Texas Tradesman Plumber-Limited Exam — All Questions

30 questions

General Requirements and Fixtures

A plastic drain pipe passes through a wall stud with its edge 1 inch from the face of the stud. Under IRC §P2603.2.1, the pipe must be protected by:

  • a.A layer of pipe insulation
  • b.A wrap of duct tape
  • c.A steel shield plate✓
  • d.A bead of fire caulking

Pipe other than cast iron or galvanized steel installed less than 1-1/4 inches from the nearest edge of the framing member is protected by steel shield plates, so that nails and screws cannot puncture it.IRC §P2603.2.1

General Requirements and Fixtures

Under IRC §P2603.2.1, a shield plate protecting pipe through a wall plate must extend beyond the top and sole plates by at least:

  • a.2 inches✓
  • b.1/4 inch
  • c.12 inches
  • d.8 inches

Shield plates are steel at least 0.0575 inch thick (No. 16 gage) and extend at least 2 inches above sole plates and below top plates.IRC §P2603.2.1

General Requirements and Fixtures

A water service passes through a concrete foundation wall. Under IRC §P2603.4, the pipe sleeve must be:

  • a.Twelve inches larger than the pipe
  • b.One-half size smaller than the pipe
  • c.The same size as the pipe
  • d.Two pipe sizes larger than the pipe✓

A pipe through a foundation wall has a relieving arch or a sleeve two pipe sizes greater than the pipe, so that settlement does not shear the pipe.IRC §P2603.4

General Requirements and Fixtures

Under IRC §P2604.3, backfill over a pipe in a trench is placed and tamped in layers of:

  • a.6 inches, until the pipe has 12 inches of cover✓
  • b.24 inches, until the pipe has 48 inches of cover
  • c.18 inches, until the pipe has 36 inches of cover
  • d.Any depth, since tamping is not required

Loose earth free of rocks and debris is placed in 6-inch layers and tamped until the crown of the pipe is covered by 12 inches of tamped earth.IRC §P2604.3

General Requirements and Fixtures

A trench for a building sewer runs parallel to a house footing. Under IRC §P2604.4, the trench may not extend below:

  • a.A 10-degree bearing plane from the top edge of the footing
  • b.The finished grade line at the outside face of the footing
  • c.The top of the foundation wall above the footing
  • d.A 45-degree bearing plane from the bottom edge of the footing✓

Trenching parallel to footings and walls does not extend into the bearing plane of the footing, taken as a 45-degree line from its bottom edge, so that the footing is not undermined.IRC §P2604.4

General Requirements and Fixtures

Under IRC Table P2605.1, horizontal PVC or ABS drain pipe must be supported at intervals of not more than:

  • a.4 feet✓
  • b.2 feet
  • c.20 feet
  • d.12 feet

Horizontal ABS and PVC pipe is supported every 4 feet; vertical runs are supported every 10 feet with mid-story guides for small sizes.IRC Table P2605.1

General Requirements and Fixtures

Under IRC Table P2605.1, horizontal PEX water tubing must be supported at intervals of not more than:

  • a.6 inches
  • b.12 feet
  • c.10 feet
  • d.32 inches✓

PEX tubing is supported every 32 inches horizontally, because the tubing is flexible and sags between supports when hot.IRC Table P2605.1

General Requirements and Fixtures

Under IRC Table P2605.1, horizontal copper water tubing 1 inch in diameter must be supported at intervals of not more than:

  • a.15 feet
  • b.6 feet✓
  • c.20 feet
  • d.1 foot

Copper tubing 1-1/4 inches and smaller is supported every 6 feet horizontally; 1-1/2 inches and larger every 10 feet.IRC Table P2605.1

General Requirements and Fixtures

A new DWV system in a house is tested with water at rough-in. Under IRC §P2503.5.1, the test needs a head of water of at least:

  • a.10 feet, held for 15 minutes✓
  • b.10 feet, held for 15 seconds
  • c.100 feet, held for 24 hours
  • d.1 foot, held for 15 minutes

The water test fills the system to a 10-foot head above the section tested and holds for 15 minutes with no leaks.IRC §P2503.5.1

General Requirements and Fixtures

Under IRC §P2503.5.1, an air test on a DWV system is made at:

  • a.100 psi for 24 hours, on any kind of piping
  • b.5 psi for 15 minutes, on plastic piping only
  • c.5 psi for 15 minutes, and not on plastic piping✓
  • d.50 psi for 15 minutes, on any kind of piping

