Advanced WiringPregunta 73 de 110
A required branch circuit that supplies a sign or outline lighting system must be rated at least:
a.20 A
b.15 A
c.30 A
d.40 A
Explicación
Each commercial building must have at least one dedicated 20-A branch circuit for a sign or outline lighting outlet.
Referencia Legal: 2023 NEC 600.5(B)Practica las 110 preguntas gratis — sin registro.