Chapter 6 of 7
Vents and Traps
Chapters 31 and 32 of the International Residential Code cover vents and traps. A trap holds a water seal against sewer gas, and the vent protects that seal from siphonage and back pressure.
Traps
Every fixture has a trap with a seal of 2 to 4 inches. Traps that siphon themselves or collect solids are prohibited.
Trap seal
Not less than 2 inches and not more than 4 inches.
IRC §P3201.2Prohibited traps
S traps, bell traps, drum traps, crown-vented traps.
IRC §P3201.5Outlet to trap
Not more than 24 inches vertically and 30 inches horizontally.
IRC §P3201.6Trap sizes
Lavatory 1-1/4 inch; tub, shower, kitchen sink 1-1/2 inch; washer standpipe 2 inch.
IRC Table P3201.7Trap arms and vent connections
The distance from trap to vent is limited by pipe size. The arm may not fall more than one pipe diameter, and the vent may not connect within two pipe diameters of the weir.
Trap arm length
1-1/4 inch: 5 feet. 1-1/2 inch: 6 feet. 2 inch: 8 feet. 3 inch: 12 feet.
IRC Table P3105.1Fall
Not more than one pipe diameter.
IRC §P3105.2Crown vent
No vent within two pipe diameters of the trap weir.
IRC §P3105.3Vent piping and terminals
Vents drain back to the drainage system, rise above the flood rim before offsetting, and end outdoors.
Roof terminal
At least 6 inches above the roof.
IRC §P3103.1.1Offsets
Not below 6 inches above the flood level rim of the highest fixture served.
IRC §P3104.4Size
At least half the drain diameter and never under 1-1/4 inches; one size larger over 40 feet.
IRC §P3113.1Wet vent
Fixtures of up to two bathroom groups on the same floor.
IRC §P3108.1Air admittance valves
Installed after testing, accessible, 4 inches above the drain served, 6 inches above attic insulation.
IRC §P3114