Fixtures & Water HeatersPregunta 72 de 120
A 100,000 Btu/h water heater is placed in a closet and will take combustion air from inside the building only. Using the rule of thumb of 50 cubic feet of room volume per 1,000 Btu/h, what minimum volume of communicating space is needed?
a.2,000 cubic feet
b.3,000 cubic feet
c.5,000 cubic feet
d.10,000 cubic feet
Explicación
Dividing 100,000 by 1,000 gives 100, and 100 times 50 cubic feet equals 5,000 cubic feet of communicating volume. 2,000 and 3,000 cubic feet come from applying a 20 or 30 cubic foot factor that the standard indoor air method does not use. 10,000 cubic feet doubles the requirement and would only be relevant if two such appliances shared the space.
Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A gas fired water heater is installed in a residential garage in a seismic zone. It must be strapped in two places. Where must the lower strap be located relative to the heater's controls?
- The same gas water heater is installed in that garage on a concrete slab. What is the minimum height that the source of ignition must be elevated above the garage floor?
- A 120,000 Btu/h gas water heater draws all of its combustion air directly from outdoors through two vertical ducts. Using the 1 square inch per 4,000 Btu/h rule for vertical ducts, what is the required free area of each opening?
- Where an enclosure takes combustion air from an adjacent room through two permanent openings, where must those openings be located?
- A shower compartment is framed 32 inches by 32 inches inside the finished walls. Does it meet the minimum area and minimum dimension requirements for a shower?
- An indirect waste pipe from a commercial ice machine is 1-1/2 inches in diameter and discharges into a floor sink. What is the minimum required air gap?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos