Code Admin & SafetyPregunta 98 de 110
What is the minimum headroom (height) of working space about electrical equipment such as panelboards?
a.6 ft
b.6.5 ft
c.7 ft
d.8 ft
Explicación
The minimum headroom of working space is 6.5 ft (or the height of the equipment, whichever is greater).
Referencia Legal: 2023 NEC 110.26(A)(3)Practica las 110 preguntas gratis — sin registro.