For circuits rated over 100 A, conductor ampacity for terminations is generally based on which temperature column?
a.60 C
b.75 C
c.90 C
d.Nameplate only
Explicación
Terminations on equipment over 100 A are based on the 75 C column unless listed and marked for a higher rating.
Referencia Legal: 2023 NEC 110.14(C)(1)Practica las 110 preguntas gratis — sin registro.