Design & SizingPregunta 20 de 110

A storm sizing table is published at 4 in/hr. A vertical leader lists a capacity of 4,600 ft^2 of roof at 4 in/hr. If the local design rate is only 2 in/hr, what roof area can that same leader serve?

a.2,300 ft^2
b.4,600 ft^2
c.18,400 ft^2
d.9,200 ft^2

Explicación

Capacity in area is inversely proportional to rainfall rate, so halving the rate from 4 to 2 in/hr doubles the allowable area: 4,600 x (4/2) = 9,200 ft^2. Conductor capacity is fixed in gpm, so a lighter storm lets the same pipe drain more roof. Always adjust table areas to the local rainfall rate.

Referencia Legal: UPC §1101.0