Advanced WiringPregunta 66 de 110
A hermetic compressor has a rated-load current of 24 A. What is the maximum branch-circuit short-circuit and ground-fault device at 175% (next standard size)?
a.40 A
b.45 A
c.50 A
d.60 A
Explicación
175% of 24 A = 42 A; the next standard overcurrent size is 45 A, which is the maximum permitted for short-circuit/ground-fault protection.
Referencia Legal: 2023 NEC 440.22(A)Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A wet-niche underwater luminaire operating without GFCI protection is limited to a maximum of:
- A motor disconnecting means must have an ampere rating of at least what percent of the motor full-load current?
- A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. What minimum branch-circuit conductor ampacity is required?
- Which nameplate value on an air-conditioning unit is used to size the branch-circuit conductors?
- A Class 2 power-limited circuit at 30 V or less is limited to a maximum power of:
- Cables listed for power-limited fire alarm use are marked with which type designation?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Electrician Licensing Exam (NEC-based) · Cómo revisamos