What is the secondary full-load current of a 25 kVA single-phase transformer with a 240-volt secondary?
a.Approximately 60 amperes
b.Approximately 104 amperes
c.Approximately 208 amperes
d.Approximately 52 amperes
Explicación
For a single-phase transformer, I = VA / E = 25,000 / 240, or about 104 amperes. The 60-ampere answer divides by 480 volts, 208 amperes divides by 120 volts, and 52 amperes is half the correct value.
Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- On a 208Y/120-volt wye system, what is the relationship between line voltage and phase voltage?
- A balanced delta-connected load has a phase current of 20 amperes. What is the line current?
- A single-phase transformer has a 480-volt primary and a 120-volt secondary. If the secondary carries 100 amperes, what is the approximate primary current?
- A 480-volt panelboard is mounted on a wall with a grounded concrete wall directly behind the working space. What is the minimum depth of working space?
- What is the minimum width of working space in front of electrical equipment?
- Entrances at each end of the working space are generally required for equipment rated at least what value and over 6 feet wide?