Chapter 5 of 10

Wiring Methods and Materials

This area is where the open book pays off, because most of its questions are settled by a table: raceway fill in Chapter 9, box fill in Article 314, burial cover in Article 300. Your job is to know which table answers which question and to run the short arithmetic without slipping. This chapter walks through the rules the journeyman questions draw on most and the wrong answers built around each one.

Raceway fill: Chapter 9, Tables 1, 4 and 5

Conductors need room in a raceway so they can be pulled without damage and so heat can escape. Chapter 9, Table 1 sets the limit as a share of the raceway's cross-sectional area: 53 percent for one conductor, 31 percent for exactly two, and 40 percent for more than two. A nipple no longer than 24 inches between boxes or enclosures may be filled to 60 percent. Every sizing question follows the same three steps. Find the area of one conductor in Table 5, multiply by the number of conductors, then go to Table 4 for your raceway type and pick the smallest trade size whose 40 percent column is at least that total. Worked example: what is the minimum EMT for sixteen 12 AWG THHN conductors? Step 1: Table 5 gives 0.0133 square inch for one 12 AWG THHN. Step 2: 16 x 0.0133 = 0.2128 square inch. Step 3: more than two conductors, so use the 40 percent column of Table 4 for EMT. One-half inch allows 0.122 square inch, which is too small. Three-quarter inch allows 0.213 square inch, which just fits. The answer is three-quarter inch. When the question runs the other way and asks how many same-size conductors fit, divide the allowed area by the conductor area. Note 7 to the Chapter 9 tables lets you go up to the next whole number only when the decimal is 0.8 or larger. For 14 AWG THHN in trade size 1/2 rigid metal conduit, 0.125 / 0.0097 = 12.89, so 13 conductors are permitted.

Fill percentages
One conductor may fill 53 percent of the raceway, two may fill 31 percent, and more than two may fill 40 percent.
2026 NEC Chapter 9, Table 1
Short nipple
A nipple 24 inches or shorter between enclosures may be filled to 60 percent.
2026 NEC Chapter 9, Table 1, Note 4
Rounding the conductor count
For conductors all the same size, round up only when the decimal is 0.8 or larger.
2026 NEC Chapter 9, Table 1 and Notes to Tables, Note 7

Box fill: count allowances, then multiply

A box that is too small crowds splices and devices and traps heat. Section 314.16 handles this by giving each conductor a volume allowance by its size: 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG and 2.50 for 10 AWG, from Table 314.16(B)(4). You count allowances and multiply. The count is where points are lost. Each insulated conductor counts once. All internal cable clamps together count once. The equipment grounding conductors in an ordinary device box count together as one. Each device yoke or strap counts as two, based on the largest conductor connected to the device. So a box with three 14-2 NM cables with grounds, internal clamps and one switch has 6 + 1 + 1 + 2 = 10 allowances, and 10 x 2.00 = 20.0 cubic inches. The wrong answers come from dropping the clamp, dropping the grounds, counting the yoke once, or using the 12 AWG allowance. With mixed sizes, each conductor takes the allowance for its own size: four 14 AWG and two 12 AWG need (4 x 2.00) + (2 x 2.25) = 12.5 cubic inches. When the question asks how many conductors a box holds, divide and round down. A 21.0 cubic inch box gives 21.0 / 2.25 = 9.33, so nine 12 AWG conductors.

Volume allowance per conductor
Each conductor takes the volume for its own size: 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG.
2026 NEC Table 314.16(B)(4)
Device yoke
A yoke or strap counts as two allowances based on the largest conductor connected to the device.
2026 NEC §314.16(B)(4)

Pull and junction boxes

Large conductors are stiff, so the box must be long enough to pull and train them. For a straight pull, Section 314.28(A)(1) requires a box length of at least eight times the trade size of the largest raceway. For an angle pull, Section 314.28(A)(2) measures from the wall where the raceways enter to the opposite wall: six times the largest raceway, plus the sizes of the other raceways in the same row on that wall. A 3 inch and a 2 inch raceway on one wall need (6 x 3) + 2 = 20 inches. The same section sets the spacing between the two raceway entries that enclose the same conductor at six times the larger raceway, so a 2-1/2 inch entry and a 2 inch exit must be at least 15 inches apart.

