Advanced WiringPregunta 70 de 110
Two 10-HP, 460-V motors (14 A each) are supplied by one feeder. What minimum feeder conductor ampacity is required?
a.28 A
b.31.5 A
c.35 A
d.25 A
Explicación
125% of the largest motor plus the other: (14 x 1.25) + 14 = 17.5 + 14 = 31.5 A.
Referencia Legal: 2023 NEC 430.24Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Which nameplate value on an air-conditioning unit is used to size the branch-circuit conductors?
- A Class 2 power-limited circuit at 30 V or less is limited to a maximum power of:
- Cables listed for power-limited fire alarm use are marked with which type designation?
- A motor without a marked service factor (or with SF under 1.15) has a full-load current of 28 A. What is the maximum overload protection at 115%?
- Which wiring method is acceptable in a Class I, Division 2 location?
- A required branch circuit that supplies a sign or outline lighting system must be rated at least:
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Electrician Licensing Exam (NEC-based) · Cómo revisamos