Chapter 6 of 7

LP Gas

LP-gas questions draw on the National Fuel Gas Code (NFPA 54) and on the properties of propane. In Texas, LP-gas work is also licensed by the Railroad Commission under 16 TAC Chapter 9.

Properties of propane

Propane vapour is about one and a half times as heavy as air, so leaks settle in low places. It carries about 2,500 Btu per cubic foot, two and a half times natural gas, and is delivered to appliances at about 11 inches of water column.

Specific gravity
About 1.5 (air is 1.0).
NFPA 54; NFPA 58
Heating value
About 2,500 Btu per cubic foot of vapour; about 91,500 Btu per gallon of liquid.
NFPA 58 annex
Appliance pressure
About 11 inches of water column, after two-stage regulation.
NFPA 54 sizing tables
Odorant
Ethyl mercaptan.
NFPA 58

Piping and testing

Piping is tested with air or an inert gas, never oxygen, and leaks are found with solution or a gauge, never a flame.

Test pressure
1-1/2 times working pressure, not less than 3 psi.
NFPA 54 Ch. 8
Prohibited locations
Circulating air ducts, clothes chutes, chimneys, elevator shafts.
NFPA 54 Ch. 7
Concealed fittings
No unions, bushings or compression couplings.
NFPA 54 Ch. 7
Plastic pipe
Outdoors and underground only.
NFPA 54 Ch. 7
Cover
12 inches minimum underground.
NFPA 54 Ch. 7

Appliances

Each appliance has a shutoff valve within 6 feet and, usually, a sediment trap. Unvented room heaters are limited by room and by input.

Unvented heaters
Bathroom 6,000 Btu/h; bedroom 10,000 Btu/h; oxygen depletion shutoff required.
NFPA 54 Ch. 10
Connectors
Listed, 6 feet maximum, not concealed.
NFPA 54 Ch. 9
Clothes dryers
Exhaust outdoors, never into a vent or chimney; no screws into the airway.
NFPA 54 Ch. 10
Licensing
Railroad Commission of Texas, LP-Gas Safety Rules.
16 TAC Ch. 9