Fixtures & Water HeatersPregunta 71 de 120
A 120,000 Btu/h gas water heater draws all of its combustion air directly from outdoors through two vertical ducts. Using the 1 square inch per 4,000 Btu/h rule for vertical ducts, what is the required free area of each opening?
a.15 square inches
b.30 square inches
c.60 square inches
d.12 square inches
Explicación
Dividing 120,000 by 4,000 gives 30 square inches, and that is the required free area for each of the two openings, one near the top and one near the bottom of the enclosure. 60 square inches is the combined area of both openings, not the size of each. 15 square inches halves the correct figure, and 12 square inches corresponds to no recognized ratio.
Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A 50 gallon water heater is installed in the attic above a finished ceiling. A drain pan is required. What is the minimum size of the pan drain line?
- A gas fired water heater is installed in a residential garage in a seismic zone. It must be strapped in two places. Where must the lower strap be located relative to the heater's controls?
- The same gas water heater is installed in that garage on a concrete slab. What is the minimum height that the source of ignition must be elevated above the garage floor?
- A 100,000 Btu/h water heater is placed in a closet and will take combustion air from inside the building only. Using the rule of thumb of 50 cubic feet of room volume per 1,000 Btu/h, what minimum volume of communicating space is needed?
- Where an enclosure takes combustion air from an adjacent room through two permanent openings, where must those openings be located?
- A shower compartment is framed 32 inches by 32 inches inside the finished walls. Does it meet the minimum area and minimum dimension requirements for a shower?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos