Chapter 7 of 7
Fuel Gas Piping
Chapter 24 of the International Residential Code reprints the residential parts of the International Fuel Gas Code. Each section carries both numbers.
Installing gas piping
Gas piping is kept out of ducts, chimneys and shafts. Plastic pipe is used only outdoors and underground, with a tracer wire. Corrugated stainless steel tubing is bonded.
Prohibited locations
Ducts, clothes chutes, chimneys, dumbwaiters, elevator shafts.
IRC §G2415.3Concealed fittings
No unions or bushings in concealed locations.
IRC §G2415.5Burial
At least 12 inches deep.
IRC §G2415.12Plastic pipe
Outdoors and underground only; yellow insulated copper tracer wire.
IRC §§G2415.17.1, G2415.17.3CSST bonding
Bonding jumper not smaller than 6 AWG copper.
IRC §G2411.2Testing
New piping is tested with air, nitrogen, carbon dioxide or an inert gas. Oxygen is never used.
Test pressure
1-1/2 times working pressure and not less than 3 psig.
IRC §G2417.4.1Duration
Not less than 10 minutes.
IRC §G2417.4.2Connecting appliances
Each appliance has its own shutoff valve, a sediment trap where required, and a connector of limited length.
Shutoff valve
Same room, within 6 feet of the appliance.
IRC §G2420.5.1Connector
Not longer than 6 feet, not concealed.
IRC §G2422.1.2.1Sediment trap
Downstream of the shutoff, close to the appliance inlet.
IRC §G2419.4