Wiring Methods & MaterialsPregunta 66 de 120

What is the minimum burial cover for rigid metal conduit installed underground in a location not otherwise specified?

a.18 inches
b.12 inches
c.6 inches
d.24 inches

Explicación

Rigid metal conduit and intermediate metal conduit are permitted at 6 inches of cover because the metal wall provides its own physical protection. Nonmetallic raceways listed for direct burial require 18 inches, direct-buried cable requires 24 inches, and 12 inches applies to GFCI-protected residential branch circuits.

Referencia Legal: 2023 NEC Table 300.5