The air test is 5 psi (10 inches of mercury) for 15 minutes. Plastic DWV piping is not tested with air, because a failure under compressed air can throw fragments.IRC §P2503.5.1

General Requirements and Fixtures

The water supply system of a new house is tested with water. Under IRC §P2503.7, the test pressure is at least:

  • a.500 psi, held for 24 hours
  • b.The working pressure of the system, held for 15 minutes✓
  • c.10 inches of water column, held for 10 minutes
  • d.Half the working pressure of the system, held for 1 minute

The water supply system is tested at not less than its working pressure, or for piping other than plastic by air at 50 psi, for 15 minutes.IRC §P2503.7

General Requirements and Fixtures

A site-built shower pan liner is tested before tile is set. Under IRC §P2503.6, the liner is filled with water to a depth of at least 2 inches at the threshold and held for:

  • a.15 seconds
  • b.4 hours
  • c.15 minutes✓
  • d.48 hours

The drain is plugged and the pan filled to at least 2 inches measured at the threshold; the water is held for 15 minutes with no leakage.IRC §P2503.6

General Requirements and Fixtures

Under IRC §P2705.1, the centre of a water closet must be at least how far from a side wall or partition?

  • a.36 inches
  • b.15 inches✓
  • c.9 inches
  • d.24 inches

A water closet, lavatory or bidet is set at least 15 inches from its centre to a side wall or obstruction and 30 inches centre to centre from an adjacent fixture.IRC §P2705.1

General Requirements and Fixtures

Under IRC §P2705.1, the clear space in front of a water closet, lavatory or bidet must be at least:

  • a.48 inches
  • b.36 inches
  • c.10 inches
  • d.21 inches✓

There is at least 21 inches of clearance in front of a water closet, lavatory or bidet to any wall, fixture or door.IRC §P2705.1

General Requirements and Fixtures

Under IRC §P2708.1, a shower compartment must have a finished interior area of at least:

  • a.900 square inches✓
  • b.1,600 square inches
  • c.2,500 square inches
  • d.400 square inches

A shower has at least 900 square inches of interior cross-sectional area and a minimum dimension of 30 inches, measured from the finished interior at the top of the threshold.IRC §P2708.1

General Requirements and Fixtures

Under IRC §P2708.1, the minimum finished interior dimension of a standard 900-square-inch shower compartment is:

  • a.18 inches
  • b.42 inches
  • c.60 inches
  • d.30 inches✓

Shower compartments need at least 900 square inches of interior area and at least 30 inches in minimum finished interior dimension. A 25-inch minimum dimension is allowed only where the area is at least 1,300 square inches.IRC §P2708.1

General Requirements and Fixtures

Under IRC §P2708.4, a shower control valve must be the pressure-balance, thermostatic or combination type and be limited to a maximum outlet temperature of:

  • a.120°F✓
  • b.140°F
  • c.100°F
  • d.160°F

Individual shower and tub-shower valves conform to ASSE 1016 or equivalent, with the high limit stop set to deliver no more than 120°F.IRC §P2708.4

General Requirements and Fixtures

Under IRC §P2713.3, hot water to a bathtub or whirlpool bathtub that has no tub-shower valve must be limited to:

  • a.180°F by a pressure-reducing valve
  • b.150°F by the water heater thermostat setting
  • c.100°F by a manual globe valve
  • d.120°F by a water-temperature limiting device✓

Bathtub and whirlpool tub fillers are limited to 120°F by a limiting device conforming to ASSE 1070 or equivalent. The water heater thermostat is not an acceptable control for this purpose.IRC §P2713.3

General Requirements and Fixtures

Under IRC §P2709.1, a shower pan liner must turn up on all sides above the finished threshold by at least:

  • a.2 inches✓
  • b.12 inches
  • c.18 inches
  • d.1/8 inch

The lining material extends at least 2 inches beyond or around the rough jambs and at least 2 inches above the finished threshold.IRC §P2709.1

General Requirements and Fixtures

Under IRC §P2709.2, the subfloor or mortar under a shower pan liner must be sloped toward the drain at:

  • a.1/4 inch per foot✓
  • b.2 inches per foot
  • c.4 inches per foot
  • d.1/32 inch per foot

The liner is laid on a base pitched 1/4 unit vertical in 12 units horizontal toward the weep holes of the drain, so that water under the tile does not stand on the liner.IRC §P2709.2

General Requirements and Fixtures

Under IRC §P2711.3, the waste outlet of a lavatory must be at least:

  • a.1/2 inch in diameter
  • b.2-1/2 inches in diameter
  • c.3-1/2 inches in diameter
  • d.1-1/4 inches in diameter✓

