An indoor dry-type transformer rated 45 kVA with standard (Class 105) insulation must maintain what minimum separation from combustible material unless otherwise protected?

  • a.18 in
  • b.3 in
  • c.12 in✓
  • d.6 in

2023 NEC 450.21(A): dry-type transformers 112.5 kVA and under must be separated at least 12 in from combustible material unless the unit has a listed fire-resistant barrier or Class 155 (or higher) insulation.

Advanced Wiring

Which value from a motor nameplate must be used with the tables to size branch-circuit short-circuit protection and conductors, per 430.6(A)?

  • a.the nameplate full-load amperes
  • b.the service-factor amps
  • c.the locked-rotor current
  • d.the table full-load current, not the nameplate current rating✓

2023 NEC 430.6(A)(1): for general motor applications, the full-load current values in Tables 430.247-430.250 (not the nameplate FLA) are used to size conductors and short-circuit/ground-fault protection. Overload protection uses the nameplate FLA.

Advanced Wiring

The disconnecting means for air-conditioning or refrigerating equipment with a motor-compressor must be located:

  • a.only at the main service panel
  • b.inside a locked mechanical room only
  • c.at least 25 ft away
  • d.within sight from and readily accessible from the equipment✓

2023 NEC 440.14: the disconnect must be within sight from, and readily accessible from, the air-conditioning or refrigerating equipment.

Advanced Wiring

How many overload (running-protection) units are required for a three-phase alternating-current motor?

  • a.one
  • b.three✓
  • c.four
  • d.two

2023 NEC Table 430.37: a three-phase AC motor requires three overload units, one in each phase.

Advanced Wiring

In patient care spaces, grounding of receptacles and fixed electrical equipment must be accomplished by:

  • a.an isolated ground only
  • b.the metal raceway alone as the only ground path
  • c.the grounded (neutral) conductor
  • d.an insulated copper equipment grounding conductor plus a metal raceway or cable armor (redundant ground)✓

2023 NEC 517.13: patient care spaces require redundant grounding - an insulated copper EGC AND a metallic raceway or cable that itself qualifies as a grounding path.

Advanced Wiring

The disconnecting means for a motor must have an ampere rating of at least what percentage of the motor full-load current?

  • a.115%✓
  • b.125%
  • c.100%
  • d.110%

2023 NEC 430.110(A): the disconnecting means for a motor circuit must be rated at least 115% of the motor full-load current.

¿Qué tan difícil es el examen?

La licencia de electricista maestro la administra cada estado y se basa en el NEC, así que el formato varía por estado. En Texas, por ejemplo, el examen tiene dos partes a libro abierto (NEC 2023) — 75 ítems de conocimiento del NEC y 33 ítems de cálculo (108 en total) — cada una requiere 70% para aprobar, por una tarifa de $78. Los electricistas ganan una mediana de unos $62,350 al año (BLS, mayo 2024).

Horas de estudio recomendadas
80-150 horas para la mayoría — los exámenes de maestro agregan cálculos más pesados y mayor profundidad de aplicación del código que el de oficial.
Tasa de aprobación publicada
19.08% (la fuente no dice qué intentos cuenta) (n = 3,946); 22.21% (la fuente no dice qué intentos cuenta) (n = 3,472) — Texas TDLR, FY 2025. Léelas como dos exámenes, no uno: TDLR no tiene fila llamada “Master Electrician”, solo “Master Calculations” (la primera cifra) y “Master NEC” (la segunda). Quien cite un único 19% de master en Texas ha descartado en silencio la mitad del examen. La licencia es estatal, así que esto es solo Texas.Fuente: Texas TDLR — Electrician Exam Statistics, Fiscal Year 2025
Por dónde empezar
Servicios, equipo de servicio y sistemas derivados por separado está entre las áreas más pesadas (cerca del 18% en Texas), más la parte de cálculo de cargas.

Las tarifas y los salarios son aproximados y cambian con el tiempo. La tasa de aprobación de arriba se cita de la fuente enlazada junto a ella, para el periodo que esa fuente cubre; cuando no hemos verificado una fuente, lo decimos y no damos ninguna cifra.

Reportar