Branch Circuits & FeedersPregunta 21 de 120

For that same 45-ampere continuous lighting feeder, what is the minimum copper conductor size at 75 degrees C terminations?

a.6 AWG
b.8 AWG
c.4 AWG
d.10 AWG

Explicación

The conductor must carry 45 x 1.25 = 56.25 A. In the 75 degrees C column, 8 AWG copper is 50 A and is insufficient, while 6 AWG copper at 65 A meets the requirement. 4 AWG is oversized for the stated minimum, and 10 AWG at 35 A is far below the calculated ampacity.

Referencia Legal: 2023 NEC §215.2(A)(1)