Gas & FuelPregunta 72 de 110

A gas appliance vent connector runs 12 ft horizontally to the chimney. Code requires a minimum upward rise of 1/4 in per foot toward the chimney. What total vertical rise must the connector have?

a.1-1/2 in
b.6 in
c.12 in
d.3 in

Explicación

Rise = 1/4 in per ft x 12 ft = 3 in of upward slope from the appliance to the chimney. The rise keeps hot flue gas moving upward and prevents it from stalling and spilling back into the room. A level or downward-sloped connector defeats natural draft and can spill carbon monoxide.

Referencia Legal: IFGC §503.6

Practica las 110 preguntas gratis — sin registro.