Wiring Methods & MaterialsPregunta 77 de 120
An angle pull box has one 2-inch raceway and one 1-inch raceway entering the same wall, with conductors turning 90 degrees. What is the minimum distance from that wall to the opposite wall?
a.24 inches
b.12 inches
c.16 inches
d.13 inches
Explicación
For angle pulls the distance is six times the trade size of the largest raceway plus the sum of the diameters of the other raceways on the same wall: (6 x 2) + 1 = 13 inches. The 12-inch answer forgets to add the additional raceway, and 24 inches applies the straight-pull factor of eight.
Referencia Legal: 2023 NEC §314.28(A)(2)Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- What is the maximum total amount of bend permitted in one run of EMT between pull points?
- A cable passes through a bored hole in a wood stud. If the edge of the hole is less than 1 and 1/4 inches from the nearest edge of the stud, what is required?
- A pull box is used for a straight pull, and the largest raceway entering it is 3 inch trade size. What is the minimum required length of the box in the direction of the pull?
- How must liquidtight flexible metal conduit be secured on a normal run?
- How many 12 AWG conductors may be installed in a 4-11/16 inch by 2-1/8 inch square box with a volume of 42.0 cubic inches, assuming no clamps, devices or fittings?
- Direct-buried conductors emerging from grade must be protected by an approved enclosure or raceway from below grade to what height?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Electrician Licensing Exam (NEC-based) · Cómo revisamos