Texas Tradesman Plumber-Limited Exam — All Questions

30 questions

Vents and Traps

Under IRC §P3201.2, a fixture trap must have a liquid seal of at least 2 inches and not more than:

  • a.4 inches✓
  • b.24 inches
  • c.8 inches
  • d.12 inches

Traps have a liquid seal of not less than 2 inches and not more than 4 inches. A deeper seal slows the flow and collects solids.IRC §P3201.2

Vents and Traps

Which trap is prohibited under IRC §P3201.5?

  • a.A trap integral with a water closet
  • b.A tubular trap with a slip joint
  • c.A P trap
  • d.An S trap✓

Prohibited traps include bell traps, drum traps, S traps, crown-vented traps and traps with moving parts or interior partitions. S traps siphon their own seal.IRC §P3201.5

Vents and Traps

Under IRC §P3201.6, the vertical distance from a fixture outlet to its trap weir may not exceed:

  • a.96 inches
  • b.60 inches
  • c.4 inches
  • d.24 inches✓

The vertical distance from the fixture outlet to the trap weir is not more than 24 inches, and the horizontal distance not more than 30 inches. A longer drop gives the waste enough velocity to siphon the trap.IRC §P3201.6

Vents and Traps

Under IRC §P3201.6, one trap may serve a kitchen sink with how many compartments at most?

  • a.Eight
  • b.Six
  • c.Three✓
  • d.Ten

One trap may serve a single fixture with not more than three compartments, or up to three lavatories or sinks, where the outlets are within 30 inches of the trap.IRC §P3201.6

Vents and Traps

Under IRC §P3201.4, a building trap (a running trap on the building drain) is:

  • a.Required with a basement
  • b.Prohibited✓
  • c.Optional with a cleanout
  • d.Required on every house

Building traps are not installed, except in special cases where sewer gases are extremely corrosive or noxious, as directed by the building official.IRC §P3201.4

Vents and Traps

Under IRC Table P3201.7, the minimum trap size for a lavatory is:

  • a.1-1/4 inches✓
  • b.1/2 inch
  • c.3-1/2 inches
  • d.2-1/2 inches

A lavatory uses a 1-1/4 inch trap; bathtubs, showers, kitchen sinks and laundry tubs use 1-1/2 inches.IRC Table P3201.7

Vents and Traps

Under IRC Table P3201.7, the minimum trap size for a clothes washer standpipe is:

  • a.1 inch
  • b.2 inches✓
  • c.1/2 inch
  • d.3/4 inch

A clothes washer standpipe has a 2-inch trap, because the washer pump discharges at a high rate.IRC Table P3201.7

Vents and Traps

A floor drain in a house is rarely used and its trap could dry out. Under IRC §P3201.2.1, the trap seal must be protected by:

  • a.A trap seal primer valve or other approved trap seal protection✓
  • b.A second trap installed directly below the first one
  • c.A coat of oil-based paint on the inside of the trap
  • d.A threaded brass plug that is left in place at all times except cleaning

Traps subject to evaporation are protected by a potable water-supplied trap seal primer valve, a waste-supplied primer, or an approved barrier-type trap seal protection device.IRC §P3201.2.1

Vents and Traps

Under IRC Table P3105.1, the maximum distance from the weir of a 1-1/2 inch trap to its vent is:

  • a.1 foot
  • b.20 feet
  • c.6 feet✓
  • d.40 feet

At 1/4 inch per foot the limits are 5 feet for a 1-1/4 inch trap, 6 feet for 1-1/2 inch, 8 feet for 2 inch and 12 feet for 3 inch.IRC Table P3105.1

Vents and Traps

Under IRC Table P3105.1, the maximum distance from the weir of a 2-inch trap to its vent is:

  • a.8 feet✓
  • b.2 feet
  • c.50 feet
  • d.25 feet

A 2-inch trap arm sloped at 1/4 inch per foot may run 8 feet to its vent.IRC Table P3105.1

Vents and Traps

Under IRC §P3105.2, the total fall in a fixture drain from the trap weir to the vent fitting may not exceed:

  • a.Four pipe diameters
  • b.Six pipe diameters
  • c.Ten pipe diameters
  • d.One pipe diameter✓

If the trap arm falls more than one pipe diameter, the top of the pipe at the vent drops below the trap weir and the arm can run full and siphon the trap.IRC §P3105.2

