Branch Circuits & FeedersPregunta 22 de 120

What is the smallest conductor size generally permitted to be installed in parallel?

a.250 kcmil
b.2 AWG
c.4/0 AWG
d.1/0 AWG

Explicación

Conductors of 1/0 AWG and larger may be run in parallel when the paralleled sets are the same length, material, size and insulation type and terminate in the same manner. Sizes smaller than 1/0, such as 2 AWG, are not permitted to be paralleled except in a few narrow special applications, and 4/0 or 250 kcmil are simply larger than the stated minimum.

Referencia Legal: 2023 NEC §310.10(G)