Advanced WiringPregunta 77 de 110

A motor feeder supplies motors whose largest branch device is 90 A, plus other motors with 50 A total full-load current. What is the maximum feeder short-circuit/ground-fault device (not to exceed the sum, next standard down)?

a.125 A
b.150 A
c.175 A
d.110 A

Explicación

The feeder device may not exceed the largest branch-circuit device (90 A) plus the other FLCs (50 A) = 140 A; the largest standard rating not exceeding 140 A is 125 A.

Referencia Legal: 2023 NEC 430.62