Vents and Traps

Under IRC §P3105.3, a vent may not connect to the trap arm closer to the trap weir than:

  • a.Twelve pipe diameters
  • b.Twenty pipe diameters
  • c.Eight pipe diameters
  • d.Two pipe diameters✓

A vent within two pipe diameters of the trap weir is a crown vent; it clogs with waste and is prohibited.IRC §P3105.3

Vents and Traps

Under IRC §P3103.1.1, an open vent pipe through the roof of a house must extend above the roof at least:

  • a.6 inches✓
  • b.1/2 inch
  • c.36 inches
  • d.72 inches

Vent terminals extend at least 6 inches above the roof or above the anticipated snow accumulation; where the roof is used as a deck or similar space, they extend 7 feet.IRC §P3103.1.1

Vents and Traps

Under IRC §P3103.5, a vent terminal may not be located directly beneath a door, openable window or air intake, and may not be within what horizontal distance of one unless it is raised well above the opening?

  • a.50 feet
  • b.100 feet
  • c.1 foot
  • d.10 feet✓

A vent terminal is kept 4 feet below, or 10 feet horizontally from, an opening into the building, or is carried up above the top of the opening.IRC §P3103.5

Vents and Traps

Under IRC §P3102.1, every house plumbing drainage system must have:

  • a.At least one vent pipe that extends to the outdoors✓
  • b.At least two vent stacks of 4 inches each
  • c.At least one air admittance valve in the attic space
  • d.At least one building trap at the foundation

The drainage system has at least one vent that runs undiminished to the open air, connected to a drainage stack or the building drain. Air admittance valves cannot replace it.IRC §P3102.1

Vents and Traps

Under IRC §P3104.4, a dry vent rising from a fixture drain must rise vertically before it offsets horizontally to at least:

  • a.6 inches above the flood level rim of the fixture✓
  • b.The underside of the floor joists below the fixture
  • c.6 inches below the trap weir of the fixture
  • d.36 inches above the finished ceiling of the room

Vents rise vertically to at least 6 inches above the flood level rim of the highest fixture served before offsetting, so that waste cannot flow into a horizontal vent if the drain stops up.IRC §P3104.4

Vents and Traps

Under IRC §P3104.2, vent pipes must be graded so that:

  • a.Moisture collects in a low loop below each fixture
  • b.Moisture drains back to the soil or waste pipe by gravity✓
  • c.They rise 1 inch per foot toward the fixture trap
  • d.They are perfectly level from the fixture to the stack

Vent and branch vent pipes are graded and connected so as to drain back to the drainage pipe by gravity; sags hold condensate and block the vent.IRC §P3104.2

Vents and Traps

Under IRC §P3104.3, where a vent connects to a horizontal drain, the connection is made:

  • a.Through a saddle on the side of the pipe
  • b.Above the centerline of the horizontal drain pipe✓
  • c.Downstream of the building drain cleanout
  • d.At the bottom of the horizontal drain pipe, through a wye

Every dry vent connecting to a horizontal drain connects above the centerline of the drain, so waste does not flow into and foul the vent.IRC §P3104.3

Vents and Traps

Under IRC §P3113.1, the diameter of a vent must be at least 1-1/4 inches and not less than:

  • a.Three times the diameter of the drain it serves
  • b.One-half the diameter of the drain it serves✓
  • c.Twice the diameter of the drain it serves
  • d.One-tenth the diameter of the drain it serves

Individual vents, branch vents, circuit vents, vent stacks and stack vents are at least one-half the required diameter of the drain served, and no vent pipe is smaller than 1-1/4 inches.IRC §P3113.1

Vents and Traps

Under IRC §P3113.1, a vent with a developed length of more than 40 feet must be:

  • a.Replaced with two air admittance valves
  • b.Fitted with a cleanout at the midpoint of the run
  • c.Reduced by one nominal pipe size for its entire developed length
  • d.Increased by one nominal pipe size for its entire length✓

Vents longer than 40 feet in developed length are increased one nominal pipe size for the entire developed length.IRC §P3113.1

Vents and Traps

Two lavatories are set back to back and connect at the same level to one vertical drain. Under IRC §P3107.1, the single vent serving both traps is called:

