where a box has no equipment grounding conductor, a two-wire receptacle may be replaced with a GFCI receptacle marked No Equipment Ground. Grounding-type receptacles fed from the load side of that GFCI must carry two markings, GFCI Protected and No Equipment Ground, and no grounding conductor is run between them. GFCI and AFCI receptacles must be readily accessible, which rules out a spot behind a fixed appliance. Smaller facts: push-in terminals are limited to 14 AWG solid copper on circuits of 15 amperes or less, an isolated ground receptacle is identified by an orange triangle on its face, and replacement mounting screws must be machine screws with 32 threads per inch.
Boxes that support luminaires and fans
A ceiling box at a luminaire outlet must be able to carry at least 50 pounds. A heavier luminaire, such as a 62-pound chandelier, needs support independent of the box unless the box is listed for the weight. On a wall, a box that is not a luminaire box may still carry a luminaire of 6 pounds or less if at least two No. 6 or larger screws hold it. A fan is a moving load, so a box used as its only support must be listed for fan support, and once the fan weighs more than 35 pounds the box must also be marked with its maximum weight. The numbers 6, 35, 50 and 70 all appear as answer choices on each other's questions, so tie each to its rule. As everywhere on this exam, PSI's stated rules apply: ignore exceptions and optional methods unless the question raises them, and treat conductors as copper unless told otherwise.