Wiring Methods & MaterialsPregunta 67 de 120

What is the minimum burial cover for a nonmetallic raceway listed for direct burial without concrete encasement, installed under a lawn?

a.18 inches
b.6 inches
c.24 inches
d.12 inches

Explicación

Listed nonmetallic raceways buried without concrete encasement require 18 inches of cover in locations not otherwise specified. Metal conduit needs only 6 inches, direct-buried cable needs 24 inches, and 12 inches applies to GFCI-protected 120-volt residential branch circuits.

Referencia Legal: 2023 NEC Table 300.5

Practica las 120 preguntas gratis — sin registro.