Wiring Methods & MaterialsPregunta 78 de 120

How must liquidtight flexible metal conduit be secured on a normal run?

a.Within 12 inches of each box and at intervals not exceeding 6 feet
b.Within 3 feet of each box and at intervals not exceeding 10 feet
c.Within 12 inches of each box or fitting and at intervals not exceeding 4 and 1/2 feet
d.Support is not required for lengths of 6 feet or less in any application

Explicación

LFMC is secured within 12 inches of each box, cabinet or fitting and supported at intervals not exceeding 4 and 1/2 feet. Certain short lengths used for flexibility or for connections to luminaires are exempt, but that exemption is narrow and does not apply to ordinary runs, and the 10-foot spacing belongs to rigid raceways.

Referencia Legal: 2023 NEC §350.30(A)