Wiring Methods & MaterialsPregunta 67 de 120
What is the minimum burial cover for a nonmetallic raceway listed for direct burial without concrete encasement, installed under a lawn?
a.18 inches
b.6 inches
c.24 inches
d.12 inches
Explicación
Listed nonmetallic raceways buried without concrete encasement require 18 inches of cover in locations not otherwise specified. Metal conduit needs only 6 inches, direct-buried cable needs 24 inches, and 12 inches applies to GFCI-protected 120-volt residential branch circuits.
Referencia Legal: 2023 NEC Table 300.5Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Four 3/0 AWG THWN conductors, each 0.2679 square inch in area, are pulled into rigid metal conduit. What is the minimum trade size?
- What is the minimum cover for a direct-buried UF cable installed in a residential yard on a 120-volt, 20-ampere circuit that is NOT GFCI protected?
- What is the minimum burial cover for rigid metal conduit installed underground in a location not otherwise specified?
- A GFCI-protected 120-volt, 20-ampere residential branch circuit is direct buried in a yard. What is the minimum cover?
- How must electrical metallic tubing be secured and supported on a normal horizontal run?
- How must Type NM cable be supported where it enters a box equipped with cable clamps?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Electrician Licensing Exam (NEC-based) · Cómo revisamos