Wiring Methods & MaterialsPregunta 65 de 120

What is the minimum cover for a direct-buried UF cable installed in a residential yard on a 120-volt, 20-ampere circuit that is NOT GFCI protected?

a.18 inches
b.24 inches
c.12 inches
d.6 inches

Explicación

Direct-buried cables and conductors under all locations not otherwise covered require 24 inches of cover. The 12-inch reduction applies only to residential branch circuits rated 120 volts or less, 20 amperes or less, and provided with GFCI protection, so removing the GFCI removes the reduction. The 6-inch and 18-inch values belong to metal and nonmetallic raceways respectively.

Referencia Legal: 2023 NEC Table 300.5