Dịch vụ & Phân phốiCâu 44 / 521
Service-entrance conductors must supply a computed load of 160 A continuous. What minimum conductor ampacity is required per 230.42?
a.160 A
b.128 A
c.175 A
d.200 A
Giải thích
Per 230.42(A), service conductors must have an ampacity of at least 125% of continuous load: 160 A x 1.25 = 200 A. 160 A ignores the factor, 128 A reduces the load, and 175 A is insufficient.
Trích dẫn luật: 2023 NEC §230.42Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- What is the minimum service disconnecting means rating for a one-family dwelling?
- The optional feeder/service calculation of 220.84 for a multifamily dwelling may be used only when which condition is met?
- A dwelling has 10 kW of electric heat and a 5 kW air conditioner that never run at the same time. What load is included in the calculation?
- What is the full-load secondary current of a 45 kVA, 3-phase, 208 V transformer?
- What is the full-load primary current of a 75 kVA, 3-phase, 480 V transformer?
- For a transformer over 1000 V or with primary-only protection under 450.3(B), where primary current is 9 A or more, the primary OCPD generally may not exceed what percentage of primary full-load current?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra