Texas Tradesman Plumber-Limited Exam — All Questions

20 questions

Fuel Gas Piping

New gas piping in a house is pressure tested. Under IRC §G2417.4.1, the test pressure must be at least 1-1/2 times the working pressure and not less than:

  • a.1/4 psig
  • b.3 psig✓
  • c.60 psig
  • d.150 psig

The test pressure is not less than 1-1/2 times the proposed maximum working pressure and never less than 3 psig.IRC §G2417.4.1 (IFGC §406.4.1)

Fuel Gas Piping

Under IRC §G2417.4.2, the pressure test on residential gas piping must be held for at least:

  • a.10 seconds
  • b.10 minutes✓
  • c.48 hours
  • d.12 hours

The test duration is not less than 10 minutes, with no drop in pressure shown on the gauge.IRC §G2417.4.2 (IFGC §406.4.2)

Fuel Gas Piping

Which may NOT be used as the test medium for gas piping under IRC §G2417.2?

  • a.Oxygen✓
  • b.Nitrogen
  • c.Air
  • d.Carbon dioxide

The test medium is air, nitrogen, carbon dioxide or an inert gas. Oxygen is never used, because it reacts violently with oil and hydrocarbons.IRC §G2417.2 (IFGC §406.2)

Fuel Gas Piping

Under IRC §G2415.12, underground gas piping must be buried at least:

  • a.72 inches deep
  • b.48 inches deep
  • c.12 inches deep✓
  • d.1 inch deep

Underground piping systems are installed at a minimum depth of 12 inches below grade; individual lines to outdoor lights and grills may be at 8 inches where approved.IRC §G2415.12 (IFGC §404.12)

Fuel Gas Piping

Under IRC §G2415.17, plastic (polyethylene) gas pipe may be installed:

  • a.Above ground on exterior walls
  • b.In return air plenums and ducts
  • c.Outdoors and underground only✓
  • d.Indoors in walls and attics only

Plastic pipe is installed outdoors underground only, apart from listed anodeless risers and similar exceptions.IRC §G2415.17.1 (IFGC §404.17.1)

Fuel Gas Piping

Under IRC §G2415.17.3, plastic gas pipe buried in a yard must have installed next to it:

  • a.A galvanized steel support cable
  • b.A yellow insulated copper tracer wire✓
  • c.A perforated plastic drain tile
  • d.A red plastic warning ribbon and nothing more

A yellow insulated copper tracer wire, or other approved conductor, at least 18 AWG is installed adjacent to underground non-metallic piping and brought above ground at each end, so the pipe can be located.IRC §G2415.17.3 (IFGC §404.17.3)

Fuel Gas Piping

Under IRC §G2415.3, gas piping may NOT be installed in or through:

  • a.An interior partition wall, through holes bored in the center of studs
  • b.An accessible attic above the ceiling insulation
  • c.A ventilated crawl space under the floor joists
  • d.A circulating air duct, clothes chute, chimney or dumbwaiter✓

Piping is not installed in or through a ducted supply, return or exhaust, a clothes chute, a chimney or gas vent, a dumbwaiter or an elevator shaft.IRC §G2415.3 (IFGC §404.3)

Fuel Gas Piping

Which fitting may NOT be used in concealed gas piping under IRC §G2415.5?

  • a.A union✓
  • b.A threaded tee
  • c.A threaded elbow
  • d.A threaded coupling

Fittings in concealed locations are limited to threaded elbows, tees and couplings, brazed fittings and listed fittings. Unions, bushings and compression couplings are not concealed.IRC §G2415.5 (IFGC §404.5)

Fuel Gas Piping

Under IRC §G2420.5.1, the shutoff valve for a gas range must be in the same room as the appliance and within:

  • a.100 feet of the appliance
  • b.25 feet of the gas meter
  • c.60 feet of the appliance
  • d.6 feet of the appliance✓

Each appliance has a shutoff valve in the same room, within 6 feet, upstream of the union or connector it serves, with access.IRC §G2420.5.1 (IFGC §409.5.1)

Fuel Gas Piping

Under IRC §G2422.1.2.1, a flexible gas appliance connector may be no longer than:

  • a.25 feet
  • b.6 feet✓
  • c.50 feet
  • d.1 foot

Connectors are not more than 6 feet in overall length, are not concealed and do not pass through walls, floors, partitions or appliance housings.IRC §G2422.1.2.1 (IFGC §411.1.3.1)

Fuel Gas Piping

Under IRC §G2419.4, a sediment trap must be installed:

  • a.Upstream of the gas meter, as close to the street main as is practical
  • b.At the vent connector, to collect condensate from the flue gases
  • c.Downstream of the appliance shutoff valve, as close to the appliance inlet as practical✓
  • d.At the highest point of the piping system, to release any air trapped in the system after testing