Straight pull
Box length is at least eight times the trade size of the largest raceway.
2026 NEC §314.28(A)(1)
Angle pull
Wall-to-wall distance is six times the largest raceway plus the other raceways in the same row on that wall.
2026 NEC §314.28(A)(2)

Underground wiring

Burial depth is a pure look-up in Table 300.7(A): find the location row, then the wiring method column. In locations not otherwise specified, direct-buried cable needs 24 inches of cover, a nonmetallic raceway listed for direct burial needs 18 inches, and rigid or intermediate metal conduit needs only 6 inches because the metal wall protects itself. A residential branch circuit of 120 volts or less and 20 amperes or less with GFCI protection may be at 12 inches. Take away the GFCI and the cable goes back to 24. Under streets, roads and alleys every column reads 24 inches. The driveway of a one- or two-family dwelling used only for dwelling purposes has its own row, where direct-buried cable needs 18 inches. Four related rules sit nearby. Direct-buried conductors coming out of the ground must be protected up to 8 feet above finished grade. Underground service conductors that are not in concrete and are 18 inches or more deep need a warning ribbon at least 12 inches above them. A raceway that could carry moisture to live parts must be sealed or plugged. And because the inside of an underground raceway is a wet location, its conductors need a wet-location type such as THWN or XHHW.

Minimum cover
Cover depends on the location row and wiring method column, with 24, 18, 6 and 12 inches as the values tested most.
2026 NEC Table 300.7(A)
Emerging from grade
Direct-buried conductors are protected by an enclosure or raceway up to 8 feet above finished grade.
2026 NEC §300.7(D)(1)
Warning ribbon
Service conductors not in concrete and buried 18 inches or more get a ribbon at least 12 inches above them.
2026 NEC §300.7(D)(3)
Wet-location conductors
Conductors in underground raceways must be listed for wet locations.
2026 NEC §310.10(C)

Protecting and supporting the run

These rules keep nails, screws and sharp edges away from the wiring. A cable through a bored hole in a wood stud needs the edge of the hole at least 1-1/4 inches from the nearest edge of the stud. If it is closer, or if the cable lies in a notch, a steel plate at least 1/16 inch thick must cover it. NM cable through holes in metal studs needs listed bushings or grommets covering all metal edges, in place before the cable is pulled. Under metal-corrugated roof decking, keep cables, raceways and boxes at least 1-1/2 inches below the lowest surface of the deck so roofing screws miss them. Where insulated conductors of 4 AWG or larger enter a box or enclosure from a raceway, they need a smooth insulating surface such as an insulating bushing. For the conduit itself: no more than 360 degrees of bend between pull points, a minimum radius of 5-3/4 inches for trade size 1 conduit bent with a one-shot bender, and rigid metal conduit fastened within 3 feet of each box or termination and supported at intervals of no more than 10 feet.

Bored holes in wood
Where the 1-1/4 inch setback cannot be kept, a steel plate or bushing at least 1/16 inch thick protects the cable.
2026 NEC §300.6(A)(1)
Roof decking clearance
Wiring under metal-corrugated roof decking stays at least 1-1/2 inches below the deck.
2026 NEC §300.6(E)
Bends between pull points
A conduit or tubing run may have no more than 360 degrees of bend between pull points.
2026 NEC §300.24
Fastening RMC
Rigid metal conduit is securely fastened within 3 feet of each box or termination.
2026 NEC §344.30(A)

Conductors, cables and boxes: fast look-ups

Several single-fact questions round out this area. Conductors may be paralleled in sizes 1/0 AWG and larger. Type NM cable is for normally dry locations only. Metal raceways such as rigid metal conduit and EMT are recognized equipment grounding conductors, but flexible metal conduit qualifies only when the ground-return length is 6 feet or less, the circuit is protected at 20 amperes or less, and it ends in listed fittings. A metal box must be connected to the equipment grounding conductor. A box in a wet location must be listed for wet locations and keep water from entering or collecting. A paddle fan may hang from a box alone only when the box is listed for fan support, and only up to 70 pounds. Two ampacity facts also appear. Table 310.15(C)(1) reduces ampacity when more than three current-carrying conductors share a raceway: 80 percent for 4 through 6, 70 percent for 7 through 9, 50 percent for 10 through 20. And a conductor's ampacity can never be used above the temperature rating of its terminals, so 2 AWG THHN copper on 60°C terminals is good for 95 amperes, not its 130 ampere 90°C value. One reminder for the whole exam: PSI's stated rules are that you ignore exceptions and optional methods unless the question itself raises them, and that conductors are copper unless the question says otherwise.

Parallel conductors
Paralleling is generally allowed only for 1/0 AWG and larger.
2026 NEC §310.10(G)
FMC as a grounding path
Flexible metal conduit serves as an equipment grounding conductor only within tight length, overcurrent and fitting limits.
2026 NEC §250.118(A)(5)
Fan support
A box that is the sole support of a paddle fan must be listed for it and is limited to 70 pounds.
2026 NEC §314.27(B)
Adjustment factors
More than three current-carrying conductors in a raceway reduces each conductor's ampacity by a table percentage.
2026 NEC Table 310.15(C)(1)