CalculationsPregunta 30 de 110
A commercial building has a 30,000-VA receptacle load. Applying the demand (first 10 kVA at 100%, remainder at 50%), what is the demand load?
a.30,000 VA
b.20,000 VA
c.15,000 VA
d.25,000 VA
Explicación
First 10,000 VA at 100% = 10,000; remaining 20,000 at 50% = 10,000. Total demand = 20,000 VA.
Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- For a 112.5-kVA, 208-V, three-phase transformer with 2% impedance, what is the approximate available fault current at the secondary terminals (infinite primary)?
- A 45-kVA, 208-V, three-phase transformer has 2% impedance. What is the approximate available fault current at its secondary (infinite primary)?
- Six current-carrying THHN conductors share one raceway. If the 90 C ampacity of #6 Cu is 75 A, what is the adjusted ampacity after the fill adjustment factor for 4-6 conductors?
- A #3 Cu THHN conductor has a 90 C ampacity of 110 A. In a 50 C ambient (correction factor 0.82), what is the corrected ampacity?
- A #2 Cu THHN (90 C ampacity 130 A) runs with 6 current-carrying conductors (0.80 factor) in a 40 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?
- An office has 45 general-use receptacle outlets. At 180 VA per outlet, what is the receptacle load before demand factors?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Electrician Licensing Exam (NEC-based) · Cómo revisamos