Chapter 5 of 7

Sanitary Drainage

Chapter 30 of the International Residential Code covers drain, waste and building sewer piping. Section numbers are from the 2018 edition.

Slope and load

Small drains need more slope than large ones. The load on a drain is counted in drainage fixture units and compared with the capacity of the pipe.

Slope
1/4 inch per foot for 2-1/2 inches and smaller; 1/8 inch per foot for 3 inches and larger.
IRC §P3005.3
Fixture units
A lavatory is 1; a tub, shower or kitchen sink 2; a 1.6-gallon water closet 3; a full bath group 5.
IRC Table P3004.1
Branch capacity
1-1/2 inch: 3 dfu. 2 inch: 6 dfu. 3 inch: 20 dfu.
IRC Table P3005.4.1
Size
Drain size is not reduced in the direction of flow.
IRC §P3005.1.6

Fittings, joints and cleanouts

The right fitting depends on the change of direction. A sanitary tee is for horizontal to vertical only. Cleanouts keep the system serviceable.

Fittings
Sanitary tees not used horizontal to horizontal.
IRC Table P3005.1
Prohibited joints
Cement or mortar joints, saddle fittings, solvent cement between different plastics.
IRC §P3003.2
Cleanout spacing
Not more than 100 feet apart; at changes of direction over 45 degrees; near the building drain and sewer junction.
IRC §P3005.2

Below the sewer

Fixtures below the sewer are pumped. Fixtures below the next upstream manhole cover are protected by a backwater valve.

Sump pit
At least 18 inches in diameter and 24 inches deep, with a gastight cover.
IRC §P3007.3.2
Ejector discharge
Check valve and full-open valve.
IRC §P3007.1
Backwater valve
Required for fixtures below the next upstream manhole cover; accessible.
IRC §P3008