Chapter 28 of the International Residential Code covers water heaters in houses: location, pans, relief valves and their discharge piping.
Location and protection
A water heater needs access for service, protection from vehicles in a garage, and a pan where a leak would cause damage. Fuel-fired heaters in garages have their ignition source raised unless the appliance is listed as flammable-vapor-ignition resistant.
Pans
Required where leakage would cause damage; the pan drains to an approved location.
IRC §P2801.6Garage installation
Ignition source raised above the floor.
IRC §P2801.7Relief valves
Every storage water heater has temperature and pressure relief protection. The discharge pipe is full size, runs by gravity, and ends where it can be seen without causing harm.
Relief valve
Temperature and pressure relief required.
IRC §P2804Discharge pipe
Not smaller than the valve outlet, no valves or traps, not threaded at the end.
IRC §P2804.6.1Mixing valve
Required for combination water and space heating appliances at higher temperatures.
IRC §P2803.2