Gas & FuelPregunta 75 de 110
An elevated industrial gas line operates at 5 psi and is regulated down for appliances rated in inches of water column. Using 1 psi = 27.7 in water column, what is 5 psi expressed in inches of water column?
a.27.7 in w.c.
b.55.4 in w.c.
c.138.5 in w.c.
d.500 in w.c.
Explicación
Inches of water column = psi x 27.7 = 5 x 27.7 = 138.5 in w.c. Appliance regulators are commonly set near 7 in w.c. for natural gas, so an elevated 138.5 in w.c. supply must be stepped down by a line-pressure regulator with overpressure protection. Mixing up psi and inches of water column is a common and dangerous error.
Referencia Legal: IFGC §614.0Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Each gas appliance must have an accessible manual shutoff. Where must the appliance shutoff valve be located?
- Using the known-air-infiltration method, an appliance space of 10,000 ft^3 is credited with 0.35 air changes per hour of natural infiltration. How many cubic feet of infiltration air per hour does the space provide?
- A gas appliance vent connector runs 12 ft horizontally to the chimney. Code requires a minimum upward rise of 1/4 in per foot toward the chimney. What total vertical rise must the connector have?
- A two-appliance system: appliance A needs 60 cfh and appliance B needs 40 cfh. Using the longest-length method, the section of pipe between the meter and the first tee carries what demand?
- A leak test on an in-service gas line uses a soap-bubble or electronic method rather than a pressure drop. When is the bubble/electronic leak check the appropriate method?
- A natural-gas dryer needs 35,000 BTU/hr and a range needs 65,000 BTU/hr on a shared branch. Using 1,000 BTU/ft^3, what is the combined cfh the common branch must carry?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos