Texas Tradesman Plumber-Limited Exam — All Questions

25 questions

Water Heaters

A storage water heater is installed in the attic of a house. Under IRC §P2801.6, because a leak would cause damage, the heater must be set in:

  • a.A pan with a drain✓
  • b.A wooden crate
  • c.A plastic bag
  • d.A bed of dry sand

Where a storage tank-type water heater is installed where leakage would cause damage, it sits in a pan of galvanized steel, aluminium or approved plastic that is drained.IRC §P2801.6

Water Heaters

Under IRC §P2801.6.1, a water heater pan must be at least how deep?

  • a.8 inches
  • b.1-1/2 inches✓
  • c.1/4 inch
  • d.12 inches

The pan is not less than 1-1/2 inches deep and is large enough to catch all dripping or condensate from the tank.IRC §P2801.6.1

Water Heaters

Under IRC §P2801.6.1, the drain from a water heater pan must be at least:

  • a.3/4 inch in diameter✓
  • b.1/4 inch in diameter
  • c.3 inches in diameter
  • d.2 inches in diameter

The pan is drained by an indirect waste pipe of not less than 3/4 inch diameter.IRC §P2801.6.1

Water Heaters

A water heater pan drain runs to the outside of the house. Under IRC §P2801.6.2, it must end above the adjacent ground surface by at least 6 inches and not more than:

  • a.8 inches
  • b.96 inches
  • c.24 inches✓
  • d.60 inches

A pan drain extended to the exterior terminates not less than 6 inches and not more than 24 inches above the adjacent ground surface; otherwise it ends over an indirect waste receptor.IRC §P2801.6.2

Water Heaters

A gas water heater is installed in an attached garage. Under IRC §P2801.7, its ignition source must be above the garage floor by at least:

  • a.2 inches, unless the garage door is kept open
  • b.60 inches, unless it is listed as flammable vapour ignition resistant
  • c.18 inches, unless it is listed as flammable vapour ignition resistant✓
  • d.18 inches, with no exception for any listed appliance

Water heaters having an ignition source are elevated so the source is at least 18 inches above the garage floor, except appliances listed as flammable vapour ignition resistant.IRC §P2801.7; §G2408.2

Water Heaters

Every storage water heater in a house must be protected, under IRC §P2804.1, by:

  • a.Temperature and pressure relief, separate or as a combination valve✓
  • b.A check valve on the cold water inlet only
  • c.A vacuum breaker on the drain valve only
  • d.A pressure-reducing valve on the hot water outlet, set at the factory to 150 psi

Appliances and equipment used for heating or storing hot water are protected by a pressure-relief valve and a temperature-relief valve, or a combination temperature and pressure relief valve.IRC §P2804.1

Water Heaters

Under IRC §P2804.3, the pressure-relief valve on a water heater must be set to open at not more than the working pressure of the heater and not more than:

  • a.15 psi
  • b.600 psi
  • c.150 psi✓
  • d.300 psi

The relief valve setting does not exceed the tank's rated working pressure or 150 psi, whichever is less.IRC §P2804.3

Water Heaters

Under IRC §P2804.4, a temperature-relief valve must have its sensing element:

  • a.In the relief discharge pipe
  • b.In the top 6 inches of the tank✓
  • c.In the cold water supply pipe
  • d.In the bottom 6 inches of the tank

The temperature element is installed so that it senses the hottest water, in the top 6 inches of the tank, and the valve opens at not more than 210°F.IRC §P2804.4

Water Heaters

A temperature-relief valve on a water heater must open, under IRC §P2804.4, at a water temperature of not more than:

  • a.300°F
  • b.125°F
  • c.210°F✓
  • d.250°F

The temperature-relief function operates at a maximum of 210°F, just below the boiling point of water at sea level, so the tank contents cannot flash to steam.IRC §P2804.4

Water Heaters

Under IRC §P2804.6.1, the relief valve discharge pipe must be sized:

  • a.Not smaller than the diameter of the relief valve outlet✓
  • b.At 3 inches, to match the building drain
  • c.At 1/4 inch tubing, whatever the size of the valve outlet
  • d.One pipe size smaller than the relief valve outlet

The discharge pipe is not smaller than the valve outlet for its full length, so that it does not restrict the flow when the valve opens.IRC §P2804.6.1

Water Heaters

Which fitting is prohibited in a water heater relief valve discharge pipe under IRC §P2804.6.1?

  • a.A coupling
  • b.A 90-degree elbow
  • c.A shutoff valve✓
  • d.A union at the valve

The discharge pipe has no valves or tee fittings, so nothing can block or divert the discharge. Elbows and couplings are permitted, although the run should be as short and direct as possible.IRC §P2804.6.1

Water Heaters

Under IRC §P2804.6.1, the end of a relief valve discharge pipe that terminates over the floor must be no more than how far above it?

  • a.6 inches✓
  • b.1/2 inch
  • c.24 inches
  • d.48 inches

The pipe ends not more than 6 inches and not less than two pipe diameters above the floor or waste receptor, so that the discharge is seen and does not scald anyone.IRC §P2804.6.1

Water Heaters

The outlet end of a relief valve discharge pipe, under IRC §P2804.6.1, must NOT be:

  • a.Threaded✓
  • b.Pointed down
  • c.Near the floor
  • d.Visible

The end of the discharge pipe is not threaded, so that nobody can screw on a cap or plug. It must discharge where it is observable and flow by gravity.IRC §P2804.6.1

Water Heaters

Under IRC §P2804.6.1, a relief valve discharge pipe must be installed so that it:

  • a.Rises above the valve before it drops
  • b.Flows by gravity and is not trapped✓
  • c.Serves two or more relief valves
  • d.Connects directly to the drainage system

