Water Heaters

Water heater questions are safety questions: the relief valve and its discharge pipe, pans, access, thermal expansion, and for gas heaters the location, combustion air and vent connector. The practical exam also asks candidates to spot water heater violations.

Relief valve and discharge pipe

Every storage heater has a combination temperature and pressure relief valve. Its discharge pipe is the most tested detail in the chapter.

Relief settings
Not over 150 psi or the tank working pressure; not over 210°F; capacity at least the heater input.
IPC §§504.4, 504.5
Discharge pipe
Full size, one device per pipe, no valves or tees, not trapped, gravity flow, air gap in the same room, ends within 6 inches of the floor or receptor, no threaded end.
IPC §504.6
Pan
No. 24 gage, 1-1/2 inches deep, 3/4-inch drain ending 6 to 24 inches above grade outdoors or at an indirect waste receptor.
IPC §504.7

Location, expansion and gas

Attic heaters need a passageway no longer than 20 feet and a 30-by-30-inch service space. A closed system needs thermal expansion control. Ignition sources in garages are raised 18 inches unless the heater is flammable vapour ignition resistant. Gas heaters stay out of bedrooms and bathrooms unless direct-vent or enclosed with outdoor combustion air.

Thermal expansion
Device required where a check valve, backflow preventer or regulator closes the system.
IPC §607.3
Combustion air
50 cubic feet per 1,000 Btu/h indoors; outdoor openings 1 sq in per 4,000 Btu/h (2,000 for horizontal ducts).
IFGC §§304.5, 304.6
Vent connector
Rises 1/4 inch per foot.
IFGC §503.10.7