Lavatories have waste outlets not less than 1-1/4 inches in diameter, with a strainer, pop-up stopper or crossbars to restrict the opening.IRC §P2711.3

General Requirements and Fixtures

Under IRC §P2714.1, the waste outlet of a kitchen sink must be at least:

  • a.3 inches in diameter
  • b.4 inches in diameter
  • c.1-1/2 inches in diameter✓
  • d.3/4 inch in diameter

Sinks have waste outlets not less than 1-1/2 inches in diameter, with a strainer or crossbars.IRC §P2714.1

General Requirements and Fixtures

A dishwasher discharges into the kitchen sink tailpiece or disposer. Under IRC §P2717.2, the dishwasher drain hose must:

  • a.Connect directly to the vent pipe above the sink
  • b.Run flat along the cabinet floor before connecting
  • c.Drop through the floor to a separate trap in the crawl space before connecting
  • d.Rise and be fastened to the underside of the counter before connecting✓

The dishwasher waste line rises and is securely fastened to the underside of the sink rim or countertop before connecting to the disposer or wye tailpiece, so that sink waste does not flow back into the machine.IRC §P2717.2

General Requirements and Fixtures

Under IRC §P2706.1.2, a clothes washer standpipe must extend above the trap weir by at least 18 inches and not more than:

  • a.20 inches
  • b.42 inches✓
  • c.96 inches
  • d.72 inches

Standpipes are 18 inches minimum and 42 inches maximum above the trap weir: tall enough not to overflow or siphon, short enough for the pump to discharge freely.IRC §P2706.1.2

General Requirements and Fixtures

Under IRC §P2720.1, a whirlpool bathtub with a circulation pump needs:

  • a.A dedicated water heater of at least 80 gallons
  • b.A second overflow outlet at the opposite end
  • c.An access opening to the pump, sized for removal and repair✓
  • d.A floor drain under the bathtub, trapped and vented to the open air

Access is provided to circulation pumps in accordance with the manufacturer's instructions; where none are given, an opening at least 12 by 12 inches is provided, larger where the pump is far from the opening.IRC §P2720.1

General Requirements and Fixtures

Under IRC §P2721.2, the water discharged from a bidet must be limited to a temperature of not more than:

  • a.110°F✓
  • b.140°F
  • c.90°F
  • d.180°F

Bidets are limited to 110°F by a water-temperature limiting device conforming to ASSE 1070 or equivalent, a lower limit than the 120°F for showers and tubs.IRC §P2721.2

General Requirements and Fixtures

A fixture is set against a tile wall. Under IRC §P2705.1, the joint where the fixture meets the wall or floor must be:

  • a.Filled with insulation
  • b.Covered with wallpaper
  • c.Made watertight✓
  • d.Left open 1/2 inch

Where fixtures come in contact with walls and floors, the contact area is made watertight, so that water does not get behind the fixture and rot the structure.IRC §P2705.1

General Requirements and Fixtures

Under IRC §P2609.1, each length of pipe and each fitting used in a house must:

  • a.Be delivered to the site in the manufacturer's sealed carton
  • b.Be painted the color assigned to the system by the installer
  • c.Be stamped with the license number of the installing plumber
  • d.Bear the manufacturer's identification and the standard it meets✓

Each length of pipe and each fitting, trap, fixture and device bears the identification of the manufacturer and any markings required by the applicable standard, so the inspector can confirm it is an approved material.IRC §P2609.1

General Requirements and Fixtures

A plumber needs to notch a floor joist for a drain. Under the IRC, cutting and notching of framing for plumbing must:

  • a.Be done only in the middle third of the span of the joist
  • b.Remove no less than half of the depth of the member
  • c.Stay within the structural limits for notches and bored holes in the building chapters✓
  • d.Be approved in writing by the plumbing supplier before any cutting or boring is done on site

Structural members are not cut, notched or bored beyond the limits in the framing provisions; for sawn joists, notches are barred from the middle third of the span.IRC §P2603.2; §R502.8

General Requirements and Fixtures

Under IRC §P2603.5, a water pipe in an exterior wall, attic or crawl space subject to freezing temperatures must be:

  • a.Made of galvanized steel with threaded joints
  • b.Protected from freezing by insulation, heat or both✓
  • c.Sized one pipe size larger than calculated
  • d.Painted black to absorb heat from the sun in winter

Water, soil and waste pipes are not installed outside a building, in attics or crawl spaces, or in exterior walls subject to freezing unless protected by insulation or heat or both.IRC §P2603.5