For a transformer over 1000 V or with primary-only protection under 450.3(B), where primary current is 9 A or more, the primary OCPD generally may not exceed what percentage of primary full-load current?
a.125%
b.300%
c.167%
d.250%
Giải thích
Table 450.3(B) permits primary-only protection at not more than 125% of rated primary current when that current is 9 A or more. 167%/250%/300% apply to higher-current or combined primary-and-secondary arrangements, not the basic 125% primary-only case.
Trích dẫn luật: 2023 NEC §450.3(B)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Service-entrance conductors must supply a computed load of 160 A continuous. What minimum conductor ampacity is required per 230.42?
- What is the full-load secondary current of a 45 kVA, 3-phase, 208 V transformer?
- What is the full-load primary current of a 75 kVA, 3-phase, 480 V transformer?
- A transformer has a primary full-load current of 40 A and uses primary-only overcurrent protection. What is the maximum standard primary OCPD (125% rule)?
- Conductors are connected to a transformer secondary without an OCPD at the secondary terminals. What set of rules governs their length and sizing?
- Why must ventilating openings of a dry-type transformer be kept clear of walls and obstructions?