Advanced WiringPregunta 67 de 110
Which nameplate value on an air-conditioning unit is used to size the branch-circuit conductors?
a.Maximum overcurrent protection
b.Nameplate horsepower
c.Minimum circuit ampacity
d.Rated-load amps only
Explicación
Conductors are sized to the marked minimum circuit ampacity (MCA); the maximum overcurrent protective device (MOCP) sizes the breaker or fuse.
Referencia Legal: 2023 NEC 440.4Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A motor disconnecting means must have an ampere rating of at least what percent of the motor full-load current?
- A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. What minimum branch-circuit conductor ampacity is required?
- A hermetic compressor has a rated-load current of 24 A. What is the maximum branch-circuit short-circuit and ground-fault device at 175% (next standard size)?
- A Class 2 power-limited circuit at 30 V or less is limited to a maximum power of:
- Cables listed for power-limited fire alarm use are marked with which type designation?
- Two 10-HP, 460-V motors (14 A each) are supplied by one feeder. What minimum feeder conductor ampacity is required?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Electrician Licensing Exam (NEC-based) · Cómo revisamos