Code Admin & SafetyPregunta 100 de 110
Equipment rated at what current or more requires two entrances to and egress from the working space when the space is large or contains overcurrent devices?
a.800 A
b.600 A
c.1000 A
d.1200 A
Explicación
For equipment rated 1,200 A or more and over 6 ft wide, two entrances/egress paths to the working space are required.
Referencia Legal: 2023 NEC 110.26(C)(2)Practica las 110 preguntas gratis — sin registro.