Services & DistributionPregunta 47 de 110
At a separately derived system such as a transformer, what conductor connects the grounded conductor to the system grounding electrode?
a.Main bonding jumper
b.Equipment bonding jumper
c.System bonding jumper
d.Grounding electrode conductor
Explicación
The system bonding jumper connects the grounded conductor of a separately derived system to the supply-side equipment grounding/bonding at one point.
Referencia Legal: 2023 NEC 250.30(A)Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Two paralleled sets of 500-kcmil Cu (75 C, 380 A each) supply one feeder. What is the combined ampacity before adjustment?
- What is the minimum service disconnecting-means rating for a one-family dwelling?
- What is the minimum vertical clearance of an overhead service drop (not over 300 V) above a residential driveway or sidewalk area limited to pedestrians?
- An emergency system must be capable of supplying power to its loads within what maximum time after normal supply is lost?
- A legally required standby system must supply its loads within what maximum time after loss of normal power?
- Generator output conductors must have an ampacity of at least what percent of the nameplate current?