Wiring Methods & MaterialsPregunta 62 de 120

When more than two conductors are installed in a raceway, what is the maximum permitted percentage of the raceway cross-sectional area they may occupy?

a.53 percent
b.31 percent
c.40 percent
d.60 percent

Explicación

Chapter 9, Table 1 allows 53 percent fill for one conductor, 31 percent for exactly two conductors and 40 percent for three or more. The 60 percent value applies only to a nipple not exceeding 24 inches in length between boxes or enclosures.

Referencia Legal: 2023 NEC Chapter 9, Table 1