Design & SizingPregunta 19 de 110

A roof drains 4,800 ft^2 at a design rainfall rate of 4 in/hr. Using Q = 0.0104 x A x i, what is the storm design flow?

a.150 gpm
b.250 gpm
c.200 gpm
d.320 gpm

Explicación

Q = 0.0104 x 4,800 x 4 = 199.7 gpm, about 200 gpm. Doubling the rainfall rate doubles the flow for the same roof, which is why the local 100-year rainfall intensity is critical to storm sizing. This flow selects the leader and storm drain sizes.

Referencia Legal: UPC §1101.0