  • a.A stack vent
  • b.A common vent✓
  • c.A circuit vent
  • d.A relief vent

An individual vent may vent two traps or trapped fixtures as a common vent, where the fixtures are on the same floor level.IRC §P3107.1

Vents and Traps

Under IRC §P3108.1, a horizontal wet vent may serve any combination of fixtures within:

  • a.Any group of fixtures located on two adjoining floors
  • b.One kitchen and one laundry on the same floor level
  • c.Two bathroom groups located on the same floor level✓
  • d.Six bathroom groups located on any floor levels

Any combination of fixtures within two bathroom groups on the same floor level may be vented by a horizontal wet vent; kitchen sinks and clothes washers are not bathroom group fixtures.IRC §P3108.1

Vents and Traps

Under IRC Table P3108.3, a 2-inch wet vent may carry a drainage load of not more than:

  • a.24 drainage fixture units
  • b.14 drainage fixture units
  • c.4 drainage fixture units✓
  • d.40 drainage fixture units

The wet vent sizes are 1-1/2 inch for 1 dfu, 2 inch for 4 dfu, 2-1/2 inch for 6 dfu and 3 inch for 12 dfu.IRC Table P3108.3

Vents and Traps

A kitchen island sink cannot have a conventional vent rising in a wall. Under IRC §P3112, the island fixture vent must rise:

  • a.No higher than the cabinet floor before turning down
  • b.Above the roof through the center of the countertop and ceiling
  • c.Above the drainage outlet of the fixture before turning down✓
  • d.No higher than the trap weir before turning down

An island fixture vent rises vertically to above the drainage outlet of the fixture before offsetting horizontally or vertically downward, and has cleanouts for rodding.IRC §P3112.2

Vents and Traps

Under IRC §P3114.4, an individual air admittance valve must be located above the horizontal branch drain or fixture drain it vents by at least:

  • a.4 inches✓
  • b.48 inches
  • c.1/4 inch
  • d.96 inches

Individual and branch-type air admittance valves are at least 4 inches above the horizontal branch drain or fixture drain being vented; stack-type valves are at least 6 inches above the flood level rim of the highest fixture.IRC §P3114.4

Vents and Traps

An air admittance valve is installed in an attic. Under IRC §P3114.4, it must be above the insulation by at least:

  • a.1/2 inch
  • b.6 inches✓
  • c.48 inches
  • d.72 inches

Air admittance valves installed in attics are at least 6 inches above insulation materials, so that the insulation does not block the air inlet.IRC §P3114.4

Vents and Traps

Under IRC §P3114.5, an air admittance valve must be installed in a location that:

  • a.Is sealed airtight inside the wall cavity
  • b.Is below the flood level rim of the fixture served
  • c.Is accessible and allows air to enter the valve✓
  • d.Is inside a supply or return air plenum

Access is provided to all air admittance valves, and the valve is in a ventilated space that allows air to enter it. Valves are not installed in supply or return air plenums.IRC §§P3114.5, P3114.8

Vents and Traps

Under IRC §P3114.3, air admittance valves are installed:

  • a.After the DWV testing required at rough-in is finished✓
  • b.Only after the house has been occupied for 30 days
  • c.Before the slab is poured, below the finished floor
  • d.Before the rough-in water test, to seal the vent openings

The valves are installed after the DWV testing required by the code has been performed, because the test pressure can damage or unseat the valve.IRC §P3114.3

Vents and Traps

Under IRC §P3111, a combination waste and vent system in a house may serve:

  • a.Food waste disposers and bathtubs
  • b.Roof drains and area drains
  • c.Floor drains, sinks and lavatories✓
  • d.Water closets and clothes washers

A combination waste and vent system is limited to floor drains, sinks and lavatories, and does not receive the discharge of a food waste disposer.IRC §P3111.1

Vents and Traps

Under IRC §P3103.2, where the winter design temperature is below 0°F, a vent extension through the roof must be at least:

  • a.8 inches in diameter, to carry snow melt
  • b.3 inches in diameter, to resist frost closure✓
  • c.12 inches in diameter, to allow inspection
  • d.1 inch in diameter, to reduce heat loss

Where the 97.5-percent winter design temperature is less than 0°F, vent extensions through a roof or wall are at least 3 inches in diameter, with any increase made inside the building. Most of Texas is warmer than this threshold.IRC §P3103.2