Where a sediment trap is not part of the appliance, one is installed downstream of the shutoff valve as close to the inlet as practical. Ranges, clothes dryers, decorative appliances and outdoor grills need not have one.IRC §G2419.4 (IFGC §408.4)

Fuel Gas Piping

Corrugated stainless steel tubing (CSST) gas piping in a house that is not listed with an arc-resistant jacket must, under IRC §G2411.2, be:

  • a.Bonded to the electrical grounding electrode system✓
  • b.Buried in the attic insulation for protection
  • c.Isolated from every metal part of the building
  • d.Painted yellow along its full length after installation

CSST that is not listed with an arc-resistant jacket or coating is bonded to the electrical service grounding electrode system (or the lightning protection grounding electrode system, where provided) with a bonding jumper not smaller than 6 AWG copper, no longer than 75 feet.IRC §G2411.2 (IFGC §310.2)

Fuel Gas Piping

Under IRC §G2411.2, the bonding jumper for CSST gas piping must be at least:

  • a.22 AWG copper
  • b.6 AWG copper✓
  • c.26 AWG copper
  • d.18 AWG copper

The bonding jumper is not smaller than 6 AWG copper wire or equivalent, and is not longer than 75 feet.IRC §G2411.2.1 (IFGC §310.2.1)

Fuel Gas Piping

Under IRC §G2412.5, exposed gas piping that is not black steel pipe must be identified by a yellow label marked "Gas" at intervals of not more than:

  • a.100 feet
  • b.6 inches
  • c.5 feet✓
  • d.50 feet

Exposed piping other than steel pipe is identified by a yellow label marked "Gas" in black letters, spaced at intervals not exceeding 5 feet.IRC §G2412.5 (IFGC §401.5)

Fuel Gas Piping

Gas piping passes through a wall stud less than 1-1/2 inches from the face of the stud. Under IRC §G2415.7, it must be protected by:

  • a.Plastic conduit
  • b.Fiberglass tape
  • c.Foam pipe insulation
  • d.Steel shield plates✓

Where piping other than black or galvanized steel is less than 1-1/2 inches from the face of the framing, shield plates of steel at least 0.0575 inch thick cover the area, extending 4 inches beyond the member.IRC §G2415.7 (IFGC §404.7)

Fuel Gas Piping

Under IRC Table G2424.1, 1/2-inch steel gas pipe run horizontally must be supported at intervals of not more than:

  • a.30 feet
  • b.20 feet
  • c.1 foot
  • d.6 feet✓

Steel pipe is supported every 6 feet for 1/2 inch, 8 feet for 3/4 and 1 inch, and 10 feet for 1-1/4 inch and larger horizontal runs.IRC Table G2424.1 (IFGC Table 415.1)

Fuel Gas Piping

A house has a furnace of 80,000 Btu/h, a water heater of 40,000 Btu/h and a range of 60,000 Btu/h on natural gas with a heating value of 1,000 Btu per cubic foot. The total demand used to size the main is:

  • a.1,800 cubic feet per hour
  • b.18 cubic feet per hour
  • c.180 cubic feet per hour✓
  • d.80 cubic feet per hour

80,000 + 40,000 + 60,000 = 180,000 Btu/h; divided by 1,000 Btu per cubic foot this is 180 cubic feet per hour.IRC §G2413 (IFGC §402)

Fuel Gas Piping

Under IRC §G2413, a section of gas piping is sized from the tables using the load it carries and:

  • a.The height of the house from grade to the roof ridge
  • b.The age of the house and the type of gas meter
  • c.The number of elbows and tees between the meter and the first outlet
  • d.The length of piping from the meter to the most remote outlet✓

In the longest-length method, every section is sized from the column for the distance from the point of delivery to the most remote outlet, using the load that section carries.IRC §G2413.4 (IFGC §402.4)

Fuel Gas Piping

Under IRC §G2406.2, a single listed unvented room heater with an oxygen depletion safety shutoff may be installed in a bathroom where its input does not exceed:

  • a.6,000 Btu/h✓
  • b.600 Btu/h
  • c.80,000 Btu/h
  • d.40,000 Btu/h

One listed wall-mounted unvented room heater with an oxygen depletion safety shutoff is permitted in a bathroom at up to 6,000 Btu/h and in a bedroom at up to 10,000 Btu/h, where combustion air is adequate.IRC §G2406.2 (IFGC §303.3)

Fuel Gas Piping

Under IRC §G2439, the exhaust duct of a gas clothes dryer in a house must:

  • a.Connect to the water heater vent through a listed draft hood
  • b.Terminate in the attic and be joined with long sheet-metal screws
  • c.Terminate in the crawl space at least 3 feet from any vent
  • d.Terminate outdoors and have no screws protruding into the airway✓

Dryer exhaust ducts convey moisture and combustion products outdoors, are of smooth metal, and are joined without fasteners that protrude more than 1/8 inch into the duct, where lint would collect.IRC §G2439 (IFGC §614)