The pipe drains by gravity, is not trapped, serves a single relief device and discharges through an air gap, not by direct connection to the drainage system.IRC §P2804.6.1

Water Heaters

Under IRC §P2801.2, every storage water heater must have a drain valve located:

  • a.On the gas supply pipe
  • b.At the top of the tank
  • c.At the bottom of the tank✓
  • d.On the hot water outlet pipe

Water heaters have a drain valve at the bottom of the tank for flushing sediment and emptying the tank for service or replacement.IRC §P2801.2

Water Heaters

Under IRC §P2903.9.2, a shutoff valve for a water heater is required on:

  • a.The cold water supply pipe at or near the heater✓
  • b.The pan drain where it leaves the building
  • c.The hot water outlet pipe only, at the first fixture
  • d.The relief valve discharge pipe near the floor

A readily accessible full-open valve is installed in the cold water supply pipe to each water heater at or near the heater.IRC §P2903.9.2

Water Heaters

A backflow preventer is installed on the water service to a house, creating a closed system. Under IRC §P2903.4, the plumber must provide:

  • a.A pressure-reducing valve on the hot water outlet
  • b.A second water heater piped in parallel with the first, of equal storage
  • c.A larger relief valve discharge pipe on the heater
  • d.A device to control thermal expansion, such as an expansion tank✓

Where a backflow preventer, check valve or pressure-reducing valve without a bypass closes the system, thermal expansion from the water heater is controlled by an expansion tank or other approved device.IRC §P2903.4

Water Heaters

Under IRC §M2005.2, a fuel-fired water heater may NOT be installed in a room used as a storage closet, and may be in a bedroom or bathroom only if it is:

  • a.Rated at less than 75,000 Btu/h and set on a stand of 18 inches
  • b.A draft-hood type connected to a masonry chimney by a single-wall vent connector
  • c.Fitted with a pan and a drain line of 3/4 inch to the exterior
  • d.A direct-vent type, or in a sealed enclosure taking combustion air from outdoors✓

Fuel-fired water heaters are not installed in storage closets. In bedrooms and bathrooms they are direct-vent, or in a sealed enclosure with a self-closing weather-stripped door so that combustion air is not taken from the living space.IRC §M2005.2; §G2406.2

Water Heaters

A water heater is installed in an attic. Under IRC §M1305.1.3, the passageway from the attic access opening to the heater may be no longer than:

  • a.150 feet
  • b.20 feet✓
  • c.2 feet
  • d.75 feet

The passageway is at least 30 inches high and 22 inches wide and not more than 20 feet long, with solid flooring at least 24 inches wide and a level service space at the appliance.IRC §M1305.1.3

Water Heaters

Under IRC §M1305.1.3, the attic access opening for a water heater must be large enough to remove the heater and not smaller than:

  • a.60 inches by 96 inches
  • b.48 inches by 60 inches
  • c.8 inches by 10 inches
  • d.20 inches by 30 inches✓

The clear access opening is at least 20 by 30 inches and large enough for the largest appliance to be removed.IRC §M1305.1.3

Water Heaters

A gas water heater stands where a car could hit it in a garage. Under IRC §G2408.3 and §M1307.3.1, the heater must be:

  • a.Enclosed in a wooden cabinet
  • b.Hung from the ceiling joists
  • c.Protected from vehicle impact✓
  • d.Painted a bright warning color

Appliances located where they are subject to vehicle impact are protected by barriers such as bollards, or are placed out of the vehicle's path.IRC §M1307.3.1; §G2408.3

Water Heaters

Under IRC §P2801.4, a water heater must be installed so that it can be:

  • a.Moved without disconnecting any piping
  • b.Reached for observation, maintenance and replacement✓
  • c.Sealed permanently behind finished drywall
  • d.Buried under attic insulation to save energy and stop heat loss

Water heaters are accessible for observation, maintenance, servicing and replacement; they are not walled in or buried behind permanent construction.IRC §P2801.4

Water Heaters

A water heater supplies both domestic hot water and a hydronic space-heating coil that needs water at 160°F. Under IRC §P2803.2, the potable hot water to fixtures must pass through:

  • a.A check valve that keeps it at 160°F or more
  • b.A second relief valve set at 75 psi on the cold inlet
  • c.A strainer with a blow-down valve
  • d.A tempering valve that limits it to 140°F or less✓

Where a combination system needs water above 140°F for space heating, a master thermostatic mixing valve conforming to ASSE 1017 limits the water supplied to the potable distribution system to 140°F or less.IRC §P2803.2

Water Heaters

In Texas, a homeowner asks why a relief valve discharge pipe may not be reduced from 3/4 inch to 1/2 inch to make the run easier. The best answer is that:

  • a.A smaller pipe is not sold in materials rated for hot water
  • b.A smaller pipe makes the relief valve open at a lower pressure setting than its rating
  • c.A smaller pipe cools the water too quickly before it reaches the floor
  • d.A smaller pipe restricts the discharge and can let pressure build in the tank✓

The discharge pipe must carry the full relief flow. Reducing it restricts the flow, so the valve cannot relieve the tank fast enough.IRC §P2804.6.1

Water Heaters

Under IRC §P2801.8, in areas where seismic design applies, a water heater must be:

  • a.Strapped to resist horizontal movement in the upper and lower thirds of the tank✓
  • b.Set loose on rollers so that it can move freely
  • c.Bolted through the bottom of the tank into the floor slab with four expansion anchors of 1/2 inch
  • d.Hung from the roof framing on threaded steel rod

In Seismic Design Categories D0, D1, D2 and townhouses in C, water heaters are anchored with strapping in the upper one-third and lower one-third of the appliance. Most of Texas is outside these categories, but the rule is part of the code tested.IRC §P2801.8