Branch Circuits & FeedersPregunta 12 de 120
What is the allowable ampacity of 8 AWG copper Type NM cable?
a.40 amperes
b.55 amperes
c.50 amperes
d.45 amperes
Explicación
The ampacity of Type NM cable must be taken from the 60 degrees C column of Table 310.16, where 8 AWG copper is 40 A, even though the conductors inside carry a 90 degrees C rating. The 50 A and 55 A choices come from the 75 degrees C and 90 degrees C columns, which may be used only as a starting point for derating, not as the final NM cable ampacity.
Referencia Legal: 2023 NEC §334.80Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Which of the following is NOT a standard ampere rating for fuses and inverse-time circuit breakers?
- What is the minimum number of 20-ampere small-appliance branch circuits required for the kitchen, pantry, breakfast room and dining room receptacles of a dwelling unit?
- What is the minimum branch-circuit rating for the receptacle outlets serving a dwelling unit bathroom?
- A feeder supplies a 100-ampere continuous load. Using 75 degrees C terminations and copper THWN, what is the minimum feeder conductor size?
- Nine current-carrying 10 AWG THHN copper conductors share one raceway at a 30 degrees C ambient. What is the adjusted ampacity of each?
- A four-wire, three-phase, 208Y/120-volt feeder supplies electric-discharge lighting, and the major portion of the load is nonlinear. How many current-carrying conductors are counted for adjustment purposes?